Busbar System

FAST BUS
Applications / Customer Benefits
Description
Program Overview
How to Design a System
Product Tips
New Products
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 2/34
Space Saving Cost-effective Flexibility
8US Busbar Systems
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 3/34
60 mm Busbar System Basics
Open systems are most
common in the U.S
Completely compartmentalized
system is more common in Europe
Illustration:
3-pole +
wiring duct


Systems up to 600 A
Flat Profile insulating barrier
Required by UL in any installation
Possible scenario:
3-pole or 4-pole completely
compartmentalized system

Systems up to 1400 A
With TT Busbar and busbar holders
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 4/34
Busbar System Components
Busbar adapter
for complete direct feeders
Busbar Adapter and Device Holder
for complete reversing feeders
Busbar adapters for VL, ED or FXD FBCB Breaker Kits
Busbar adapters
for individual components
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 5/34
Busbar System Components
End Covers, Busbar Covers and Cover Profiles Busbar and Busbar Holders
Connection terminals Terminal Systems w/cover
PE / N Bus Bar Holders
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 6/34
Technical Data
Busbar dimension System Continuous current at a busbar temperature of
65C 85C 105C
mm mm A A A
20 x 5 60 274 362 430
25 x 5 60 327 432 513
30 x 5 60 379 500 595
20 x 10 60 427 564 670
30 x 10 60 573 756 900
TT profile 60 1020 1020 1600
Uninterrupted current for Busbars , E-Cu bare (at air temp. 35 C in acc. with DIN 43617)
Technical data for System
Rated insulation voltage 1000 V AC
Short-circuit strength
of the 8US device adapters of the busbar systems
Current limiting by means of associated
circuit-breakers/load feeders up to 50 kA
see Characteristic Curves
Material
of the 8US1 busbar supports, device adapters and device holders Fiberglass-strengthened polyamide
Color RAL 7035, light grey
Thermal stability
of the busbar supports, device adapters and device holders 120 C
of the AWG connection leads 105 C
of the cover profiles and end covers 70 C
Approvals
Busbar supports, device adapter, device holders and terminals UR, CSA
Busbar System
FAST BUS
Applications / Customer Benefits
Description
Program Overview
How to Design a System
Product Tips
New Products
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 8/34
The Fast Bus system
Fast Bus is a
3-phase busbar
system for power
distribution.


The modular design
provides the
flexibility needed to
fit your application.


Fast Bus also
carries domestic and
international
approvals, which
make it ideal for one
global panel design.
The Fastbus system can help you save
panel space by allowing you to wire and
mount circuit protection and motor
starters in a tight line.
Leave space for future
system expansion. Covering
all exposed bus bars with
the plastic profile.
Fastbus helps provide for efficient assembly and simple maintenance, reducing down
time..
Adapter shoes can be easily snapped on or removed from the Busbars in seconds and
many of the starters and circuit breakers come pre-assembled from Siemens.
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 9/34
The Fast Bus system and UL508A

Feeder circuit is the circuit section located upstream from the last short-circuit-proof element
(short circuit protection device = SCPD).

Branch circuit is the circuit section located downstream from the last short-circuit-proof element.

Clearance

Creepage distance
Between phases

50.8 mm (2 inches) 25.4 mm (1 inch)
Between phases and grounded,
non-isolated metal parts
25.4 mm (1 inch) 25.4 mm (1 inch)
Clearance and creepage distances in acc. with UL508A in the feeder circuit (rated voltage 251- 600V):
When using the Fast Bus busbar system in a power distribution board erected in accordance with UL
regulations, it has to be checked whether the application is located in the Feeder or Branch circuit.

