Under the guidance of Sri S.S.Tulasiram Das Garu Professor in EEE Dept by M.Dorababu Roll No. 11012D4302 The most common power quality problems are voltage sags , harmonic distortion and low power factor Voltage sags is caused by fault in the Distribution system Harmonic currents in the distribution system will cause harmonic distortion , low power factor & additional losses as well as heating of electrical equipment. Different ways to enhance power quality problems in transmission and distribution systems. D-Statcom is the most effective device used for enhancement of power quality in transmission & Distribution systems PWM based control scheme is used for control of electronic valves in the D-STATCOM The D-Statcom injects a current in to the system to mitigate the voltage sag. LCL Passive Filter is added to D-STATCOM to improve harmonic distortion and low power factor
The objective is Voltage sags are mitigated by inserting D- STATCOM in the Distribution System By adding LCL passive filter to D-STATCOM the harmonic distortion is reduced & power factor increase close to unity.
Statcom requires some amount of energy storage to accommodate harmonic power and AC system unbalances
Statcom equivalent circuit D-Statcom :
I L = Load current Is = Source current Vth = Thevenin Voltage V L = Load voltage Z th = impedance Iout = IL- IS = IL- (Vth-VL) / Zth
The output current ( I out) from the D-STATACOM will correct the voltage sags by adjusting the voltage drop across the system impedance ( Z th = R+ j X)
Voltage sag correction with D- Statcom depends on: The value of impedance : ( Zth = R+ j X ) The fault level of load bus
The shunt injected current I sh corrects the voltage sag by adjusting the voltage drop across the system impedance Z th .
The value of I sh can be controlled by adjusting the output voltage of the converter
The switching frequency is set at 475 Hz
D STATACOM( Distribution Static Compensator):
The D-STATCOM is the voltage-sourced inverter that converts an input dc voltage into a three-phase output voltage at fundamental frequency. It consist of i) Voltage source converter (VSC) ii)DC energy storage device iii) Controller iv) Coupling Transformer
Voltage source converter (VSC): a) It is a power electronic device which can generate a sinusoidal voltage with any required magnitude, frequency & phase angle. b) The VSC is used to either completely replace the voltage or to inject the missing voltage. c) The missing voltage is the difference between the nominal voltage and the actual.
d) It converts the DC voltage across the storage device in to a set of three phase ac out put voltages. e) These voltages are in phase and coupled with the ac system through the reactance of the coupling transformer. f) Suitable adjustment of the phase and magnitude of the D- STATCOM output voltages allows effective control of active and reactive power exchanges between the D-STATCOM and the ac system g) This configuration allows the device to absorb or generate controllable active and reactive power.
The VSC connected in shunt with the ac system which can be used for up to three quite distinct purposes: 1. Voltage regulation and compensation of reactive power; 2. Correction of power factor; and 3. Elimination of current harmonics.
Operation principle of the voltage source rectifier:
The voltage source rectifier operates by keeping the dc link voltage at a desired reference value, using a feedback control loop To accomplish this task, the dc link voltage is measured and compared with a reference VREF The error signal generated from this comparison is used to switch the six valves of the rectifier ON and OFF In this way, power can come or return to the ac source according to dc link voltage requirements Voltage VD is measured at capacitor CD When the current ID is positive (rectifier operation), the capacitor CD is discharged, and the error signal ask the Control Block for more power from the ac supply.
The Control Block takes the power from the supply by generating the appropriate PWM signals for the six valves.
In this way, more current flows from the ac to the dc side, and the capacitor voltage is recovered.
Inversely, when ID becomes negative (inverter operation), the capacitor CD is overcharged, and the error signal asks the control to discharge the capacitor and return power to the ac mains.
The PWM control not only can manage the active power, but also reactive power, allowing this type of rectifier to correct power factor.
The ac current waveforms can be maintained as almost sinusoidal, which reduces harmonic contamination to the mains supply.
V i : effective output voltage of the D-STATCOM & :power angle & Vs: System voltage.
