Вы находитесь на странице: 1из 43

e terragridcom

T390
Power Line Carrier

e-terragridcom T390 Power Line Carrier


Key feature Installation: No change in
outdoor equipment
HV LINE

Line
Trap

C
C
Line Matching
Unit
e-terragridcom
LMU

Line Matching Unit


e-terragridcom LMU

Power Line Carrier


e-terragridcom T390
& e-terragridcom DIP

SERVICES

Power Line Carrier

Management software

e-terra
Sentinel using SNMP protocol

e-terragridcom T390
& e-terragridcom DIP

e-terragridcom T390 Power Line


Carrier
Key feature: Modular equipment

Services & Density

Low end

High end

T390 Digital & Mixed


Mode
T390 Analogue Mode

up to 40W (80W as option)


4 RS232 for internal modem
3 speech interface (1 speech +
2 Tg )
1 Ethernet port
1 IRIG B interface
SNMP management
Input for TP (up to 4 cmds)

up to 40W (80W as option)


4 RS232 Interface
1 V11 Interface 64Kbps
1 LAN port
1 IRIG B interface
Maintenance handset
3 speech channels
Input for TP (up to 4 cmds)
SNMP management
Input for TP (up to 4 cmds)

e-terragridcom T390 Power Line


Carrier
Key feature: Modular equipment
Power Line
Medium

Additional amplifier 80W

Handle racks not cards


providing more flexibility

External Teleprotection

Telephones

Data RS232

Data V11

Protection Relays

PABX

LA
NLA
N Ethernet
Data

Processing unit

High speed bus

Amplifier 40W

No hardware limitation
Modules can be configured
and upgraded according to
customer needs by himself
without any return to the
factory

e-terragridcom T390 Power Line


Carrier
Key feature

Power grid evolution


e-terragridcom T390 an answer to New Scada
feature/constraints
Modular equipment.
Basic 4 integrated modem RS 232 in analogue mode up
to a complete range of speed including V11.
LAN communication available (Digital Mode only).
Data rate from 1200 bit/s in FSK with RS 232 to 128
kbit/s with LAN communication or 64 kbit/s using
V11(Digital Mode only).
Very low latency even in digital mode to make it possible
to transit data over many hops.
Pooling mode ( point to multipoint ) allowed in traditional
analogue mode or digital mode for faster transit

e-terragridcom T390 Power Line


Carrier
Key feature: Modular equipment
Point to Multipoint application on RS 232 transmission
SS 1

SS 2
Analogue or digital

PLC2

PLC1

CC

Analogue or digital

PLC3

PLC4

Control

600b/s

600b/s
RTU1

RTU2

Request RTU1 (broadcast)

Answer RTU1

Transit

Transit

Request RTU1 (broadcast)

Answer RTU1

e-terragridcom T390 Power Line


Carrier
Key feature: Modular equipment

Customer constraint

Frequency plan allocation : e-terragridcom T390


complies with all requirement of IEC 60495
Compatibility in term of frequency planning with
capacity to work in 2; 2,5 or 4 kHz bandwidth in
analogue ( single or double channel)
Can work with bandwidth as low as 4khz in Digital
mode or 8 or 16 kHz
Superimposed mode allowing to reduce by half
bandwidth requirement compare to analogue or
other competitor digital equipment
Paralleling of e-terragridcom T390 with other PLC
equipment analogue or digital possible due to IEC
60495 latest edition compliance.
Offer a smooth evolution to higher bit rate and new
service (IP) based with IEC 104 or future IEC 61850

e-terragridcom T390 Power Line Carrier


Key features: Support all the traditional
PLC feature
Modular functioning

Analogue or Digital transmission or


combination of both mode.
Change from an Analogue version to Digital by
simple firmware license Download
FSK

FSK

Analogue single channel

InterBand for
separated mode

Analog
RX
with TPX

: Separated / adjacent
band, 2.5khz and 4Khz
band

Analog
TX
with TPX

2.5 or
4KHz

2.5 or
4KHz
0 to max

RX

Analog
CH2
2.5 or
4KHz

Analog
CH1
with TPX

TX

FSK

FSK

InterBand for
separated mode

2.5 or
4KHz
0 to max

Analogue double

Analog
CH1
with TPX

Analog
CH2

2.5 or
4KHz

2.5 or
4KHz

channel : Separated
/ adjacent band,
2.5khz and 4Khz
band

e-terragridcom T390 Power Line Carrier


Key features:
features Offer a smooth evolution to higher
bandwidth & new service (IP) based
Change from Analogue to Digital by simple
firmware license Download
Mix mode
RX

Analog
CH1
with TPX

Digital
CH2

InterBand for
separated mode

2.5 or
4KHz

4 or
8KHz

1 channel for Analogue

TX

FSK

FSK

Analog
CH1
with TPX

Digital
CH2

2.5 or
4KHz

4 or 8
KHz

service
(Non
compressed speech + TP
command + low speed
data)