Components used in the Feeder circuit require larger clearance and creepage distances than in the
branch circuit.
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 10/34
The Fast Bus system
Current Ratings for standard busbar
1)

5 x 20 mm copper busbar - 362 Amps @ 600V

5 x 25 mm copper busbar - 432 Amps @ 600V


5 x 30 mm copper busbar - 500 Amps @ 600V


10 x 20 mm copper busbar - 564 Amps @ 600V


10 x 25mm copper busbar 660 Amps @ 600V


10 x 30 mm copper busbar - 756 Amps @ 600V
TT Profile copper busbar - 1020 Amps @ 600V
2)

1) When using 8US1923-3UA01, FBS400F, FBB60F and FBSXPF Busbar Supports at 85C
2) When using 8US1943-3AA00
Bracing ratings
1)

65kA
3)
bracing ratings at 480V at max 600A w/ 24 between supports
35kA
3)
bracing ratings at 600V at max 600A w/ 24 between supports

3) SCCR for 5mm x 20mm and 10mm x 20mm busbars

Factory assemblies for quick installation
SIRIUS 3RA Combination Starters (direct & reversing) up to 75HP @ 460V
Sentron ED & FXD Circuit Breakers (UL489) up to 250A
Customer assemblies for quick installation
SIRIUS 3RA6 Compact Starters up to 20HP @ 480V
Siemens VL: DG, FG, JG, LG Circuit Breakers (UL489) up to 600A


3RA
3RA6
ED & FXD
VL
Busbar System
FAST BUS
Applications / Customer Benefits
Description
Program Overview
How to Design a System
Product Tips
New Products
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 12/34
Applications
Group Installation
according to NEC 430.53
One of the most common uses
for Fastbus is multi-motor
applications.

Fastbus offers a great solution
when applied in accordance
with National Electric Code
section 430.53.

We offer a full line of Main
Circuit Breakers from 100 A to
250 A mounted on Fastbus
shoe adapters.

Since our 3RV Motor Starter
Protectors are listed for Group
Installation they eliminate the
need for an additional branch
circuit protector for each motor

Main Circuit
Breaker feeding
the Busbar
Assembly sized
according to
NEC 430.52
3RA11 Combination
Starters can be used
for Single Motor Taps
in accordance with
NEC 430.53 (D) (3)
since the 3RV Manual
Motor Controllers are
labeled Suitable for
Tap Conductor
Protection in Group
installations as well
as Listed for Type E
when using the
3RV1928-1H or
3RT1946-4GA07
Busbar
cover for
covering
open Busbar
Branch
Circuit
Breaker for
Power
Transformer
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 13/34
Applications
The Fastbus System
reduces installation
time and cost by
improving mounting
density in panels and
speeding up installation
time with faster
mounting and fewer
power connections
Ideal for Large Systems
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 14/34
Applications
Here is a good
example of how to
control multiple motor
loads using Fastbus
Multiple Busbar runs can
be connected by using any
one of six different 3-pole
Lug Plate assemblies.
(see ratings)
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 15/34
Initial Build Cost Savings
Preassembled starters save labor
More condensed panel design
Future Expansion Cost Savings
Mean Time To Repair Savings
Technical Benefits
Customer Benefits
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 16/34
Commercial Savings: Panel Build Labor
* Information taken from Customer case study
Standard Panel
Install 3 Fuse blocks 1.5 Hours
Install Starters 1.5 Hours
Install Disconnect 0.5 Hours
Install PDB 0.5 Hours
Install Plexiglas 1.0 Hours

Total 5 Hours



At $30/Hour Savings of $90 per Panel
SIEMENS Panel

Install Busbars 1.0 Hour
Install Starters 0.5 Hours

Install Breaker 0.5 Hours

Total 2 Hours



Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 17/34
Commercial Savings: Panel Space
2 INCHWIRING DUCT
3