The D-STACOM employs an inverter to convert the DC link voltage Vdc on the capacitor to a voltage source of adjustable magnitude and phase.
The inductance(L) and resistance(R)represents the equivalent circuit elements of the step-down transformer and the inverter is the main component of the D-STATCOM
The controller of the D STATCOM is used to operate the inverter in the phase angle between the inverter voltage and the line voltage is dynamically adjusted so that the D-STATCOM generates or absorbs the desired VAR at the point of connection. If Vi is equal to Vs, the reactive power is zero and the D-STATCOM does not generate or absorb reactive power No-load mode (Vs = Vi)
When Vi is greater than Vs, the DSTATCOM shows an inductive reactance connected at its terminal. The current, I, flows through the transformer reactance from the D-STATCOM to the ac system, and the device generates capacitive reactive power
If Vs is greater than Vi, the D-STATCOM shows the system as a capacitive reactance. Then the current flows from the ac system to the D-STATCOM, resulting in the device absorbing inductive reactive power
PWM Generator Pulses Uref W in_ref data PI Mag
abc
Phase 1
1 - + CONTROLLER SYSTEM Control Block Sequence analyzer Constant Te ln1
Phase-Modulation of the control signal The sinusoidal signal Vcontrol is phase-modulated by means of the angle VA = Sin (t +) VB= Sin(t+-2/3) VC = Sin (t ++2/3)
Proportional-integral controller (PI Controller) is a feedback controller which drives the system to be controlled with a weighted sum of the error signal (difference between the output and desired set point) and the integral of that value PI controller will process the error signal to zero The load r.m.s voltage is brought back to the reference voltage by comparing the reference voltage with the r.m.s voltages that had been measured at the load point PWM generator will generates the Sinusoidal PWM waveform or signal. It produces the desired synchronizing signal that required The modulated signal is compared against a triangle signal in order to generate the switching signals for VSC valves
Energy Storage Circuit:
DC source is connected in parallel with the DC capacitor It carries the input ripple current of the converter and it is the main reactive energy storage element DC capacitor could be charged by a battery source or could be recharged by the converter itself.
LCL Passive Filter: LCL Passive filter is used reducing harmonic distortion
Lg = En / 26iripm fsw Lc = Lg / 2 C= (L+Lg ) / L Lg (2f res ) 10 f n f res 0.5 f sw
Start Design distribution system using MATLAB SIMULINK Create distortion by inserting different types of faults Analyze the result from scope Vary the value of fault resistance Is the voltage sag>0.9p.u PF>0.9 Is the THD below 5% Run the simulation between 0-1s end Inject D-STATCOM into distribution system Add LCL passive filter Flow Chart Yes Yes No No TEST SYSTEM SIMULINK DIAGRAM WITHOUT D-STATCOM Different Types of faults : i)Three phase to ground fault (TPG) ii) Double line to ground fault (DLG) iii) Line to line fault (LL) iv) Single line to ground fault (SLG) Fault resistance(Rf) :0.66 Three phase to ground fault (TPG) Fault resistance(Rf) :0.66 Double line to ground fault (DLG) Time in sec Vpu Vpu Time in sec Fault resistance(Rf) :0.66 Line to line fault (LL) Fault resistance(Rf) :0.66 Single Line to Ground fault (SLG) Vpu Vpu Time in sec Time in sec
