Вы находитесь на странице: 1из 54

THE PENINSULA MANILA

TESTO 175T3 DATA LOGGER


April 9, 2014

Contents

Testo Data Loggers


Testo 175 T3 Data Logger (Set
Contents)
Testo 175 T3 Data Logger Features
Getting Started
Software Installation
Programming Procedure
Data Extraction

Testo Data Loggers

Testo Data Loggers


What are Data Loggers?

Data collecting devices/ Diagnostic


Tool
Data Loggers will only show the
Real Score Favorable or
Unfavorable Data.
Data Loggers eliminate Human
Error or Partiality.

Data Loggers are NOT

Loggers are NOT data processors.


Loggers are NOT solution

Testo 175T3 Data Logger


Features

Testo Comsoft V
5.0 Software
Installer CD

3 pcs. AAA
Alkaline Batteries

USB Download
Cable

Other Contents:
Instruction Manual
Calibration Protocol

Testo 175T3 Data Logger

Features
Testo 175T3 Data Logger is for Hot to Cold

Temperature applications using Probes.


Operating Temp.: -20 to +55C.
Measuring Range: -50 to +1000C (type K).
Battery Life 500 Days @ 15min Measuring
Frequency, +25C.
Measuring Frequency 10 to 24hrs. (Can be
selected)
Software Can be used with Windows XP,
Windows Vista and Windows 7.
Warranty 1 yrs. Under Normal Working
Conditions.

Getting Started

Getting Started
Battery Installation

Data Logger is delivered secured to the


Wall
Bracket for its protection.
Using a small FLAT Screw Driver loosen
the screw of the data logger.
Insert 3 pcs AAA ALKALINE Batteries.
Observe polarity.
NOTE: Use only ALKALINE batteries.
Do not mix old and new
batteries.

Getting Started

DO NOT use any sharp


object to open cap from the
side. This will damage the
gasket on the groove of the
cover.

Getting Started

Using a 1 Peso Coin, open the


Download Cable Port by turning the
screw COUNTER CLOCKWISE.
Plug the USB Download Cable

Connect the Probe on to the Port


following the Plug Orientation.
In the Philippines it is common to
use the TYPE K Thermocouple
Probe

Software Installation

Software Installation

Load the Testo ComSoft V.5 CD installer. Click Run


setup.exe

Software Installation

Click Next

Software Installation

Click to Check Acceptance License Agreement then Next

Software Installation

Click Next

Software Installation

Click Next

Software Installation

Click Install

Software Installation

Click Finish. Create Shortcut and Remove CD Installer.

Programming
Procedure

Programming Procedure
1.

2.

Connect the data logger and


download cable to your computer.
Click the Testo Comsoft Icon to open
Testo Data Logger Program.

Click
Icon

Programming Procedure

Click Connect Instrument

Programming Procedure

Data Logger
SERIAL NO.

Click Connect of the Live Data Logger

Programming Procedure

Scroll Down Battery Type/ Brand you installed and click OK.

Programming Procedure

Click Configure Instrument

Programming Procedure

Click Operation Settings.

Programming Procedure

Click Start Time and Select Date and input Program Time
to start

Programming Procedure

Click Start Button for Manual Start

Programming Procedure

Click Memory Full for logger to record until memory is full.

Programming Procedure

Input no. of values XXX you wish to take before logger will
stop.

Programming Procedure

Scroll Down the recording time interval. It is advise to make it


same

Programming Procedure

Select C or F for the unit of measurement.

Programming Procedure

Label Probe 1 and 2.

Programming Procedure

Switch ON and select TYPE K Probe.

Programming Procedure

Set Upper and Lower Limits XX Temperature Values.

Programming Procedure

Type Instrument Name and Description .

Programming Procedure

Click Transfer to Instrument to load program to the logger.

Programming Procedure

Click OK to upload NEW Program and Erase Previous


Program.

Programming Procedure

Click Select Instrument to return to instrument selection


page.

Programming Procedure

Click Disconnect.

Programming Procedure

You may now pull out the logger from the Interphase.

Programming Procedure
To do MANUAL, Press and Hold GO
button for 5 sec. The display will turn
from Wait to Rec. Logger will start
recording data.

Press and
Hold for 5
sec. to start
recording

Data Extraction

Data Extraction
Before doing data extraction, it is
recommended to create a File Folder in
your Documents Library solely for this
purpose.
Data downloaded is in vi2 format thus
this cannot be altered to preserve and
protect data integrity.

Data Extraction
1.

2.

Plug the download cable to the USB


Port of your computer.
Connect the data logger to the
download cable and click the Testo
Program icon.

Click
Icon

Data Extraction

Click Connect Instrument

Data Extraction

Data Logger
SERIAL NO.

Click Connect of the Live Data Logger

Data Extraction

Click Evaluating

Data Extraction

Click Import Measurement Data.

Data Extraction

Click Save Folder Icon.

Data Extraction

Save File Name to the designated folder and Click Save.

Data Extraction

Computer will do data downloading. Wait for a few


seconds

Data Extraction

Click Diagram Settings arrow to open graph details palet.

Data Extraction

Scroll Down from the diagram settings list for more details

THANK YOU AND GOD


BLESS