I
N
C
H

W
I
R
I
N
G

D
U
C
T
5"
M AIN
CIRCUIT
BREAKER
2 INCHWIRING DUCT
21"
40 HP
3
HP
34"
23"
3

I
N
C
H

W
I
R
I
N
G

D
U
C
T
FBCB100M

3
R
A
1
1
1
5
-
1
G
D
1
5

3
R
A
1
1
1
5
-
1
E
D
1
5

3
R
A
1
1
4
0
-
4
J
D
4
4 1.5
HP
100 AM P S
1.5 HP
5"
2 INCHWIRINGDUCT
19"
23"
2 INCHWIRINGDUCT
JTN60030
J60100-3COR
BLOCK
40 HP
3 HP
26"
3

I
N
C
H

W
I
R
I
N
G

D
U
C
T
3

I
N
C
H

W
I
R
I
N
G

D
U
C
T
PWR. DIST.
* Information taken from Customer case study
Standard Panel
SIEMENS Panel
Busbar System
FAST BUS
Applications / Customer Benefits
Description
Program Overview
How to Design a System
Product Tips
New Products
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 19/34
How to Configure Fast Bus for Group Installation

1. Determine Required Load
2. Select Method to Power Fastbus
Main lug up to 600A
Circuit breakers, 15A to 500A
3. Select any additional circuit breakers or lugs to feed non-motor loads or
motors greater than 100A.
4. Select 3RA Combination, Compact Starters, or individual starter components
for each motor load.
5. Select Additional Fastbus Adapters for other control components
6. Determine the required length of busbar based on component widths and plan
for expansion space.
7. Select appropriate length busbar, busbar supports, end covers and any other
required components.
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 20/34
Step 1 Determine total amperage of required loads

Due to the nature of Fast Bus, most applications are
considered Group Installation per NEC 430-53

Group Installation is an approach to building multiple motor
control systems. In Group Installation, multiple motor
starters can be grouped under a short circuit protective
device. The 3RA Combination Starters have been UL
listed for Group Installation in conjunction with Fast Bus.

Circuit Breaker Selection - Select a circuit breaker (CB) between:

Minimum CB size (per NEC430-110) = Sum of all motor Full Load Currents x 115%
Maximum CB size (per NEC430-53c) = 250% x FLC of the largest motor + FLC of all other motors
Fuse Selection - Calculate the maximum fuse size per NEC 430-53c:

Maximum Fuse size = 175% x FLC of the largest motor + FLC of all other motors
A. Review the specification or line drawing to determine all of the loads in the circuit
B. Use the calculations below to determine the size to the Short Circuit Protective Device
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 21/34
Step 2 Select Method to Power Fast Bus
For Short Circuit Protection from 50 to 250A, we recommend
using the FBCB***M Main Circuit breakers kits

These circuit breakers have the Fast Bus wires on the load side.
Incoming power wires can be fed through the top of the enclosure
directly to the line terminals of the circuit breaker. A Rotary or Max-
Flex handle operator can be added to disconnect and lock the breaker
in the off position.

For Short Circuit Protection from up to 500A, we offer the VL
Circuit breakers on Fast Bus Adapters see slide 30
These Fast Bus adapters offer user flexibility in making electrical
connections on the line or load side of the breaker.

For Short Circuit Protection greater than 500A, use the Three
Pole Lug Plate assembly with cover

Provides terminals for the incoming supply from a separately mounted
Circuit Breaker or Fuse Block. These lug kits could also be used to
jumper from one run of Fast Bus to another.

Panel mount circuit breaker or fuse block over 500A

Breaker Rating Width SCCR
480V
FBCB050M 50A 140mm 25kA
FBCB060M 60A 140mm 25kA
FBCB070M 70A 140mm 25kA
FBCB090M 90A 140mm 25kA
FBCB100M 100A 140mm 65kA
FBCB125M 125A 140mm 65kA
FBCB150M 150A 140mm 65kA
FBCB175M 175A 140mm 65kA
FBCB200M 200A 140mm 65kA
FBCB225M 225A 140mm 65kA
FBCB250M 250A 140mm 65kA

