INSTRUMENT TRANSFORMERS
INSTRUMENT TRANSFORMERS
INSTRUMENT TRANSFORMERS
INSTRUMENT TRANSFORMERS
INSTRUMENT TRANSFORMERS
For a given CT, burden & ALF are inversely related i.e. If
connected burden is less than rated, ALF is up.
INSTRUMENT TRANSFORMER
INSTRUMENT TRANSFORMER
INSTRUMENT TRANSFORMER
INSTRUMENT TRANSFORMER
INSTRUMENT TRANSFORMER
CURRENT TRANSFORMER
5A CT SECONDARY
1A CT SECONDARY
INSTRUMENT TRANSFORMER
INSTRUMENT TRANSFORMER
To and fro lead burden between CBCT & Relay (say 1 ohm)
INSTRUMENT TRANSFORMER
Metering VT
Protection VT
Dual Purpose VT
Residual VT
SPECIFICATIONS
Voltage Ratio
Accuracy Class
Rated VA Burden
Rated Voltage Factor
ANOTHER CLASSIFICATION
Electro-magnetic Voltage Transformer
Capacitor Voltage Transformer (CVT)
INSTRUMENT TRANSFORMER
% RATIO ERROR
0.1
(+/-) 0.1%
(+/-) 5
0.2
(+/-) 0.2%
(+/-) 10
0.5
(+/-) 0.5%
(+/-) 15
1.0
(+/-) 1.0%
(+/-) 20
3.0
(+/-) 3.0%
REFERENCE CONDITIONS
Voltage 80 120%
Burden 25 100%
Frequency - Rated.
----
INSTRUMENT TRANSFORMER
PROTECTION VT
CLASS
3P
6P
% RATIO ERROR
(+/-) 3%
(+/-) 6%
RESIDUAL VT
5 PR
(+/-) 5%
200
10 PR
(+/-) 10%
-----
REFERENCE CONDITIONS
Burden 25 100%
Frequency - Rated.
INSTRUMENT TRANSFORMER
Effectively Earthed
Non-effectively
Earthed (With
Automatic E/F trip)
RATED V.F.
1.2
1.5
1.2
1.9
RATED TIME
Continuous
30 Seconds
Continuous
30 Seconds
Non-effectively
1.2
Continuous
Earthed (W/O
Automatic E/F trip)
1.9
8 Hours
In non-effectively earthed system, healthy phase voltage rises to phase to
phase value, in the event of an earth fault. Thus, considering 10% , permissible
over voltage,
V (Healthy Phase) = 1.1 x 1.732 = 1.9
INSTRUMENT TRANSFORMER
VOLTAGE TRANSFORMER
STAR / STAR CONNECTION
V- CONNECTION
INSTRUMENT TRANSFORMER
VOLTAGE TRANSFORMER
RESIDUAL CONNECTION (STAR / OPN DELTA)