Вы находитесь на странице: 1из 30

Introduction

Substation Types
Parts of
Substation
Major Components
Of Substation
Substatio
ns
When electricity leaves a power plant (1),
its voltage is increased at a step-up substation (2).
Next, the energy travels along a transmission line to the
area where the power is needed (3).
Once there, the voltage is decreased or stepped-down,
at another substation (4),
and a distribution power line (5)
carries the electricity until it reaches a home or business
(6).
A substation is a high-voltage electric system facility.
It is used to switch generators, equipment, and
circuits or lines in and out of a system. It also is
used to change AC voltages from one level to
another, and/or change alternating current to direct
current or direct current to alternating current.
Some substations are small with little more than a
transformer and associated switches. Others are
very large with several transformers and dozens of
switches and other equipment
Substation Types: Although, there are generally
four types of substations there are substations
that are a combination of two or more types.
Step-up Transmission Substation

Step-down Transmission Substation

Distribution Substation

Underground Distribution Substation

Substation Functions

Substation Equipment

A step-up transmission substation receives
electric power from a nearby generating facility
and uses a large power transformer to increase
the voltage for transmission to distant locations.
A transmission bus is used to distribute electric
power to one or more transmission lines. There
can also be a tap on the incoming power feed
from the generation plant to provide electric
power to operate equipment in the generation
plant.

A substation can have circuit breakers that are
used to switch generation and transmission
circuits in and out of service as needed or for
emergencies requiring shut-down of power to a
circuit or redirection of power.


The specific voltages leaving a step-up
transmission substation are determined by the
customer needs of the utility supplying power
and to the requirements of any connections to
regional grids. Typical voltages are:

High voltage (HV) ac:69 kV, 115 kV, 138 kV, 161
kV, 230 kVExtra-high voltage (EHV) ac:345 kV,
500 kV, 765 kVUltra-high voltage (UHV) ac:1100
kV, 1500 kVDirect-current high voltage (dc HV):
250 kV, 400 kV, 500 kV

Direct current voltage is either positive or negative
polarity. A DC line has two conductors, so one
would be positive and the other negative.
Step-down transmission substations are
located at switching points in an electrical
grid. They connect different parts of a grid
and are a source for subtransmission lines
or distribution lines. The step-down
substation can change the transmission
voltage to a subtransmission voltage,
usually 69 kV. The subtransmission
voltage lines can then serve as a source to
distribution substations. Sometimes,
power is tapped from the subtransmission
line for use in an industrial facility along
the way. Otherwise, the power goes to a
distribution substation.

Distribution substations are located near to
the end-users. Distribution substation
transformers change the transmission or
subtransmission voltage to lower levels for
use by end-users. Typical distribution
voltages vary from 34,500Y/19,920 volts to
4,160Y/2400 volts.

34,500Y/19,920 volts is interpreted as a
three-phase circuit with a grounded neutral
source. This would have three high-
voltage conductors or wires and one
grounded neutral conductor, a total of four
wires. The voltage between the three
phase conductors or wires would be
34,500 volts and the voltage between one
phase conductor and the neutral ground
would be 19,920 volts.

From here the power is distributed to
industrial, commercial, and residential
customers.

Underground distribution substations are
also located near to the end-users.
Distribution substation transformers
change the subtransmission voltage to
lower levels for use by end-users. Typical
distribution voltages vary from
34,500Y/19,920 volts to 4,160Y/2400
volts.


An underground system may consist of these parts:

Figure 10. Underground Distribution Substation
Conduits

Duct Runs

Manholes

High-Voltage Underground Cables

Transformer Vault

Riser

Transformers
From here the power is distributed to industrial, commercial, and residential customers.

