Вы находитесь на странице: 1из 31

Sepam 1000+

Presentation

Sepam protection relays,


a range of solutions or all applications
Serie 80
Serie 40
Serie 20

Sepam series 80:


intelligent solutions
for custom applications

Sepam series 40:


high-performing solutions
for demanding applications
Sepam series 20:
simple solutions
for usual applications
Sepam General.ppt

2 /31

Sepam selection guide


Sensors
Sepam series 20

3I + I0

10 I / 8 O
1 comm. port

3V + V0

Specific
protection

Substation

Transformer

Motor

S20

T20

M20

Generator

10 I / 8 O
1 comm. port
Logic equations
Sepam series 80
42 I / 23 O
2 comm. ports
Logic equations
Logipam

3I + I0
3V

B22
S40

67N

S41

67N
67

S42

G40
M41

T42
B80

67N

S81

T81

67N
67

S82

T82

81R

S84

87T
87M

3I + I0
2x3V + V0
3I + I0
4 Ides
3V + V0

T40

S80

3I + 2xI0
3V + V0

2x3I + 2xI0
3V + V0

Capacitor

B21
81R

Sepam series 40

Busbar

T87

M81
G82

M88

G88

M87

G87
B83

51C

C86

Sepam General.ppt

3 /31

Sepam 1000+
standard applications
For industrial and service
sector site networks
For public distribution
networks
For all voltage levels

Sepam General.ppt

4 /31

S20 substation application


Series 20
Substation incomer and
feeder applications
Protection functions:
50/51, phase
overcurrent
50N/51N, earth fault
46, negative sequence /
unbalance
Logic discrimination
4-cycle recloser
Sepam General.ppt

5 /31

Substation application
(S40/S41/S42 types)

Series 40

Parallel incomers or closed


ring networks
Isolated or compensated
neutral networks
Protection functions:
50/51,50N/51N,46,50BF
67N/67NC,
directional earth fault
67, directional phase
overcurrent
32P, reverse power
I, U, P, E metering
Sepam General.ppt

6 /31

T20 transformer application


Series 20
Protection functions:
50/51, 50N/51N and 46
49RMS, thermal
overload
38/49T, temperature
monitoring (8 sensors)
Processing of faults
detected by transformer
Buchholz or thermostat
(MES module required)

Sepam General.ppt

7 /31

Transformer application
(T40/T42 types)

Series 40

Parallel transformers
Isolated or compensated
neutral networks
Protection functions:
50/51,50N/51N, 46,50BF
49RMS and 38/49T
67N/67NC, directional
earth fault
67, directional phase
overcurrent
I, U, P, E metering

Sepam General.ppt

8 /31

M20 motor application


Series 20
Protection functions:
50/51, 50N/51N, 46
49RMS
38/49T
Specific functions:
37, phase undercurrent
48/51LR, excessive
starting time and
locked rotor
66, starts per hour
specific motor-related
function (MES114)

Sepam General.ppt

9 /31

Motor application
(M41 type)

Series 40

Isolated or compensated
neutral networks
All the M20 protection
functions, plus:
67N/67NC, directional
earth fault
32P, reverse power
27/59, 81L/81H,
Automatic load shedding
I, U, P, E metering

Sepam General.ppt

10 /31

Generator application
(G40 type)

Series 40

Protection functions:
50/51, 50N/51N,46,50BF
49RMS and 38/49T
27/59, 81L/81H,
Specific functions:
50V/51V, voltage
restraint overcurrent
32P, 32Q/40, directional
active and reactive
overpower
I, U, P, E measurements

Sepam General.ppt

11 /31

B21 busbar application


Voltage protection
functions:
27/59, phase-to-phase
under/overvoltage
81L/81H,
under/overfrequency
59N, neutral voltage
displacement
27D/47, positive sequence
undervoltage and phase
rotation direction
27R, remanent undervoltage
27S, 3 phase-to-phase
undervoltages V1,V2,V3

Series 20

Sepam General.ppt

12 /31

B22 busbar application


Series 20
Voltage protection functions:
27/59, 27S, 59N
81L/81H
27D/47, 27R
Loss of mains protection
81R, rate of change of
frequency (ROCOF)
fast, reliable detection of
loss of mains
for substations with
generators in parallel
with the main network

Sepam General.ppt

13 /31

Sepam 1000+
User Machine Interfaces
Logic inputs / outputs
Communication
Temperature acquisition
Analog output

Sepam General.ppt

14 /31

Basic User Machine Interface


When local metering
and control are not
required

The SFT2841 software tool is essential


to set up Sepam.
Sepam General.ppt

15 /31

To manage your
installation locally!

