Presented By
ADVANTAGES OF FF
ADVANTAGES OF FF
ADVANTAGES OF FF
Two Types of FF Devices: Bus-Powered 32 Devices Devices take power from Bus Require 10-30 mA of current between 9 and 32 volts. Non Bus-Powered 16 Devices Devices take Power over Separate Wires
6
TOPOLOGIES OF FF NETWORK
FF can have different topologies in a network Bus Tree (Chicken-foot) Daisy-chain Point-to-point
BUS TOPOLOGY
TREE TOPOLOGY
10
11
12
H1 Physical Layer
14
15
The transmitting device delivers 10 mA at 31.25 kbit/s into a 50 ohm equivalent load to create a 1.0 volt peak-to-peak voltage modulated on top of the direct current (DC) supply voltage. The DC supply voltage can range from 9 to 32 volts. However, for Intrinsically Safe (I.S.) applications, the allowed power supply 16 voltage depends on the barrier rating
Total Trunk Length Repeaters ( Max) Segments ( Max) Max Spur Length
= 1900 m =4 =5 = 120 m
17
18
19
Reducing Noise
Each fieldbus segment must have exactly two terminators. Terminators located in the field should be installed in a junction box;
20
A terminator is used to prevent reflection at the ends of a field bus cable.This reflection is a form of noise that distorts the signal.
21
Lightning/Surge Protection
Surge suppression shall consist of lowcapacitance silicon avalanche diodes or spark gaps, wired for both normal- and common-mode protection, connected to the electrical safety ground grid.
22
All cables shall be single or multiple twisted pair with an individual shield for each pair. Multi-pair cables shall have an 23 additional overall shield.
24
25
26
Barriers
27
Galvanic Isolator
Maintains safety by having high integrity isolation that prevents the transmission of electrical surges or overloads from the safe to the hazardous area
28
29
30
31
Exi Barriers
Entity FISCO - Fieldbus Intrinsically Safe Concept FNICO - Fieldbus Non-Incendive Concept
32
33
35
FNICO
Fieldbus Non-Incendive Concept It is only applicable to Zone 2 (Division 2). FNICO puts the current limitation on the trunk without any further limitations on the spur.
36
37
38
39
41
A power supply impedance module prevents short circuit of communication signal by the power supply. The power supply impedance also regulates the power supply voltage.
If ordinary power supply is used it will absorb signals on the cable, as it will try to maintain a constant voltage level.
42
43
Thank You