1 channel for digital

0 or 8 min

services ( data + speech )

Full Digital
With or without echo
canceller

FSK
Rx

QAM Signal
RX

QAM Signal
TX

FSK
Tx

LAN / Ethernet
V11 up to max PLC
speed

16 kHz
or
8 KHz
Or
4kHz

16 kHz
or
8 KHz
or
4KHz

Min 4 RS232
Min 3 speeches

e-terragridcom T390 Power Line Carrier


Key features:
features Network security
Network security
Fully compliant with the requirement of the Cigr
committee recommending an analogue channel
dedicated to the teleprotection signals
Teleprotection signals are fully independent from the
digital channel. e-terragridcom T390 with its
standard 4wires interface can accommodate all
standard stand alone teleprotection
Boost mode / the Full PLC power is allocated to the
teleprotection signal in order to have the lowest Pmc
Possibility to use as low as 2+2 kHz for
teleprotection only application with stand alone
teleprotection like e-terragridcom DIP dual tone
functioning or integrated teleprotection TPI.

e-terragridcom T390 Power Line Carrier


Key features:
features Enhanced monitoring and
management capabilities
Monitoring

Drawing of curve on
some PLC
parameter

Can be activated
manually or by
programmable
threshold

Real time monitoring of the Line Quality

e-terragridcom T390 Power Line Carrier


Key features:
features Innovative commissioning Tools:
Spectrum analyzer

Allows fast analysis


of possible noise
coming from other
source ( PLC , other
radio frequencies )
on the line in the
nearby frequencies
of the Receiver
central frequency

e-terragridcom T390 Power Line


Carrier
Key features:
features Power full HMI
Full graphical interface HMI running on Windows XP
environment

Access local or remote through PLC module IP


address

Possibility as an option to activate a Security


pack to encrypt password exchange between
the PLC and the computer

e-terragridcom T390 Power Line Carrier


Architecture
The e-terragridcom T390 PLC is
made of:
1 or 2 AMP Amplifier Unit for 1
to 80W Output power
PRCS - Processing Unit ,
Provides a comprehensive range of
Data interfaces and an external
Teleprotection port
Provides a comprehensive
range of
Data interfaces and Voice
Interfaces

- Flexible Architecture -

e-terragridcom T390 Power Line Carrier


Architecture overview
Some modules can be duplicated if more
services are required
All modules are connected to each other by a
very high speed/capacity link: LVDS
currently only 20% of this link is used

All the interfaces are on the front panel

- Flexible Architecture -

e-terragridcom T390 Power Line


Carrier
Architecture

Amplifier Unit

e-terragridcom T390 Power Line Carrier


Architecture
Amplifier Unit - Size 19 inches - 3U

Information
Led

Access for
filter settings

- Amplifier Unit -

40 W balanced
output

40 W Unbalanced
output

e-terragridcom T390 Power Line Carrier


Architecture

Processing Unit

e-terragridcom T390 Power Line Carrier


Architecture
Processing Unit - Size 19 inches - 2U
Management
Interface

V11 data
Interface

External analog
Teleprotection
Interface

4 RS 232 data
Interface

- Processing Unit -

3 Speech
Interface

IRIG B
Interface

Reference
for E&M

e-terragridcom T390 Power Line


Carrier
Architecture

Firmware

e-terragridcom T390 Power Line Carrier


Firmware architecture
Equipment entirely based on firmware programmed function fully upgradeable
with no need to change hardware => Cost ownership reduction
By activating software key possibility to enable :
DIGITAL MODE with or not the analogue one
LAN to LAN transfer of information and/or remote configuration (in
Digital mode only)
SNMP monitoring capability
Standard firmware : Analogue on 2.5 or 4 kHz
Possibilities:
1 analogue channel
1 speech with band allocation by firmware . 2W or 4Wires / E&M
interface for PABX connection
2 Telegraph interface for external modem with bandwidth allocation
4 internal modem using the 4 RS 232 interface (Speed 300, 600 or
1200 bd)
All these mode are available in adjacent or separate mode
Additional option : IRIG B allows time synchronization of the data
logger using a GPS clock receiver.

e-terragridcom T390 Power Line Carrier


Analogue or digital

Remote configuration by IP

or mix

addressing

V11, Ethernet,
RS232 data
interfaces

Speech, E&M
IRIG B

COMPREHENSIV
E

INSTALLATION

Remote monitoring
Local and remote
Configuration

SNMP trap management

compatible with standard


Network management
system
eterragridcom MANAGEMENT
T390

MODULAR

All in front connection


Powerful IHM
Embedded configuration
tools

Embedded commissioning
tool

One 40W amplifier or 2 for


80W

Basic configuration fully


equipped

Additional service units to


accommodate even more
speech/data interfaces

e-terragridcom T390 Power Line Carrier


The new e-terragridcom T390 product range
offers:
Complete digital transmission
capability
New modular integrated concept

