GE Consumer & Industrial
Protection Fundamentals
By
John Levine
2
GE Consumer & Industrial
Outline
Introductions
Tools
Enervista Launchpad
On Line Store
Demo Relays at Levine
ANSI number
Training CDs
Protection Fundamentals
3
GE Consumer & Industrial
Objective
We are here to help make your job easier.
This is very informal and designed around
Applications. Please ask question. We
are not here to preach to you.
The knowledge base in the room varies
greatly. If you have a question, there is a
good chance there are 3 or 4 other people
that have the same question. Please ask
it.
4
GE Consumer & Industrial
Tools
5
GE Consumer & Industrial
6
GE Consumer & Industrial
7
GE Consumer & Industrial
Relays at L-3
8
GE Consumer & Industrial
9
GE Consumer & Industrial
10
GE Consumer & Industrial
ANSI Symbols
11
GE Consumer & Industrial
Conversion of Electro-Mechanical
to Electronic sheet
12
GE Consumer & Industrial
13
GE Consumer & Industrial
Protection Fundamentals
14
GE Consumer & Industrial
16
GE Consumer & Industrial
Types of Protection
Overcurrent
Uses current to determine magnitude of fault
Simple
May employ definite time or inverse time curves
May be slow
Selectivity at the cost of speed (coordination stacks)
Inexpensive
May use various polarizing voltages or ground current
for directionality
Communication aided schemes make more selective
20
GE Consumer & Industrial
CTI
50
+2
Distribution
Substation
50
+2
21
GE Consumer & Industrial
(TOC) Coordination
Relay closest to fault operates
first
Relays closer to source
operate slower
Time between operating for
same current is called CTI
CTI
Distribution
Substation
22
GE Consumer & Industrial
23
GE Consumer & Industrial
Multiples of pickup
24
GE Consumer & Industrial
Types of Protection
Differential
current in = current out
Simple
Very fast
Very defined clearing area
Expensive
Practical distance limitations
Line differential systems overcome this using
digital communications
26
GE Consumer & Industrial
1 pu
IP
CT-X
IP
CT-Y
IS
IS
Relay
IR-X
IR-Y
+1
Current, pu
1 + (-1) = 0
0
-1
Differential
Note CT polarity
dots
This is a
through-current
representation
Perfect
waveforms, no
saturation
DIFF CURRENT
27
GE Consumer & Industrial
2 pu
2 pu
Fault
IP
CT-X
IP
CT-Y
Differential
X
IS
IS
Relay
IR-X
IR-Y
+2
Current, pu
2 + (+2) = 4
0
-2
DIFF CURRENT
Note CT
polarity dots
This is an
internal fault
representation
Perfect
waveforms, no
saturation
28
GE Consumer & Industrial
Types of Protection
Voltage
Uses voltage to infer fault or abnormal condition
May employ definite time or inverse time curves
May also be used for undervoltage load shedding
Simple
May be slow
Selectivity at the cost of speed (coordination stacks)
Inexpensive
29
GE Consumer & Industrial
Types of Protection
Frequency
Uses frequency of voltage to detect power
balance condition
May employ definite time or inverse time curves
Used for load shedding & machinery
under/overspeed protection
Simple
May be slow
Selectivity at the cost of speed can be expensive
30
GE Consumer & Industrial
Types of Protection
Power
Uses voltage and current to determine
power flow magnitude and direction
Typically definite time
Complex
May be slow
Accuracy important for many applications
Can be expensive
31
GE Consumer & Industrial
Types of Protection
Distance (Impedance)
32
GE Consumer & Industrial
Impedance
ZL
ZB
T2
ZA
T1
21
21
Source
33
GE Consumer & Industrial
Generation-typically at 420kV
Typical
Bulk
Power
System
Transmission-typically at 230765kV
Receives power from transmission
system and transforms into
subtransmission level
Subtransmission-typically at 69-161kV
Receives power from subtransmission
system and transforms into primary
feeder voltage
Distribution network-typically 2.469kV
Low voltage (service)-typically
120-600V
36
Protection Zones
1. Generator or Generator-Transformer Units
2. Transformers
3. Buses
4. Lines (transmission and distribution)
5. Utilization equipment (motors, static loads, etc.)
6. Capacitor or reactor (when separately protected)
Bus zone
Unit Generator-Tx zone
Bus zone
Line zone
Bus zone
Motor zone
Transformer zone
Transformer zone
~
Generator
XFMR
Bus
Line
Bus
XFMR
Bus
Motor
37
GE Consumer & Industrial
Zone Overlap
1. Overlap is accomplished by the locations of CTs, the key
source for protective relays.
2. In some cases a fault might involve a CT or a circuit breaker
itself, which means it can not be cleared until adjacent
breakers (local or remote) are opened.