Add HB to above (eg. FBCB250M-HB)
for High Interrupting versions 100A-
250A only. (see next slide)
Lug Kit Rating Width SCCR
480V
FBT600F 560A 180mm 65kA


Feeder Circuit Compliant

Other ratings available
See page 5/6 of the 2010 Controls
Catalog


Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 22/34
Step 3 Choosing additional CBs
Pre-assembled on Shoes or Kits ready to go
Item Number Suffix Description:
Blank = Feeder or Branch Circuit with adaptor terminals at the top
H: = Feeder or Branch Circuit Higher Interrupt with adaptor terminals at the top
M: = Main Circuit Breaker with adaptor terminals at the bottom
M-HB: = Main Circuit Breaker w/ higher interrupt and adaptor terminals at the bottom
Feeder CB
Main CB
1. These ratings apply to circuit breaker shoes used either as feeder circuit breakers
(power taken from the load side of the circuit breaker to other equipment) or main circuit
breakers (power applied to the bus from the circuit breaker).
2. Kits are pre-assembled up to 90A. Kits above 90A
require shoe to be torqued to busbar prior to assembly.
3. Circuit Breakers are 80% rated.
4. Interrupt ratings based on Circuit Breaker.
Notes:
Sentron Ratings
Breaker (A)
Frame 480V Max 600V Max
FBCB015 - 125 ED 15-125 25 18
FBCB150 FXD 150 35 22
FBCB175 FXD 175 35 22
FBCB200 FXD 200 35 22
FBCB225 FXD 225 35 22
FBCB250 FXD 250 35 22
FBCB020H - 080H HHED 20-80 65 18
FBCB50M - 90M ED 50-90 25 18
FBCB100M FXD 100 65 25
FBCB125M FXD 125 65 25
FBCB150M FXD 150 65 25
FBCB175M FXD 175 65 25
FBCB200M FXD 200 65 25
FBCB225M FXD 225 65 25
FBCB250M FXD 250 65 25
FBCB100M-HB HHED 100 65 25
FBCB125M-HB HHED 125 65 25
FBCB150M-HB HFXD 150 65 25
FBCB175M-HB HFXD 175 65 25
FBCB200M-HB HFXD 200 65 25
FBCB225M-HB HFXD 225 65 25
FBCB250M-HB HFXD 250 65 25
Short Circuit Ratings
Item Number Current (kA)
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 23/34
Step 4 Select Combination Starters
Fully assembled Starters:
Non-reversing or reversing motor?
Full Load Current of the motor?
Control Voltage?
Number of auxiliary contacts required on the MSP and on the
Contactor?
The 3RA devices can be ordered without any auxiliaries or they can
be ordered with one SPDT contact block that plugs into the top
front of the MSP and one NO contact block that mounts to the front
of the contactor
We recommend using front mount or plug in auxiliary contact
blocks to keep the device width to a minimum
Regardless of which version is ordered, additional auxiliary
contacts can always be added in the field

These starters can also be built from stock components:
For quick component selection, use Section 4 of the catalog to
select a 3RA factory assembled version. To the right of the 3RA
catalog number, you will find a list of the components required for
field assembly
To see a detailed visual of how to assemble these starters, refer to
pages 4/63 through 4/68 of the 2010 catalog.
Starter Selection Process
Non-reversing Width
3RA111 45 mm
3RA112 45 mm
3RA113 55 mm
3RA114 72 mm
Reversing Width
3RA121 90 mm
3RA122 100 mm
3RA123 120 mm
3RA124 150 mm
Pages 4/38 4/41
Pages 4/46 4/49
Non-Reversing 480 VAC 600 VAC
3RA111 65KA 10kA
3RA112 65KA 25kA
3RA113 65KA 65kA
3RA114 65KA 65kA
Reversing 480 VAC 600 VAC
3RA121 65KA 10kA
3RA122 65KA 25kA
3RA123 65KA 65kA
3RA124 65KA 65kA
UL SCCR's

Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 24/34
Step 5
Select Additional Fastbus Adapters for other control components


Adapters for Sirius:
101 (S00)and 102 (S0) frame size 25A rated:
8US1251-5DM07 (45 x 182mm)
8US1250-5AM00 (45 x182mm)

103 (S2) frame size 50A rated:
8US1261-5FM08 (55 x 182mm)
8US1260-5AM00 (55 x 182mm)

Long adapter for combination starters:
8US1261-5FP08 (55 x 242mm)
8US1260-5AP00 (55 x 242mm)

104 (S3) frame size:
8US1211-4TR00 (70A rated, 72mm x 215mm)
FBS10072 (100A rated, supplied w/o wires, with DIN, 72mm x 200mm)



The 8US Fastbus system offers Adapter Shoes in various sizes so that you can customize your own Fastbus
assembly to your application. Some Adapter Shoes come pre-wired and some without wire so that you can size
the wire to your needs or attach to another adapter to mount a connecting device.
8US1260-5AM00
8US1251-5DM07
8US1211-4TR00
Note: It is not recommended to build your own circuit breaker assemblies
as Siemens offers these as kits that include the appropriate brackets and mounting hardware.
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 25/34
Step 6 Determine the Required Length of Busbar

Add the widths of all components that will be mounted to the busbar. Including:
End Supports and Intermediate Supports
Main Circuit Breaker or Main Lug Kit
3RA Combination Starters
Feeder Circuit Breakers
Feeder Lug Kits
Adapters to hold other control products

Determine what additional length may be required for future expansion (if any).
Specify required bracing rating for the system to determine if and how many intermediate
supports are required.
Add the widths of all intermediate supports and end supports, which are 21 mm each.
Add all distances together to determine total length of busbar required.


NOTE:
Make sure that the required busbar length will fit in your control panel. If necessary, break the Fast Bus in to multiple runs
within the cabinet. When breaking in to additional runs, be sure to add the additional end & intermediate supports and any
additional Feeder Lug Kits or Circuit Breakers to your overall length calculation.
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 26/34
Step 7 Selection of Bus Bar Components

Mounting Components Required for compliance with UL 508A:
1. Bus Bar End and Intermediate Support
A. 8US1923-3UA01 (bus bar holder support end & intermediate)
B. 8US1922-1AC00 (end cover)
2. Busbar Choices:
A. FBB36 / FBB60
Qty.(3) 36 inches long x 5mm x 20mm Tinned Copper Busbar
Qty.(3) 60 inches long x 5mm x 20mm Tinned Copper Busbar

B. Tin plated Copper Busbar (for bare copper contact Siemens)
8WC5120 6mm x 6mm x 2m (78.74) for PE/N application up to 135A
8WC5053 5mm x 20mm x 2m (78.74)
8WC5054 5mm x 25mm x 2m (78.74) (note: can be double stacked = 660A Ampacity)
8WC5055 5mm x 30mm x 2m (78.74)
8WC5063 10mm x 20mm x 2m (78.74)
8WC5065 10mm x 30mm x 2m (78.74)
8US1948-2AA00 TT busbar 720mm
2
x 2.4m (94.49)

Optional Components depending on specifications:
Ground Busbar Holder
8US1923-1AA01 (mounts separately from 8US1923-3UA01 Bus Bar Holder)
Allows use of 5mm x 20mm to 10mm x 30mm busbars as well as
6mm x 6mm busbar
Choice of busbar determines ratings
Busbar System
FAST BUS
Applications / Customer Benefits
Description
Program Overview
How to Design a System
Product Tips
New Products
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 28/34
Changes in Basic Construction to ensure UL508A Compliance
1. Always specify 8US1922-1AC00 End Cover with
8US1923-3UA01 Busbar Holders. Do not use FBS400F
or FBSXPF in new designs. The 8US1923-3UA01
Busbar Holder also acts as the intermediate support.

