Cooling Strategies
for Ultra-High Density
Racks and Blade
Servers
Prepared by: Michael C. Pacis
Module no. 46
BASIC FACTS
- The power consumed by a equipment
housed in a single rack enclosure can vary
dramatically. The average power consumed
by an enclosure in a data center is about 1.7
kW, but the maximum power that can be
obtained by filling a rack with available high
density servers, such as blade servers, is
over 20 kW.
A TYPICAL EXAMPLE
MAJOR OBSERVATIONS
Most enclosures in data centers operate at a
power below the design value for the data
center
High density computing equipment is not
actually installed at the maximum density that
it is capable of achieving
Power density values that are routinely talked
about in the popular press are not achieved by
any significant number of current or impending
data centers.
POWER REQUIREMENTS
- From the power standpoint, this six-chassis
blade system would most likely require
twenty-four 20A power supply circuits at
either 208V or 230V.
COOLING REQUIREMENTS
- Cooling an ultra-high density enclosure is a
much more difficult problem than providing
power. The blade server system described
above would require approximately 2,500
cfm (cubic feet per minute) (1,180 L/s cool
air at the intake (based on a common value
of 20F [11C] exhaust air temperature rise)
and would exhaust the same amount of
heated air from the rear of the enclosure.