SM6 Switchgear- General Introduction

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

SM6 Switchgear- General Introduction


What is SM6-24?
It is an Air Insulated Modular Switchgear that
guarantees hi-reliability for your underground
secondary distribution applications.
SM6-24 units are used for the medium voltage
section in MV/LV transformer substations in
public distribution systems and MV consumer or
distribution substations up to 24kV and 1250A

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

SM6 Switchgear- General Introduction


Taking advantage of the reference
1975

innovation
Sulphur hexafluoride (SF6) is first used in a MV switchboard for an MV/LV transformer
substation, with the hi-reliable VM6

1991

innovation and experience


Cumulated with second generation of SM6-24 modular SF6 range

2012

the widest installed-base in the world


With over quantity 1,100,000 SM6 functions installed all around the world, you avoid any
risk by recommending and using the reference in the Medium Voltage field

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

SM6 Switchgear- General Introduction


Environment: our real concern

SM6-24 has been designed to


be environmentally friendly
The material used, both
conductors and insulators are
identified, and easily
separable
At the end of its life, SM6-24 is
recycled and its materials
recovered in conformity with
the European regulations
This process runs without any
gas being released to the
atmosphere nor any polluting
fluids being discharged
Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

SM6 Switchgear- General Introduction


General characteristics- Normal operating conditions
SM6 units are designed for indoor installations
Ambient air temperature:
1) less than or equal to 40C
2) less than or equal to 35C on average over 24 hours
3) greater or equal to 5C.
Altitude:
1) less than or equal to 1000 m
2) above 1000 m, a derating coefficient is applied (please consult us).
Solar radiation:
1) no solar radiation influence is permitted.
Ambient air pollution:
1) no significant pollution by dust, smoke, corrosive and/or flammable gases, vapours or salt
Humidity:
1) average relative humidity over a 24 hour period, less than or equal to 95%
2) average relative humidity over a 1 month period, less than or equal to 90%
3) average vapor pressure over a 24 hour period, less than or equal to 2.2 kPa
4) average vapor pressure over a 1 month period, less than or equal to 1.8 kPa

For these conditions, condensation may occasionally occur. please pay attention on Civil
Engineering recommendations for design of the building or housing, by suitable ventilation
and installation.
Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

SM6 Switchgear- General Introduction


General characteristics- Main characteristics
The hereunder values are for working temperatures from -5C up to +40C and for a setting up at
an altitude below 1000 m.

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

SM6 Switchgear- General Introduction


General characteristics- Main characteristics

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

SM6 Switchgear- General Introduction


General characteristics- Main characteristics
Endurance

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

SM6 Switchgear- General Introduction


General characteristics- Main characteristics
Endurance

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

SM6 Switchgear- General Introduction


General characteristics- Main characteristics
Internal arc withstand (in accordance with IEC 62271-200):
SM6-24:
12.5 kA 1 s, IAC: A-FLR & IAC: A-FL
16 kA 1 s, IAC: A-FLR & IAC: A-FL
20 kA 1 s, IAC: A-FLR & IAC: A-FL
SM6-36:
16 kA 1 s, IAC: A-FL.

Electro-magnetic compatibility:
Relays: 4 kV withstand capacity, as per recommendation IEC 60801.4
Compartments:
o electrical field:
- 40 dB attenuation at 100 MHz
- 20 dB attenuation at 200 MHz
o magnetic field: 20 dB attenuation below 30 MHz .

Temperatures:
The cubicles must be stored and installed in a dry area free from dust and with limited temperature
variations.
For stocking: from 40C to +70C
For working: from 5C to +40C

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

10

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

SM6 Switchgear- General Introduction


General characteristics- Main characteristics
Protection index:

Classes: PI (insulating partition)


Loss of service continuity classes: LSC2A (LSC1 for metering functions)
Units in switchboard: IP3X
Between compartments: IP2X for SM6-24,
Cubicle: IK08 for SM6-24, IK07 for SM6-36.

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

11

Thanks!
Make the most of your energy

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

12