Академический Документы
Профессиональный Документы
Культура Документы
Introduction
Electricity is a specific product which need to meet
certain quality requirements defined in the European
standard EN 50160, EN61000-4-7 and EN61000-4-30.
Harmonic distortion is a deviation of a current or
voltage waveform from a perfect sinusoidal profile.
The current harmonics in nonsinusoidal situations can
be evaluated using the IEEE Standard 1459-2010.
Non-linear loads, such as power supplies and charge
controllers, current distortion is very common due to
the use of power electronics switches to convert
power from an AC to a DC form.
IEEE 1459
IEEE Standard Definitions for the Measurement of Electric
Power Quantities Under Sinusoidal, Nonsinusoidal,
Balanced, or Unbalanced Conditions.
Sinusoidal Conditions
v 2V sin t
Sinusoidal voltage source
Supplying a linear load,
i 2 I sin t
will produce a sinusoidal current:
P
PF
S
S P2 Q2
10
Nonsinusoidal Conditions
Apparent power (VA)S V I
P P1 PH
Active power (W)
kT
1
Fundamental active power (W)P1 kT v1i1dt V1 I1 cos 1
V
V
THDv H 1
V1
V1
I
I
THDi H 1
I1
I1
P
PF
S
P
Power factor
PF1 cos 1 1
S1
11
PFC
12
13
Boost Converter
A boost converter (step-up converter) is a DC-toDC power converter with an output voltage
greater than its input voltage. Since power (P =
VI) must be conserved, the output current is lower
than the source current.
14
15
16
17
IEEE 1459-2010
18
19
20
23
Measured values
according to standard 1459-2010
25
26
Technical Evaluation
Only exact technical evaluation can guarantee adequate
solution, working concept is based on four steps:
1. Determining the Current Situation
2. Measurements of electrical parameters of the
transformer with a fast power quality analyzer
3. Analysis of the recorded results with powerful
software tool in the time domain (rms and instantaneous
values) and frequency domain. Technical definition of
solution.
4. Software simulation - modern approach that is
used in completing the verification process of the
decision through the simulation process of compensation.
27
24h profile
24h profile
29
1h profile
30
5min profile
31
10s profile
1s profile
Solution
Given the current approved state and the conducted analysis, to
compensate the transformer the following characteristics are required:
- Full compensation cycle by cycle: 5-20ms (for 50Hz)
- Total reactive power 1200kvar
- Compensation with 5 steps 240kvar (1:1:1:1:1)
- 14% detuned filter with iron core
Compliant with standards N60831/1/2, EN50081-2, EN50082-2,
EN55011, EN61000-4-2/3/4/5, ENV50204, ENV50141 and safety
requirements EN61010-1, EN50439-1
The proposed compensation with Elspec Equalizer provides the fast
compensation (15ms two thirds of a 50 Hz cycle), via solid state
transient free switching, the Equalizers controller uses FFT (fast Fourier
transforms) to analyze each and every cycle and apply appropriate
compensation per cycle. The Equalizer can apply different levels of
reactive compensation to each and every 50Hz cycle!
35
36
37
Other benefits
Significantly improve voltage stability under the most
difficult loads.
Significantly reduce current spikes from large motor startups or other large sudden reactive loads.
Prevent damage to sensitive electronic equipment
Free up capacity on transformers overloaded with reactive
power
Extremely long life expectancy
Integral power quality analyzer
Accurate power factor correction even under dynamic loads
Unique self testing and reporting features
Solid state transient free switching
38
Simulation
Simulation
Conclusions
Devices for power supply, converters and inverters with switching elements have a
low power factor. To increase the efficiency and the exploitation of such devices in
addition should be used a correcting power factor (PFC - Power Factor Correction)
embedded in them, which are often complex circuits that reach the power factor
greater than 0.95 (PF> 0.95).
On the thyristor power control, the capacitive compensation complicates the system
further.
For the correction of the power factor in a time variant loads in presence of
distortions, should be used compensators with dynamic response in the order of
period of network voltage. Derived from analysis of parameters for an industrial
complex time variant load with fast dynamic compensation of 17ms order are
achieved good results at rapid changes in dynamic events around 200-300ms (10-15
cycles). The proposed system of compensation for time variant load improves power
quality in real time by: correcting the power factor to nearly ideal value of 1, saving
electricity, reducing flickers, harmonics and current spike reduction
Based on the analysis of the measured values of electrical parameters of time variant
load in the presence of distortions, using a fast dynamic compensator with a
response time in the order of the grid voltage period gives very good results in the
correction of the Power Factor and improving the Power Quality of network.
41
42