Functions of the EMUA

This describes the functions of the EMUA. Providing a variety of input


ports for monitoring
signals, the EMUA supports real-time monitoring and remote
monitoring. In addition, the
EMUA is highly reliable and can be flexibly configured. It supports a
large area for temperature
monitoring.
The EMUA4832 supports -48 V DC power input, and the voltage can
range from -36 V
DC to -72 V DC.

Exterior of the EMUA

Internal Structure of the EMUA

DIP Switch Setting


Silkscreen

SW_ADDR

Function

Selection of the
communication protocol

Thirty-two bits for Boolean signal input

Bits 1-8 of the DIP switch SW12A correspond to input signals 1-8.
Bits 1-8 of the DIP switch SW12B correspond to input signals 9-16.
Bits 1-8 of the DIP switch SW24A correspond to input signals 17-24.
Bits 1-8 of the DIP switch SW24B correspond to input signals 25-32.
When a bit is set to ON, it represents high-level alarms.
When a bit is set to OFF, it represents low-level alarms or is not used.

Bit 4: door status sensor setting


Bit 1: temperature sensor setting

SW_AE
SW_AV

SW12A,
SW12B,
SW24A,
SW24B

(If a DIP switch bit is set to ON, it represents 0. If a DIP switch bit is set to OFF,
it represents 1.)

Bit 2: humidity sensor setting


Four bits for analog signal sensor
settings
Four bits for analog signal sensor
settings

Bit 3: infrared sensor setting

SW_THE

The settings of the DIP switch


SW_ADDR is : 0010
This bit is set to ON if a sensor is not used.
This bit is set to OFF if a sensor is used.
This bit is set to ON no matter whether a sensor is used.
This bit is set to ON if a sensor is not used.
This bit is set to OFF if a sensor is used.
This bit is set to ON if a sensor is used.
This bit is set to OFF if a sensor is not used.
This bit is set to ON if a sensor is used.
This bit is set to OFF if a sensor is not used.
This bit is set to ON if a sensor is used.
This bit is set to OFF if a sensor is not used.
This bit is set to ON if a sensor is used.
This bit is set to OFF if a sensor is not used.
This bit is set to ON if a current-type sensor is used.
This bit is set to OFF if a voltage-type sensor is used.

Bit 1: water sensor setting


Bit 2: smoke sensor setting

SW_BKE

Setting

Position
The EMUA can be installed inside
BTS3900 cabinet or AMP30 cabinet

Cable connection

External alarm position on EMUA board


Position On EMUA
S1
S2
S3
S4
S5
S6
S7
S8
S9
S10
S11
S12
S13
S14
S15
S16
S17
S18
S19
S20
S21
S22
S23
S24
S25
S26
S27
S28
S29
S30
S31
S32

External Alarm Name


A-Alarm Generator Switch
High temp. power room > 25 Degrees
A-Alarm Over-tension controller Failure
A-Alarm Power Controller Phase 1-3
Intruder alarm telecom room
On site telecom room
High temp. telecom room > 25 Degrees
Low temp. telecom room < 10 Degrees
Generator in Operation
Battery Charge Alarm + Low Battery Voltage
Aircraft Obstruction Light Alarm
A Alarm Low Fuel
A-Alarm Generator Failed
Rectifier Mains Power Failure
Low temp. power room < 10 Degrees
A-Alarm Rectifier
B-Alarm Rectifier
Fire Alarm
Intruder alarm power room
On site power room
Clogged Filter AC1+AC2+AC3
B-Alarm AC1+AC2+AC3
A-Alarm AC1+AC2+AC3