Substations are designed to accomplish the following functions, although not all
substations have all these functions:
Change voltage from one level to another

Regulate voltage to compensate for system voltage changes

Switch transmission and distribution circuits into and out of the grid system

Measure electric power qualities flowing in the circuits

Connect communication signals to the circuits

Eliminate lightning and other electrical surges from the system

Connect electric generation plants to the system

Make interconnections between the electric systems of more than one utility

Control reactive kilovolt-amperes supplied to and the flow of reactive kilovolt-amperes in the
circuits

The major components of a typical substation are:

Air circuit breakers are used to interrupt
circuits while current flows through them.
Compressed air is used to quench the arc
when the connection is broken.

Batteries are used in the substation control
house as a backup to power the control
systems in case of a power blackout

Bus support insulators are porcelain or fiberglass insulators that
serve to isolate the bus bar switches and other support structures
and to prevent leakage current from flowing through the structure or
to ground. These insulators are similar in function to other insulators
used in substations and transmission poles and towers.

Capacitor Bank
Capacitors are used to control the level of
the voltage supplied to the customer by
reducing or eliminating the voltage drop in
the system caused by inductive reactive
loads.

Circuit switchers provide equipment
protection for transformers, lines, cables,
and capacitor banks. They also are used
to energize and deenergize capacitor
banks and other circuits.

Concrete foundations or pads are laid for
all large equipment, support structures,
and control buildings in a substation.

Conduits are hollow tubes running from
manhole to manhole in an underground
transmission or distribution system. They
can contain one or more ducts (See Duct
Runs). They can be made of plastic
(PVC), fiberglass, fiber, tile, concrete, or
steel. PVC and fiberglass are most
commonly used.

The substation control house contains
switchboard panels, batteries, battery
chargers, supervisory control, power-line
carrier, meters, and relays. The control
house provides all weather protection and
security for the control equipment. It is
also called a doghouse.

Control Panels
Control panels contain meters, control
switches and recorders located in the
control building, also called a doghouse.
These are used to control the substation
equipment, to send power from one circuit
to another or to open or to shut down
circuits when needed.
Control wires are installed connecting the
control house control panels to all the
equipment in the substation. A typical
substation control house contains several
thousand feet of conduit and miles of
control wire.

Converter stations are located at the terminals of a DC transmission line. Converter
stations can change alternating current into direct current or change direct current to
alternating current. Sometimes converter stations are located at a generation power
plant or at transmission substations. Two unsynchronized AC transmission systems
can be connected together with converter stations.

Converter stations are also found in most substations for converting the emergency
battery back-up system to AC power for use in an emergency.

Coupling capacitors are used to transmit communication signals to
transmission lines. Some are used to measure the voltage in
transmission lines. In signal transmission the coupling capacitor is
part of a power line carrier circuit as shown in the schematic below.
A coupling capacitor is used in this circuit in conjunction with a line
trap. Line traps can be installed at the substation or on a
transmission line tower.

Current Transformers
Current transformers can be used to supply information for
measuring power flows and the electrical inputs for the operation of
protective relays associated with the transmission and distribution
circuits or for power transformers. These current transformers have
the primary winding connected in series with the conductor carrying
the current to be measured or controlled. The secondary winding is
thus insulated from the high voltage and can then be connected to
low-voltage metering circuits.

Disconnect switches or circuit breakers are used to isolate
equipment or to redirect current in a substation. Many different types
of disconnect switches are shown below.
A distribution bus is a steel structure
array of switches used to route power
out of a substation.
A frequency changer is a motor-generator
set that changes power of an alternating
current system from one frequency to one
or more different frequencies, with or
without a change in the number of phases,
or in voltage. Sometimes a converter is
used to accomplish this.

High voltage fuses are used to protect the
electrical system in a substation from
power transformer faults. They are
switched for maintenance and safety.

Lightning arresters are protective devices for limiting surge voltages
due to lightning strikes or equipment faults or other events, to
prevent damage to equipment and disruption of service. Also called
surge arresters.

Lightning arresters are installed on many different pieces of
equipment such as power poles and towers, power transformers,
circuit breakers, bus structures, and steel superstructures in
substations.

Вам также может понравиться