Академический Документы
Профессиональный Документы
Культура Документы
Course Title:
Advanced Power System Protection
Symmetrical Components
Symmetrical Components
Symmetrical Components
Symmetrical Components
Vectors
The vectors are instantaneous snapshots of an AC sinusoidal wave,
represented by a straight line and a direction.
A sine wave starts from zero value at 0, reaches its peak value at
90, goes negative after 180 and again reaches back zero at 360.
Straight lines and relative angle positions, which are termed vectors,
represent these values and positions. For a typical sine wave, the
vector line will be horizontal at 0 of the reference point and will be
vertical upwards at 90 and so on and again comes back to the
horizontal position at 360 or at the start of the next cycle.
Impedance
Impedance This is the AC equivalent of resistance in a DC system,
and takes into account the additional effects of reactance. It is
represented by the symbol Z and is the vector sum of resistance
and reactance
Reactance
Capacitance is the electrostatic charge required when energizing the
system. It is represented by the symbol C and is measured in farads.
To convert this to ohms,
Reactance
Reactance is a phenomenon in AC systems brought about by
inductance and capacitance effects of a system.
Energy is required to overcome these components as they react
to the source and effectively reduce the useful power available
to a system.
The energy, which is spent to overcome these components in a
system is thus not available for use by the end user and is
termed useless energy though it still has to be generated by
the source.
Inductance is represented by the symbol L and is a result of
magnetic coupling which induces a back emf opposing that
which is causing it. This back-pressure has to be overcome
and the energy expended is thus not available for use by the
end user and is termed useless energy, as it still has to be
generated. L is normally measured in Henries.
Reactance
When a voltage is applied to a system, which has an impedance
of Z, vectorally the voltage is in phase with Z as per the above
impedance diagram and the current is in phase with the
resistive component.
Accordingly, the current is said to be leading the voltage vector
in a capacitive circuit
and is said to be lagging the voltage vector in an inductive
circuit.
Complex Numbers
Any complex number, such as a + jb , may be represented by a single point p,
plotted on a Cartesian coordinates, in which a is the abscissa on the x axis of real
quantities and b the ordinate on the y axis of imaginary quantities.
Referring to Fig., let r represent the length of the line connecting the point p to the
origin and the angle measured from the x-axis to the line r.
It can be observed that:
a = r cos
b = r sin
Complex Numbers
The angular position of the phasor represents position in time, not space.
A phasor quantity or phasor, provides information about not only the
magnitude but also the direction or angle of the quantity.
When using a compass and giving directions to a house, from a given location, a
distance and direction must be provided.
For example one could say that a house is 10 miles at an angle of 75 degrees
Phasors are written in polar form as:
Y = Y
= Y cos + Yj sin
(Polar Form )
(Rectangular Form)
The j operator
In polar form, j = 190 .
Multiplying by j has the effect of
rotating a phasor 90 without affecting
the magnitude.
The a operator
a-operator is defined as unit
vector at an angle of 120, written
as
a = 1120 .
The operator a2, is also a unit
vector at an angle of 240o,
written a2 = 1240o
Symmetrical Components
Phasor-a or a-operator
positive in
Anti-Clockwise
rotation
Symmetrical Components
Phasor-a or a-operator
positive in
Anti-Clockwise
rotation
Vb
= Va. 1120 = aVa
Va
Vc
= Va. 1240 = a2Va
a-operator
Phasor-a or a-operator
Transformation of Vectors
Transformation of Vectors
Va1 = Va1
Vb1 = 1( 240)Va1 = a2Va1
Vc1 = 1( 120)Va1 = aVa1
Transformation of Vectors
Transformation of Vectors
Transformation of Vectors
Symmetrical Components
Symmetrical Components
Magnitudes can be
subtracted but not the
angles. Convert to
rectangular coordinates
then calculate.
Symmetrical Components
Calculation of short-circuit
MVA
It is important that we know how to calculate the level of fault
current that will flow under these conditions, so that we can
choose equipment to withstand these faults and isolate the
faulty locations without major damages to the system
A fault can occur immediately after the generator or after a
transformer and depending upon the location of fault, the fault
current could vary.
