First goal
Second goal
Third goal
Fourth goal
Fifth goal
Sixth goal
Guaranty a
good level
of control of
temperature
and humidity
Obtain the
first 5 goals
guarantiing
the maximum
energy saving
First goal
Elimination or
minimization
of chemical
contamination
due to the
anestetical gas
Chemical contamination
cant be filtered.
The only solution
is the dilution with a
great quantity of fresh air.
The fresh air quantity
depends from the local
Norms
First goal
Technical
considerations
Second goal
Elimination of
bacteriological
contamination
coming from
the external
environement
The bacteriological
contamination coming from
outside is eliminated
through the absolute filters
to be fitted at the end of the
supply ducts: H13 for
general surgery, and H14
for orthopedics and more
delicate operations.
Third goal
Elimination of
bacteriological
contamination
coming from the
surrounding
environments
The batteriological
contamination coming from
the surrounding
environments is eliminated
by mantaining the room is
overpressure respect to
them.
Third goal
Elimination of
bacteriological
contamination
coming from the
surrounding
environments
To mantain an environment
in over/underpressure in
respect to a reference one it
is sufficient to extract more
or less air than the one
supplied in.
Fourth goal
Reduction of
batteriological
contamination due
to the surgical team
or to the patient
himself
The endogenous
batteriological pollution
from the patient or from the
surgical team is eliminated
by filtering with absolute
filters as frequently as
possible the treated air.
How is it done?
Fifth goal
Guaranty a good
level
of control of
temperature and
humidity
Sixth goal
Obtain the first 5
goals guarantiing
the maximum
energy saving
How is it done?
Sixth goal
Obtain the first 5
goals guarantiing
the maximum
energy saving
Direct expansion
surgical room air
conditioner
MODEL OHA 3600
AIR FLOW:
3.600 m3/h
Cooling capacity
40 kW
Chilled water
surgical room air
conditioner
MODEL
OHU 6800 HR
AIR FLOW:
6.800 m3/h
Cooling capacity
60 kW
Chiller water
surgical room air
conditioner with
post-cooling
MODEL
OHU 6800 HR PC
AIR FLOW:
6.800 m3/h
Cooling capacity
60 + 30 kW
Air Distribution
in Surgical
Rooms
Necessary
Air Flow
Terminal
Filter
Distribution
Generic
Surgery
ISO 7
20 Ac/h
H13
Turbulent
Specific
Surgery
ISO 5
250 Ac/h
H14
Unidirectional
ADVANTAGES ISO 5
1) Best possible protection for the patient
2) Dynamic Overpressure of the Aseptic Nucleus
3) Faster Recovery Time of the room
4) Best comfort for the Surgical Team
5) Best Flexibility
Installation
without local
recirculation
Installation
With local
recirculation
European Community
CEN/TC 156/WG 18
United States
ASHRAE Handbook
2.000 m3/h
1.000 m3/h
total 20 ACH
Positive: 10 - 15 Pa
2.000 m3/h
4 ACH
total 20 ACH
Positive: 5 - 10 Pa
20 - 24C
20 - 23C
20 - 60%
20 - 60%
NA
NA
NA
NA
NA
NA
F7 + F9
Filtration stages
Unidirectional (laminar) ceiling
Air filters inside the unit
Final air filter
Air flows and pressures
Air speed from the ceiling
Total air flow
Minimum outdoor air flow
Minimum total ACH
Pressure relationship to adaicent rooms
Thermoigrometric conditions
Temperature:
If something different is not requested by the surgeons
Humidity:
If something different is not requested by the surgeons
AHU mechanical characteristics:
Mechanical stability of the AHU frame
Air tightness of the AHU frame
Filters by pass leakages
Thermal insulation of the frame
Commissioning tests
Particulate test: at rest
Recovery time: 100 to 1
European Community
CEN/TC 156/WG 18
United States
ASHRAE Handbook
20 - 24C
20 - 23C
20 - 60%
20 - 60%
NA
NA
NA
NA