Results of voltage sags for different types of fault without D- Statcom Fault Resistance (Rf) Voltage sag for TPG fault (p.u) Voltage sag for DLG fault (p.u) Voltage sag for LL fault (p.u) Voltage sag for SLG fault (p.u) 0.66 0.6600 0.7070 0.7587 0.8259 0.76 0.7107 0.7487 0.7918 0.8486 0.86 0.7515 0.7833 0.8210 0.8679
SIMULINK DIAGRAM WITH D-STATCOM Fault resistance(Rf) :0.66 Three phase to ground fault (TPG) Fault resistance(Rf) :0.66 Double line to ground fault (DLG) Vpu Vpu Time in sec Time in sec Fault resistance(Rf) :0.66 Line to line fault (LL)
Fault resistance(Rf) :0.66 Single Line to Ground fault (SLG) Vpu Vpu Time in sec Time in sec
RESULTS OF VOLTAGE SAGS FOR DIFFERENT TYPES OF FAULT WITH D-STATCOM Fault Resistance (Rf) Voltage sag for TPG fault (p.u) Voltage sag for DLG fault (p.u) Voltage sag for LL fault (p.u) Voltage sag for SLG fault (p.u) 0.66 0.9367 0.9800 1.0168 0.9837 0.76 0.9450 0.9806 1.0142 0.9817 0.86 0.9543 0.9858 1.0152 0.9863 Type of fault Without D- STATCOM (p.u) With D- STATCOM (p.u) Percentage of improvement (%) TPG 0.6600 0.9367 29.65 DLG 0.7070 0.9800 27.85 LL 0.7587 1.0168 25.38 SLG 0.8259 0.9837 16.06 RESULTS FOR DIFFERENT TYPES OF FAULTS BEFORE AND AFTER INSERTION OF D- STATCOM HARMONIC SPECTRUM OF OUTPUT CURRENT WITH OUT LCL PASSIVE FILTER OUTPUT CURRENT WITHOUT LCL FILTER Wave form of spectrum distortion output current without LCL passive filter for Three Phase to Ground fault Number of harmonic spectrum Harmonic distortion of TPG fault% Harmonic distortion of DPG fault% Harmonic distortion of LL fault% Harmonic distortion of SLG fault% 1 st 100.00 100.00 100.00 100.00 3 rd 61.57 86.09 42.52 47.22 5th 1.98 1.84 1.55 1.73 7 th 13.43 17.38 10.27 8.28 9 th 5.98 8.53 5.00 3.56 11 th 1.21 2.95 2.10 0.95 13 th 5.29 6.92 3.55 3.36 15 th 0.84 0.74 0.62 0.61 17 th 1.75 2.84 1.71 1.14 19 th 1.90 2.54 1.33 1.24 THD 63.63 88.68 44.52 48.27 Power factor 0.84 0.75 0.91 0.90 The above table shows the current harmonic for different types of faults without filter The percentage of THD shows that , it is not within the IEEE STD 519-1992. The percentage of power factor is low in the range of 0.75 to 0.91 lagging. Results of current harmonic for different types of faults without LCL passive filter HARMONIC SPECTRUM WITH LCL FILTER OUTPUT CURRENT WITH LCL FILTER
Wave form of Spectrum of out put current with LCL passive filter for Three Phase to Ground fault Number of harmonic spectrum Harmonic distortion of TPG fault% Harmonic distortion of DLG fault% Harmonic distortion of LL fault% Harmonic distortion of SLG fault% 1 st 100.00 100.00 100.00 100.00 3 rd 0.80 0.81 0.43 0.83 5th 0.41 0.42 0.16 0.42 7 th 0.29 0.30 0.13 0.32 9 th 0.23 0.24 0.13 0.28 11 th 0.19 0.19 0.08 0.20 13 th 0.16 0.16 0.07 0.17 15 th 0.14 0.14 0.05 0.14 17 th 0.12 0.12 0.05 0.12 19 th 0.11 0.11 0.04 0.11 THD 1.11 1.12 0.65 1.15 Power factor 0.99 0.99 0.99 0.99 The below table shows that with LCL passive filter the percentage of THD has reduced . Now the THD is within IEEE STD 519-1992. The percentage of power factor increases close to unity.
Results of current harmonic for different types of faults with LCL passive filter
From the above results it is concluded that the voltage sags are mitigated by inserting D-STATCOM in to the distribution system. By adding LCL passive filter to D-STATCOM, the total harmonic distortion (THD) is reduced within the IEEE STD 519-512. The power factor also increases close to unity. Hence it is concluded that by adding D- STATCOM with LCL filter the power quality is improved.