Академический Документы
Профессиональный Документы
Культура Документы
A PRESNTATION
BY
S.K.TRIPATHI
Dy. MANAGER (E) , CPU
Control Philosophy
No of coolers working
Healthiness of oil circulation temperature
Transformer winding temperature
Transformer oil temperature
Humming sound
Any water leakage from any point
Any oil leakage from any point
90 HP VT Dewatering pump
35 HP submersible pump (Drainage pit)
Start Sequence
STOPPING SEQUENCE
STOPPING SEQUENCE
DOS
DONTS
S.No
.
Operation Parameter
Normal Value
1.
90 C
120 C
2.
95 C
125 C
3.
Generation Voltage
11 kV
11 kV(+/-) 5%
4.
Generation Current
1850 A
5.
Field Voltage
340 V
6.
Field Current
900 A at rated
load
530 A at no load
& rated voltage
7.
Frequency
50.00 Hz.
50 Hz(+/-) 3%
9.
Generator Speed
136.4 rpm
10.
Power Factor
0.9 lagging
11.
5 kg/cm2
7 kg/cm2(Max.)
12.
30% of Syn.
speed
70 rpm (Max.)
S.No
.
Operation Parameter
Normal Value
13.
85 bar
14.
7 kg/cm2
15.
MVAR-Generator
4.8 MVAR
16.
20-35C
(depending on
weather)
17.
30-45 C
(depending on
weather & load)
18.
5-6kg/cm2
19.
2-3 kg/cm2
20.
200-250 A
21.
Depends on load
& guide vane
opening
Range of movement=20.5
22.
18-20 kg/cm2
15 kg/cm2(min.
recomended)
23.
50-60 C
80 C
24.
50-55 C
70 C
14 MVAR
7 kg/cm2(max.)
5 kg/cm2(min.)
S.No
.
Operation Parameter
Normal Value
25.
50-60 C
80 C
26.
50-55 C
70 C
27.
50-60 C
80 C
28.
50-55 C
70 C
29.
Line Current(CB-Ganj-I/II)
140 A/Line
280 A
30.
48 MW
96 MW
31.
5 MVAR/Line
40 MVAR
32.
220 kV
245 kV(Max)/200kV(Min)
33.
28 A
98 A
34.
0-20 MW
50 MW
35.
2.5 MVAR
9.5 MVAR
36.
132 kV
S.No
.
Operation Parameter
Normal Value
37.
246.7 m
38.
246.0 m-246.2 m
246.4 m(Bye-pass)
39.
221-223 m
depends on generation(No.
of units running)
40.
Upto 150000
cusecs (flood)
41.
20000 (max.)
cusec
depends on load
42.
Silt in ppm
100-1000 ppmSummer/Winter
1000-3500 ppmRainy Season
43.
40-42 kg/cm2
44 kg/cm2
44.
6-7 kg/cm2
45.
6-7 kg/cm2
46.
2-3 kg/cm2
47.
-1 to +1 kg/cm2
48.
2-3 kg/cm2
4.7 kg/cm2(max.)
S.No
.
Operation Parameter
Normal Value
49.
220 V
50.
25 A
40 A
51.
220 V
52.
25 A
40 A
53.
Depends on load
54.
6.0 kg/cm2(Max.)
55.
Depends on load
Emergency shutdown
10
11
12
13
14
15
16
17
18
LBB protn
19
Governor failure
10
Condition Monitoring in
Hydroelectric power station
Technologies
Offline
1.
2.
3.
4.
1.
2.
3.
4.
5.
6.
7.
8.
9.
Online
Vibration analysis
Air gap between stator & rotor
Temperature of bearing , oil & winding
Inflow
Efficiency of Turbine & generator
Cavitation in turbine
Silt monitoring
Partial discharge
Gas & moister in transformer oil
DGA is well established tool to asses health & suggest further course by
assessing risk involved in operating with suspected faults
DGA only indicates suspected fault not conclusive in nature and further
complementary tests are required for validating & pinpointing
Gases evolve due to normal aging of oil & cellulose as well as due to
various faults
Actual phenomena of gas generation is very complex and host of factors
like type & design of equipment , load pattern , age , type of oil used ,
application etc affect gas generation
These gases partly dissolve in oil and also find way to free gas space
Ratio of dissolved and free gas depend on solubility of gas in oil in
equilibrium condition
Suspected fault is analyzed by monitoring gas in free space and / or
dissolved in oil
As name suggest in DGA the emphasis is on extracting & analyzing
dissolved gases and pattern of gas generation indicate type & severity of
fault
Characteristic fault
C2H2
C2H4
CH4
H2
C2H4
C2H6
PD
Partial discharge
NS
<0.1
<0.2
D1
>1
0.1 0.5
>1
D2
0.6 2.5
0.1 - 1
>2
T1
Thermal fault
T<3000C
NS
>1 but
NS
<1
T2
Thermal fault
3000C< t < 7000C
<0.1
>1
1 -4
T3
Thermal fault
t> 7000C
<0.2
>1
>4
NOTE 1- In some countries the ratio C2H2/C2H6 is used ,rather than the ratio CH4/H2. Also in some countries ,
slightly different ratio limits are used.
Note 2- The above ratios are significant and should be calculated only if at least one of the gases is at a
concentration and a rate of gas increase above typical values.( see clause 9
NOTE 3 CH4/H2 <0.2 for partial discharge in instrument transformers.
CH4/H2<0.07 for partial discharge in bushing.