2. Always specify 8US1922-2UA01 (Flat Insulator base)


3. Edge profile is not common in U.S. Do not specify as
part of a design if the customer does not request it.

4. No changes

5. Do not use the 5SH3532 top cover and 5SH3533 side
cover combination which is what is comprised with the
FBS400F. This rounded cover is made specifically for
mounting the 3 edge profile.

See next slide for more detail
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 29/34
Product Tips for UL508 Installations
Use Flat Base insulation panel
8US1922-2UA01
Use 3-pole, Busbar Holder for flat busbars
20x5 mm, to 30x10 mm for end and intermediate
supports. No top cover reqd.
8US1923-3UA01
Use side cover on end busbar supports for 5-10mm
busbars 8US1922-1AC00

For TT Busbar use:
8US1943-3AA00 Busbar Holder with End Cover

Use PE / N Busbar Holder as reqd
Mounts separately from 3-phase holder. Accepts 6x6mm
and 20x5 mm, to 30x10 mm busbars
8US1923-1AA01 (new) or 5SH3506 (phase-out)
Notes:
FBS400F is no longer required to Meet UL508A and will
be discontinued. This kit contains the busbar holders,
top and side covers. The top cover is intended for
accepting the top or bottom edge profiles.
FBSXPF is no longer required to Meet UL508A and will
be discontinued. This kit contains the intermediate
busbar holder and top cover. The top cover is intended
for accepting the top or bottom edge profiles.


Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 30/34
Product Tips for VL Shoes up to 500A
8US1213-4AQ03 105mm wide 150A-250A Shoe + hardware for VL DG and FG frame
Breaker - Feeder or Main Circuit Breaker. Requires (1) 3VL9300-8SA40 metric mounting
screws (4pcs set) to be ordered separately. For FG frame, CB shall not be marked for
100% continuous current. Note: Accepts Max Flex Flange Disconnects but requires
additional screw set 3VL9300-8SE20.

8US1213-4AH00 140mm wide 400A-540A Shoe + hardware for VL JG and LG frame
Breaker - Feeder or Main Circuit Breaker. Requires (1) 3VL9500-8SA40 metric mounting
screws (4pcs set) to be ordered separately. LG frame for use with Elec. Trip unit max rated
400A or for use with thermal MAG trip unit max rated 500A. Note: Accepts Max Flex
Flange Disconnects but requires two M6 x 120mm screws. Contact Product
Management for part number.
Bus Bar Shoe
For use with
30x10mm and TT
busbar only
Current
Rating
UL Short Circuit ratings
240 VAC 480 VAC 600 VAC 600Y /
347 V
250
VDC
500
VDC
8US1213-4AQ03

600V 250A 200kA 100kA 25kA - 30kA

30kA
8US1213-4AH00

600V 540A 200kA 100kA 25kA - 35kA 35kA
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 31/34
Product Tips
40mm vs. 60mm Designs:
To clarify North American design requirements, 60mm center to center systems are approved
in the U.S. whereas 40mm systems are not and are predominantly for European systems. For
40mm system components, refer to the LV1 catalog chapter 17 for Fast Bus.
UL Panel Inspection Update:
The use of Fast Bus components must be described under the Panel Builders Procedure
documentation for UL inspection. For all current and future projects, please be sure to provide
a copy of the Siemens UL report E160776 Vol 1 Sec 1.

Busbar System
FAST BUS
Applications / Customer Benefits
Description
Program Overview
How to Design a System
Product Tips
New Products
Siemens Industry, Inc 2010 - Subject to modifications
Industrial Automation Busbar Systems Fast Bus
2010-03 Slide 33/34
NEW 5SH3538
80A Connection Module
Feed components off the
bus or another rung of
bus bar up to 80A
Wires feed to bottom
only
Spring loaded terminals
3 pole
16 4 AWG cables
See page 5/6 of the 2010 Controls catalog
Busbar Systems
SIVACON 8US
Thank you