In the first case, only the source impedance limits the fault
current whereas in the second case the transformer impedance
is an important factor that decides the fault current.
Generally, the worst type of fault that can occur is the three-phase
fault, where the fault currents are the highest. If we can calculate this
current then we can ensure that all equipment can withstand (carry)
and in the case of switchgear, interrupt this current.
Calculation of short-circuit
MVA
Calculation of short-circuit
MVA
X% = %age Impedance = %Z
= P / Zp.u
Calculation of short-circuit
MVA
Calculation of short-circuit
MVA
In a three-phase system which generates a 3phase voltage of Ep and where the phase current
is Ip,
Calculation of short-circuit
MVA
Calculation of short-circuit
MVA
Calculation of short-circuit
MVA
Useful formulae Following are the methods adopted to
calculate fault currents in a power system.
Ohmic method: All the impedances are expressed in .
Percentage impedance methods: The impedances are
expressed in percentage with respect to a base MVA.
Per unit method: Is similar to the percentage impedance
method except that the percentages are converted to
equivalent decimals and again expressed to a common
base MVA. For example, 10% impedance on 1 MVA is
expressed as 0.1 pu on the same base.
Calculation of short-circuit
MVA
Ohmic reactance method
In this method, all the reactances components are expressed
in actual ohms and then it is the application of the basic formula
to decide fault current at any location.
It is known that when fault current flows it is limited by the
impedance to the point of fault.
The source can be a generator in a generating station whereas
transformers in a switching station receive power from a remote
station. In any case, to calculate source impedance at HV in :
Calculation of short-circuit
MVA
Ohmic reactance method:
Transformer impedance is expressed in terms of percent
impedance voltage
and is defined as the percentage of rated voltage to be applied
on the primary of a transformer for driving a full load secondary
current with its secondary terminals shorted.
Hence, this impedance voltage forms the main factor to decide
the phase-to-phase or any other fault currents on the secondary
side of a transformer
Z=V/I
Z = KV / KA
Vp/Vs = Np/Ns
Calculation of short-circuit
Current
Percentage reactance method
P = 3 x V x I
XB %
Since
Per_unit value =
Actual_Value
Base_Value
The base value always has the same units as the actual value, forcing the perunit value to be dimensionless.
The base value is always a real number, whereas the actual value may be
complex. The subscript pu will indicate a per-unit value.
Per-unit quantities are similar to percent quantities. The ratio in percent is 100
times the ratio in per-unit. For example, a voltage of 70kV on a base of 100kV
would be 70% of the base voltage. This is equal to 100 times the per unit value of
0.7 derived above.
Z = V^2 / P
Z% = Zp.u. 100%.
Zp.u = Z% = Z (Actual ohm)
100%
Z (Base Ohms)
Z (Actual Ohms) = Z% x Z(Base ohms)
100
= Z% x [ KV (Base) ]^2
100 [ MVA (Base)]
In most cases the turns ratio of the transformer is equivalent to the system voltages,
and the equipment rated voltages are the same as the system voltages. This
means that the voltage-squared ratio is unity
Step-4: Calculate fault current from fault MVA by using formula of 3-phase
power for phase voltage and current: P = 3 x V x I instead of 3xVxI Where V
and I are line voltage and currents
P = 3 x V x I
XB %
Since
P = 3 x V x I
XB %
Since
A transformer is
rated 2000 VA,
200V/400V, and
has an internal
impedance of
j4.0 as seen
from the low
voltage side.
Notice in Table 1 that the transformer per unit impedance is the same, regardless
of to which side of the transformer it is referred.
Again, the conversion complications are absorbed into the base relationships.
In the transformer equivalent circuit the different voltage levels disappear and the
transformer equivalent circuit is reduced to a single impedance:
Each of the sequence networks are then connected together in various ways
to calculate fault currents and voltages depending upon the type of fault.
Summary
Summary
Summary
Summary
Summary
P = 3 x V x I
XB %
Since