Advanced
User Machine Interface

The keypad and display are used to set the Sepam parameters and
protection functions and to display measurements and alarms.
The advanced UMI does not give access to the matrix (use SFT2841).
Sepam General.ppt

16 /31

Remote advanced
User Machine Interface
Module to be flushmounted
wherever
To improve
ergonomics
To facilitate
installation
N.B. The remote UMI may not be installed on the front panel
of Sepam.
Sepam General.ppt

17 /31

SFT2841 software
To make the most
of your Sepam !

The SFT2841 tool may be used to set parameters and protection functions and
customize Sepam. It provides the alarm history, disturbance records and
parameter down and uploading.
Sepam General.ppt

18 /31

Sepam 1000+
User Machine Interfaces

Logic inputs / outputs


Communication
Temperature acquisition
Analog output

Sepam General.ppt

19 /31

Additional
Inputs / Outputs
4 logic outputs as a standard
feature
a choice of 2 additional
input/output modules:
MES108: 4 logic inputs/4
logic outputs
MES114: 10 logic inputs/4
logic outputs

To enhance the
monitoring/control
functions
This module is essential to be able to use certain functions.
Sepam General.ppt

20 /31

Sepam 1000+
User Machine Interfaces
Logic inputs / outputs

Communication
Temperature acquisition
Analog output

Sepam General.ppt

21 /31

Communication functions

Modbus/Jbus protocol
Measurement readouts
TS status readouts
Logic input status readouts
TC remote control orders
Remote settings
Control of the optional MSA114 analog output
Disturbance recording OPG readouts

Sepam General.ppt

22 /31

Communication interfaces
Modbus communication
protocol
ACE949-2: RS485 2-wire
communication interface
with distributed supply
2 wires for the RS485
signal
2 wires to supply the
ACE949-2
Auxiliary supply for the
ACE949-2 provided by the
ACE909-2 interface or the
ACE919 or a 12 or 24 V DC
external power supply

Sepam General.ppt

23 /31

Communication interfaces
Modbus communication
protocol
ACE959: RS485 4-wire
communication interface
with distributed supply
4 wires for the RS485
signal
2 wires to supply the
ACE959
Auxiliary supply for the
ACE959 provided by a 12 or
24 V DC external power
supply

Sepam General.ppt

24 /31

Sepam 1000+
User Machine Interfaces
Logic inputs / outputs
Communication

Temperature acquisition
Analog output

Sepam General.ppt

25 /31

Temperature
acquisition
Measurement
of 8 or 16
temperatures
By Pt100, Ni100 or
Ni120 temperature
sensors
For better motor,
generator and
transformer
protection!

N.B.: 1 module for Sepam series 20


1 to 2 modules for Sepam series 40

Sepam General.ppt

26 /31

Sepam 1000+
User Machine Interfaces
Logic inputs / outputs
Communication
Temperature acquisition

Analog output

Sepam General.ppt

27 /31

Analog output
A choice of
formats (4-20mA,
0-10mA or 0-20mA)

For remote analog


measurements!

Sepam General.ppt

28 /31

Sepam 1000+

a complete solution

Sepam General.ppt

29 /31

Sepam 1000+, easy to install


Series 20
Same cutout as Sepam 1000
Compact, reduced depth (< 100mm)
Universal power supply
48 to 250 V DC and 110 to 240 V AC
and 24 V DC power supply
Universal logic inputs
24 to 250 V DC
Engraved terminal identification
Immunity to 10V/m radiated fields
Disconnectable I/O module
Prewired remote modules
Extended temperature range: -25C to 70C

<100mm
Sepam General.ppt

30 /31

Sepam 1000+, Easy to install


series 40
Base unit:
new basic board
3 resident voltage channels (3 internal transformers)
the same size as Sepam 1000+ series 20
(same cutout dimensions and same depth)
Auxiliary power supply:
universal: 24 V DC to 250 V DC and 100 V AC to
240 V AC
power line disturbance withstand: 20 ms
consumption < 15W

<100mm
Sepam General.ppt

31 /31