NOTE 4 Gas decomposition patterns similar to partial discharge have been reported as a result of the
decomposition of thin oil film between overheated core laminates at temperature of 1400C and above.
NS = Non significant whatever the value.
An increasing value of the amount of c2h2 may indicate that the hot spot temperature is higher than 1000 0C.
Fault
PD
Partial Discharges
D1
D2
T1
Thermal faults
T , 3000C
Fault
T2
Thermal fault
3000C < t <
7000C
T3
Thermal fault
T> 7000C
H2
CO
CO2
CH4
C 2H 6
C2H4
C 2H 2
No OLTC
600-150
540-900
510013000
40-110
50-90
60-280
3-50
Communicating
OLTC
75-150
400-850
530012000
35-130
50-70
110-250
80-270
NOTE 1 The values listed in this table were obtained from individual networks. Values on other networks may differ.
NOTE 2 Communicating OLTC means that some oil oil and/ or gas communication is possible between the OLTC
compartment and the main tank or between the respective conservator. These gases may contaminate the oil in the main
tank and affect the normal values in these types of equipment. No OLTC refers to transformers not equipped with an
OLTC or equipped with an OLTC not communicating with or leaking to the main tank.
NOTE 3- In some countries, typical values as low as 0.5 l/l for C2H2 and 10 l/l for C2H4 have been reported.
<5
<2
<2
<2
<0.1
<50
<200
NOTE The values listed in this table were obtained from individual networks. Value on other networks
may differ. Values on other types of transformers , for instance sealed transformers , may also differ.
H2
CH4
C2H2
C2H4
C2H6
CO
CO2
TDCG
Conditio
n1
100
120
35
50
65
350
2500
720
Conditio
n2
101700
121100
36-50
51-100
66-100
351570
25004000
7211920
Conditio
n3
7011800
4011000
51-80
101200
101150
5711400
400110000
19214630
Conditio
n4
>180
0
>1000
>80
>200
>150
>1400
>1000
0
<4630
NOTES: (1) table 1 assumes that no previous tests on the transformer for dissolved
gas analysis have been made or that no recent history exists. If a previous analysis
exists , it should be reviewed to determine if the situation is stable or unstable. Refer
to table 2 and 3 for appropriate actions to be taken.
(2) An ASTM round robin indicated variability in gas analysis between labs. This
should be considered when having gas analysis between different labs.
The numbers shown in table are in parts of gas per million parts of oil(ppm)
volumetrically and are based on a large power transformer with several thousand
gallons of oil. With a smaller oil volume , The same volume of gas will give a higher
gas concentration. Small distribution transformers and voltage regulators may
contain cumbustible gases because of the operation of internal expulsion fuses or load
break switches. The status codes in table 1 are also not applicable to other apparatus
in which load break switches operate under oil.
** The TDCG value does not include CO2 which is not a cumbustible gas.
Conditio
n1
Conditio
n2
TDCG within this range indicate higher than normal cumbustible gas
level . Any individual cumbustible gas exceeding specified level
should prompt additional investigation.
Conditio
n3
Conditio
n4
Condition 4
Condition 3
Condition 2
Condition 1
>=5
<5 to >=2
< 2 to >=0.5
<.5
TCG Rate
( %/day)
Operating Procedures
>.03
Daily
.03 - .01
Daily
<. 01
Weekly
>.03
Weekly
.03 - .01
Weekly
< .01
Monthly
>.03
Monthly
.03 - .01
Monthly
<.01
Quarterly
>.03
Monthly
Exercise
Analyse for individual gases.
Determine load dependence.
.03 - .01
Quarterly
<.01
Annual
Exercise caution.
Analyze for individual gases.
Determine load dependence.
Condition 4
Condition 3
Condition 2
Condition 1
>4630
1921 - 1630
721 - 1920
<=720
TDCG
Rates
(ppm/day)
Operating procedure
>30
Daily
10 - 30
Daily
< 10
Weekly
>30
Weekly
10 30
Weekly
<10
Monthly
>30
Monthly
10-30
Monthly
<10
Quarterly
>30
Monthly
Exercise caution
Analyse for individual gases.
Determine load dependence
10 30
Quarterly
<10
Annual
Exercise caution
Analyse for individual gases.
Determine load dependence.
Ratio R2
C2H2/C2H4
Ratio R3
C2H2/CH4
Ratio R4
C2H6/C2H2
Extracted from
Extracted from
Extracted from
Extracted from
Oil
Gas
space
Oil
Gas
space
Oil
Gas
space
Oil
1. Thermal
decomposition
>1.0
>1.0
<0.75
<1.0
<0.3
<0.1
>0.4
2. Corona
( Low intensity
PD)
<0.1
<. 0.01
Not significant
<0.3
<0.1
>0.4
>0.2
3. Arcing
( High intensity
PD)
>1.0
<1.0
>.01
<0.1
>0.75
>0.3
>0.1
<0.4
<0.2
>1.0
Gas
space
R2
C2H2/C2H4
R1
CH4/H2
R5
C2H4/C2H6
Suggested
fault diagnosis
<0.1
>0.1
<1.0
<1.0
Unit normal
<0.1
<0.1
<1.0
Low energy
density arcing
- PD
0.1 0 3.0
0.1 1.0
>3.0
Arcing high
energy
discharge
<0.1
>0.1
<1.0
1.0
3.0
Low
temperature
thermal
<0.1
>1.0
1.0 3.0
Thermal
<7000C
<0.1
>1.0
>3.0
Thermal
>7000C