TLH 300 + Fixture : For AEG - NGEF 220 kV/ 400 kV SF6 CB.
LTF 250 C : For CGL make 132 kV/220 kV/400 kV SF6 CB.
CB Travel
Important things to
observe
Shocks
Overshoot margin.
Rebound margin.
Care in handling.
Making connections...
DCRM 100 B to CB
D E T A IL O F IN S T R U M E N T
500
1000
2000
Making connections...
DCRM 100 B to CB
Check continuity of C+, C-, V+ & V- end to end. Ensure that there is
no continuity of any of above cables with earth terminal of DCRM.
Making connections
Memory Bank : HISAC MB 3.0 to HISAC 2406
Connect RS 232 output
P ower
port connections of
P r in te r P o w e r
RS
T
XT
N
EC
R
RX
T
ON
IG IN
T
P
O
A
E
R
T
S
ER
M
F
N
IO
T
C
U
AS
B
Y
K
PRN
D a ta
RS
232C
R e fe r to in s tr u c tio n m a n u a l b e f o re te s tin g .
V e r if y tw ic e th e fi r m n e s s o f e a r th in g c o n n e c tio n s .
W h e n H IS A C is n o t in u s e fo r a p ro lo n g e d p e r io d , k e e p it
p o w e re d u p fo r 2 4 h o u rs , a t le a s t o n c e a m o n th .
S EL ECT A B C D E F G H I
T E S T O P TIO N S
C
TO M OVE
C URSO R
ENT
TO SE LE CT
O P T IO N
ESC
P R E V IO U S
MENU
RST
O P E N IN G
MENU
OC
O CO
D IS P L AY R ES U L T S
Mc
T im
Vel
M AX
CU RR EN TS
T IM I N G S
V E L O C IT Y
P R IN T R ES U L T S
R EP OR T
GRAPH
CO
RST
NXT
REC
TRX
O P E R A T IN G IN S T R U C T IO N S
ON REAR O F M EM ORY BANK
B R E A K E R S TA T U S
CUR R EN T
T IM IN G S
V EL O C I T Y
U S E R D AT A E N T R Y
T E S T S E T T IN G S
C U R R EN T S E TTIN G S
T R A V E L S E T T IN G S
D OW N L OAD TO P C
S P E C IA L FU N C TIO N S
Before the data transfer from HISAC, the selected location No. on
LCD of HISAC MB 3.0 should not be FULL. If so, go to next
available location.
B R E A K E R S TAT U S
U S E R D ATA E N T R Y
T E S T O P T IO N S
T E S T S E T T IN G S
C U R R E N T S E T T IN G S
T R A V E L S E T T IN G S
D O W N LO A D T O P C
S P E C IA L F U N C T IO N S
CO
OC
OCO
D IS P L A Y R E S U LT S
M c
T im
Vel
M AX
CURRENTS
T IM I N G S
V E L O C IT Y
P R IN T R E S U LT S
REPORT
GRAPH
CURRENT
T IM I N G S
V E L O C IT Y
Enter actual mechanism travel or use AUTOPLACE option for finding out travel.
Enter points P1 & P2 and P3 & P4 for obtaining closing & tripping velocities
respectively.
Keep both MIN & MAX pots in fully anti-clockwise direction for all travel channels.
Keep CB in closed condition.
After entering the travel and points P1 to P4 for the respective channel to which TDX
is connected AMPLITUDE option will appear.
When CB is in closed condition set MAX amplitude pot to show count 225 on LCD.
Take Open operation on CB.
Set count on LCD to 25 by using MIN amplitude pot without disturbing the MAX pot.
Two to three such operations may be required to set MIN & MAX counts to steady
values i.e. when CB is closed count should be 225 and when CB is open count
should be 25.
And Finally .
Take operation on CB.
View important test results on display.
Take the printout.
Troubleshooting ...
OBSERVATION
PROBABLE CAUSE
No contact timings, No
PIR timings.
Excessive bounce
Troubleshooting
Contd...
OBSERVATION
PROBABLE CAUSE
No current trace.
Range selected is 0.
Spikes on current
channel
No travel trace
Troubleshooting ...
contd...
OBSERVATION
PROBABLE CAUSE
Troubleshooting ...
Contd...
OBSERVATION
No DCRM trace
PROBABLE CAUSE
No continuity between C+ & V+ and C- & V- cables
after connections to CB when it is in open condition.
The voltage across resistance output of DCRM is
less than 4.63 V when CB is in open condition.
One of C+, C-, V+or V- has continuity with earth
terminal.
Ck clamps are not making proper contact with CB
for some reason, e.g. paint, rust at the point of
connection.
Troubleshooting ...
Contd...
OBSERVATION
1.
2.
3.
PROBABLE CAUSE
1.
2.
Troubleshooting ...
Contd...
OBSERVATION
1.
2.
3.
Excessive spikes at
the beginning of
DCRM trace
PROBABLE CAUSE
1.
Pitting of CB contacts.
2.
3.
Troubleshooting ...
Contd...
OBSERVATION
Data not downloaded
from MB 3.0 to PC.
PROBABLE CAUSE
condition.
The DOs :
The DOs :
The DOs :
Do not tighten the Ck clamps excessively as it may deform the shape &
affect the measurement.
The
: while used with DCRM.
Do not enter any travel
for TYDONTs
& TB channels
Do not power ON DCRM , if CB is close & Ck clamps are connected.
Do not add oil /grease of any make to the threads of Ck clamp, as it will
affect the measurement.
Do not connect the contact sensing cables to the pole on which
DCRM signature is being taken.
Do not try to open the instrument.
THANK YOU !