Академический Документы
Профессиональный Документы
Культура Документы
AHU
The purpose of air distribution system is to create the proper combination of temperature, humidity and air velocity in the occupied zone of the conditioned room. If not properly designed, the air distribution system has the potential to compromise the comfort conditions it was designed to maintain.
Terminology
Diffusion temperature
Supply air to space air temperature difference is termed diffusion temperature. In the example, the room design temperature, Tr is 25 deg C. and the supply temperature Tla, is 13 deg.C, hence the diffusion temperature is ( 25 13) = 12 deg C.
Terminology
Induction, entrainment, or aspiration Involve mixing of room air with the supply air outside the occupied zone. Entrainment is defined as the movement of room air into the jet caused by the air stream discharged from the outlet (secondary air motion).
aspiration
Terminology
Throw (blow) and radius of diffusion The throw or blow and the radius of diffusion refer to the horizontal distance that the supply air travels before reaching a specified low velocity known as the terminal velocity. Generally, throw or blow refers to discharge from the sidewall outlet, and the radius of diffusion relates to the ceiling outlets.
TERMINOLOGY AHU
An air handler, or air handling unit (often abbreviated to AHU), is a device used to condition and circulate air as part of a heating, ventilating, and air-conditioning (HVAC) system. Usually, an air handler is a large metal box containing a blower, heating and/or cooling elements, filter racks or chambers, sound attenuators, and dampers. Air handlers usually connect to ductwork that distributes the conditioned air through the building, and returns it to the AHU. Sometimes AHUs discharge (supply) and admit (return) air directly to and from the space served, without ductwork.
Good room air distribution requires the following characteristics for comfort:Comfort is maintained through the change in seasons when the following conditions are maintained in the space occupied zone.
Air temp maintained between 73-77F RH maintained between 25-60% Maximum air motion in the occupied zone 1. Air velocities throughout the occupied zone (called residual velocities ) between 25 35 FPM for applications where people are seated. (FPM feet perminute) 2. Moving people are higher air velocities are acceptable ( 50 -70 FPM) Maximum temperature gradient (temperature fluctuation) 1-2 cooling 4 heating
Note: Occupied zone of most spaces is considered to be from the floor to an elevation of 6 ft. Above this height, greater temperature fluctuations are permissible
The effective draft temperature is evaluated at many locations throughout the space and comfort studies have shown that the effects of temperature and velocity on comfort will be acceptable if is kept between -3 and +2 F
Throw (T) - The maximum horizontal distance from the center of the air outlet to a point in the airstream where the air velocity has decayed (menyusut) to some arbitrary terminal velocity (typically 150, 100, and 50 fpm). The common unit of measure is feet (ft) Drop (D) - The vertical distance from an air outlet to the lower edge of a horizontally projected airstream envelope. The common unit of measure is feet (ft).
Air patterns
The are a few facts about how facts about how an air supply to a room will behave which are important to understand in order to select and locate air supply devices properly and to balance and adjust the devices. 1. When air lower temperature than room air is supplied (as in summer), it will drop. 2. When air higher in temperature than room air is supplied (as in winter), it will rise. 3. When air is supplied parallel to and near a ceiling, it will tend to hug the ceiling for some distance. This is called the ceiling or surface effect. 4. The supply air to the room ( called the primary air) when distributed from air supply device, will induce room air (called secondary air) into air stream, thus rapidly mixing the supply air and the room air.
Outlet location
High wall. This is a good location for cooling because the cold air will drop naturally and adequate air circulation throughout the occupied zone will occur. Ceiling. This is excellent location for cooling because the cold air will drop naturally. Low wall. This is a good location for heating because the warm air will rise naturally. Floor or sill. This is an excellent location for heating if located under windows, because it counteracts the cold air downdraft.
location
Floor or sill location under window for heating provides good air distribution
Circular Diffuser
The downward-jet pattern may be of benefit when the outlet is installed in a tall space and HVAC (heating, ventilation air conditioning) is in heating Mode The visualization Shows consequences for cooling mode
Square/Rectangular Diffusers
Square Diffuser
provides flexibility for distributing air in a variety of patterns
Slot Diffuser
Slot Diffuser
Outlet Selection and location procedure 1.Determine Air Volume Requirements & Room Size. In case more than one air outlet
is used, the total air flow rate needs to be divided by the number of outlets. = 1.2 = (3 /) = ( ) = ()
2.Select diffuser type and location within room. Considering factors as air quantity, distance available for throw, structural characteristics and architectural constraints. For example, if circular ceiling diffusers are to be used, each would be centred in a ceiling area that is roughly square in shape as the air is supplied in all directions from the diffuser. 3.Determine room characteristic length from table, L
ASHRAE Outlet Selection Steps 4.Select recommended throw to length ratio from the ADPI selection guide
6.Locate appropriate outlet size from mfgrs catalog. 7.Check static pressure & noise criteria
Example 1
Select a round ceiling diffuser for a room in an office building, as shown in below. The room, 4.2 m wide by 4.8 m long and with ceiling 2.4 m above the floor, is to be supplied with 120 litres/s of conditioned air. The room load was estimated to be 125 W/m2. A noise criteria (NC) of 20 -35 would be acceptable.
diffuser 4.2 m
4.8 m
Example 2
Specify circular ceiling diffusers for cooling a school room to be maintained at 25 deg. C. The cooling load for the room is 13.2 kW and the supply air temperature is 13 deg.C.
10 m
12 m