Relay Zone A
Zone A
Relay Zone B
Relay Zone A
Zone B
Zone A
Relay Zone B
Zone B
38
GE Consumer & Industrial
C37.2:
Device
Numbers
Partial listing
44
GE Consumer & Industrial
Multilin
46
GE Consumer & Industrial
47
GE Consumer & Industrial
48
GE Consumer & Industrial
49
GE Consumer & Industrial
1-Line [1]
50
GE Consumer & Industrial
1-Line [2]
3-Line
52
GE Consumer & Industrial
55
GE Consumer & Industrial
58
GE Consumer & Industrial
Trip/Close
Contact
Coil Monitor
Input
Relay
52/a
or
52/b
T/C
Coil
Breaker
52/a for trip circuit
52/b for close circuit
59
GE Consumer & Industrial
Relay
Relay
Breaker
Breaker
60
GE Consumer & Industrial
Current Transformers
Current transformers are used to step primary system
currents to values usable by relays, meters, SCADA,
transducers, etc.
CT ratios are expressed as primary to secondary;
2000:5, 1200:5, 600:5, 300:5
A 2000:5 CT has a CTR of 400
61
GE Consumer & Industrial
62
GE Consumer & Industrial
Burden
Designation
Impedance
(Ohms)
VA @
5 amps
Power
Factor
Metering
B0.1
B0.2
B0.5
B0.9
B1.8
0.1
0.2
0.5
0.9
1.8
2.5
5
12.5
22.5
45
0.9
0.9
0.9
0.9
0.9
Relaying
B1
B2
B4
B8
1
2
4
8
25
50
100
200
0.5
0.5
0.5
0.5
64
GE Consumer & Industrial
Voltage Transformers
Voltage (potential) transformers are used to isolate
and step down and accurately reproduce the scaled
voltage for the protective device or relay
VT ratios are typically expressed as primary to
secondary; 14400:120, 7200:120
A 4160:120 VT has a VTR of 34.66
VP
VS
Relay
66
GE Consumer & Industrial
67
GE Consumer & Industrial
Secondary Circuit
68
GE Consumer & Industrial
Equipment Grounding
Prevents shock exposure of personnel
Provides current carrying capability for the
ground-fault current
Grounding includes design and construction of
substation ground mat and CT and VT safety
grounding
69
GE Consumer & Industrial
System Grounding
Limits overvoltages
Limits difference in electric potential through local
area conducting objects
Several methods
Ungrounded
Reactance Coil Grounded
High Z Grounded
Low Z Grounded
Solidly Grounded
70
GE Consumer & Industrial
System Grounding
1. Ungrounded: There is no
intentional ground applied to
the system-however its
grounded through natural
capacitance. Found in 2.415kV systems.
2. Reactance Grounded: Total
system capacitance is
cancelled by equal inductance.
This decreases the current at
the fault and limits voltage
across the arc at the fault to
decrease damage.
71
GE Consumer & Industrial
System Grounding
3. High Resistance Grounded:
Limits ground fault current to
10A-20A. Used to limit
transient overvoltages due to
arcing ground faults.
R0 <= X0C/3, X0C is capacitive
zero sequence reactance
4. Low Resistance Grounded: To
limit current to 25-400A
R0 >= 2X0
72
GE Consumer & Industrial
System Grounding
73
GE Consumer & Industrial
Medium/High
Resistance
Ground
Low/No
Resistance
79
Ground
GE Consumer & Industrial
Substation Types
Single Supply
Multiple Supply
Mobile Substations for emergencies
Types are defined by number of
transformers, buses, breakers to
provide adequate service for
application
80
GE Consumer & Industrial
81
GE Consumer & Industrial
82
GE Consumer & Industrial
83
GE Consumer & Industrial
Bus
1
Bus 2
Main bus
Aux. bus
Main
Reserve
Transfer
Tie
breaker
Bus 1
Bus 2
85
GE Consumer & Industrial
Switchgear Defined
Assemblies containing electrical switching,
protection, metering and management devices
Used in three-phase, high-power industrial,
commercial and utility applications
Covers a variety of actual uses, including motor
control, distribution panels and outdoor
switchyards
The term "switchgear" is plural, even when
referring to a single switchgear assembly (never
say, "switchgears")
May be a described in terms of use:
"the generator switchgear"
"the stamping line switchgear"
86
GE Consumer & Industrial
Switchgear Examples
96
GE Consumer & Industrial
Contribution to Faults
97
GE Consumer & Industrial
98
GE Consumer & Industrial
102
GE Consumer & Industrial
Useful Conversions
105
GE Consumer & Industrial
107
GE Consumer & Industrial
Vpu = Vactual
Vbase
Ipu = Iactual
Ibase
Zpu = Zactual
Zbase
108
GE Consumer & Industrial
base
Z base
MVAbase x 1000
=
3 x kV L-L base
kV2L-L base
= MVA
base
109
GE Consumer & Industrial
Zbase = kV 2base
MVAbase
Zpu2 = MVAbase2
X
X Zactual
kV 2base2 Z
2
base1 x
kV 2base2
Zpu2 =Zpu1 x kV
actual
MVAbase2
MVAbase1
110
GE Consumer & Industrial
A Study of a Fault.
123
GE Consumer & Industrial
125
GE Consumer & Industrial
Sacrifices coordination
129
GE Consumer & Industrial
131
GE Consumer & Industrial
Multilin
132
GE Consumer & Industrial
Multilin
136
GE Consumer & Industrial
Protection Fundamentals
QUESTIONS?
137