Академический Документы
Профессиональный Документы
Культура Документы
RCCB
What is RCCB
Working Principle
The RCCB works on the current
balance principle. The supply
conductors, i.e. the phases and
the neutral, are passed through a
torroid and form the primary
windings
of
a
current
transformer.
Its
secondary
winding is connected to a highly
sensitive electromagnetic trip
relay, which operates the trip
mechanism.
According to behavior
In presence of D.C component
2P & 4P
30,100 &300mA
Type AC
&
Type A
30 mA
100 mA
300 mA
Characteristics of RCCB
Rated current :
16A TO 125A
CALIBRATION PROCESS
witch on the Calibration Machine.
Set the sensitivity of RCCB by magnetic and
demagnetise.
MT testing: Magneting Tripping Test is being performed
to test the tripping ability of the device produced , as it
is designed to work up to a certain range of residual
current as it must open the circuit when the specific
leakage current range also it must trip in a predefined
range of time period.
LSL
USL
Central Value
30
24
27
25
100
80
90
85
300
240
260
250
ELECTROMECHANICAL
ENDURANCE FIXTURE
RCCB remain ok on electromechanical endurance (3000
operations).
H.V TEST
Operation : High voltage test
Tool/Equipment: H.V Tester
Procedure:
Procedure:
Switch on the supply (230V AC).Place in RCCB in the
fixture on ON condition.
Press test button.