Permits fully IEC compliant Teleprotection

Pay for what you need

High reliability

Transmission bit rate fallback

Competitive solution

Reduced cost of ownership


Reduction of associated costs

e terragridcom
DIP
Protection Coupler

e-terragridcom DIP Protection Coupler


Generalities
Voice frequency mode on Power line carrier
Line Trap
H.V.
TRANSPORT
NETWORK

Services
Services

Line matching unit


e-terragridcom LMU

Power line
Carrier
e-terragridcom
T390

Control
command
or
SCADA

Management software
for
eIntertripping
e-terragridcom DIPterragridcom T390 and
e-terragridcom DIP

e-terragridcom DIP Protection Coupler


Operating Mode 1: Analog Single Tone Mode
Frequency coding in the 0 - 4
As part of this principle the standby state (all the contacts whose
kHz band
position is to be transmitted open) corresponds to the continuous
transmission of a Guard Frequency. If one or more contacts close,
transmission of the guard frequency stops and one or up to 4
command frequencies FC are transmitted (via closed contact or
transmitted command).

e-terragridcom DIP Protection Coupler


Operating Mode 2: Analog Dual Tone Mode
In
dual tone
mode,
guard
Frequency
coding
ineither
the 0 - the
2 kHz
bandtone or the command dual
tone is always transmitted.
When using PLC medium, at the reverse of single tone version,
using the signalling of PLC as guard tone (also called silent
mode) is impossible.
In dual tone mode, the Guard frequency is F8 and command
frequencies are coded
in a combination of 2 frequencies
between F1 and F7.
DF

F1

F2

F3

F4

F5

F6

F7

F8

e-terragridcom DIP Protection Coupler


Operating Mode 2: Analog Dual Tone Mode

8 frequency tones
DF

F1

F2

F3

F4

F5

F6

F7

F8

Command coded dual tone (F1 to F7)


F8 as guard frequency

Cmd1

F1+F2

Cmd2

F2+F3

Cmd3

F3+F4

Cmd4

F5+F6

Cmd1+2

F1+F3

Cmd1+3

F3+F5

Cmd1+4

F1+F5

Cmd 2+3

F2+F4

Cmd 2+4

F2+F6

Cmd3+4

F4+F6

Cmd1+2+3
+4
Cmd1+2+3

F4+F5

Cmd2+3+4

F2+F5

Cmd1+3+4

F1+F6

Cmd1+2+4

F3+F6

Test link

F3+F7

Guard

F1+F4

F8

e-terragridcom DIP Protection Coupler


Software Capabilities
SOFTWARE Capabilities using a PC terminal:
Hardware test
Remote configuration and test (digital)
Possibility to lock independently or simultaneously the signal
transmission and command outputs

Local and remote (digital) loop back


Inputs / Outputs forcing
transfer time directly measured in event list by clicking (digital)
2 counters for each command (received and sent)
Real time event recorder :1750 events memorized (1 ms accuracy)
Real time alarm recorder :1750 alarms memorized (1 ms
accuracy)

e-terragridcom DIP Protection Coupler


Board Arrangement

Name

Function

UT148D

CPU board

SR200

Input-output board with 4 commands for 24 to 250 Vdc


acquisition voltage.

AL137

Power supply 48 V nominal input with standard, normally


closed, alarm contacts

Position
1
2/3
5/6*

e-terragridcom DIP Protection Coupler


Terminal Block Location

P16

Tx

P11

P14
1

Rx

AUX
- BAT
- BAT
+BAT
+BAT

MAIN

- BAT
+BAT

- BAT
+BAT

Optical Fiber
Access

P10

P15

P12

P19

P20

P13
1

P18

Complete
power
supply
redundan
cy
Possibility
of
different
power

e-terragridcom DIP Protection Coupler


Technical Data

- Input / Output logic combination capacity

- Firmware Up gradable on site by simple download


- 24 to 250 VDC power supply with power supply duplication as an
option
- Up to 8 independent fast solid state relay output + 1 copy contact for
each output : Rating Max 2A, cut off power 120 W

e-terragridcom DIP Protection Coupler


Technical Data

Type tested as per IEC 60834-1 by International


Laboratory

Compliance with latest IEC standard :

IEC 68-2

EMC compliance as per

IEC 61000

Conforms to European Directives

EN 50204 Class A

EN 55011 Class A

EN 55022 Class A

Equipment is CE compliant.

e-terragridcom DIP Protection Coupler


At a Glance

Fastest transfer time


High level of reliability and security
Enhanced monitoring capabilities
Built in optical interface
Up to 8 independent commands
TESTED as per latest IEC and ANSI EMC requirement
Intuitive commissioning
Powerful HMI
Plug in board for easy hardware upgrade