Вы находитесь на странице: 1из 44

Sharjah University

Electric Power Distribution System Engineering


Dr. Amr El Nady

Secondary Distribution System

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Introduction
It is a part of the distribution
system which is located
between the distribution
transformer
and the
consumers property.
Secondary
distribution
systems include:
Step
down
distribution
transformers.
Secondary circuits
Meters and protection

Generally, the secondary


distribution systems are in
three-phase/single-phase
circuits
for
areas
of
residential loads and in the
three-phase circuits for
areas of industrial or

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Introduction

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Secondary Distribution System


Secondary Voltage Level
The secondary voltage level should match the voltage
requirements of the loads. The residential, commercial and
industrial loads have different voltages. There is no standard
voltage for this system because the voltage in North America is
different from the voltage in Europe and the Middle East.

Types of Secondary
Distribution
Radial
System

The radial system is used for residential, rural, light commercial


loads. The radial secondary distribution system is shown in the
next slide
4

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Secondary Distribution System


Distribution substation low voltage side

3 Primary main
Lateral fuse cutout

1 Laterals
Transformer fuse
Distribution transformer
120/240 V

Secondary main

4-20 Customers

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Secondary Distribution System


Secondary
Banking

The secondary banking exists where two or more transformers are


connected in parallel fed from a primary feeder, and to supply a load or
a group of loads
The advantages of banking of distribution transformers include
Improved voltage regulation
Improved service reliability
Improved system ability for load growth

The common schemes for the secondary banking is shown below

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Secondary Distribution System


Spot Network
It is similar to the secondarybanking system, but with
more than one transformer
connected in parallel and
connected to more than one
feeder or one bus.
It is used for the critical, highdensity loads, urban areas
and downtown areas. Also, it
is used to provide high
reliability of electric service.

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Secondary Distribution System


The Secondary Network
Generally speaking, most of the secondary systems are radialdesigned except for some specific service areas (e.g. downtown
areas or business districts, some military installations, and
hospitals) where the reliability and service continuity
considerations are far more important than the cost and
economic considerations. Therefore, the secondary systems may
be designed in grid-or-mesh-type network configurations in those
areas. They can also be built underground to avoid overhead
congestion. The figure, shown next, indicates one-line diagram of
a small segment of a secondary network supplied by three
primary feeders.

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Secondary Distribution System

The Secondary Network

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Secondary Distribution in Sharjah

The Secondary Network

10

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Secondary Distribution in Sharjah

The Secondary Network

11

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Secondary Distribution in Sharjah


33 kV
6.6 kV

0.415 kV

0.415 kV

12

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Secondary Distribution in Sharjah

Bus
section

0.415 kV

Circuit
breaker

Earth switch

6.6 kV

13

Bus
section

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Secondary Mains (feeders)


All secondary mains, (underground or overhead), are routed
along the streets and are three-phase four-wire Wye-connected
with solidly grounded neutral wire for the overhead
The cables are in three-phase or single-phase structure and they
can be installed in conduits, ducts, or directly buried in the
ground. Also, the workers should have accessibility the
underground cables.
PVC-sheet

Filler

Copper screen

PEXInsulation Conductor shield


Insulation shield
Conductor

Underground
Cable

Underground
Cable

14 Overhead
Line

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Secondary Mains (feeders)


(Some Pictures-Underground)

15

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Secondary Mains (feeders)


(Some Pictures-Underground)
In UAE, all the secondary distribution systems are underground
distribution because it is more safe, but it is more expensive.

16

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Secondary Mains (feeders)


(Some Pictures-Overhead)

17

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Protection System
(Limiters)
To have fast clearing for some
faults, limiters are used. The
limiters are a high-capacity fuse, it
can be installed in each phase
conductor of the secondary main
at each junction point.
The limiters fusing or time-current
relations are designed to allow the
normal network current to pass
without melting but to operate and
clear a faulted section of the main
before the cable insulation is
damaged
by
the
heating
generated in the cable by fault
current.
Its characteristics should be
coordinated with the upstreamsystem protection in order to
minimize the isolated faulty area.

18

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Protection System
(Limiters)

19

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Protection System
(Fuse)

20

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Protection System
(Fuse-Pictures)

21

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Protection System
(Fuse-Pictures)

22

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Protection System
(Circuit Breaker)
What is the circuit breaker?
A Circuit Breaker (CB) is basically a switch used to interrupt the flow of
current. It opens based on a relay command. The relay command initiates
mechanical separation of the contacts. It is a complex element because it
has to handle large voltages (few to hundreds of kV's) and currents (in
kA's). Interrupting capacity of the circuit breaker is therefore expressed in
MVA.
Power systems under fault behave more like inductive circuits. X/R ratio of
lines is usually much greater than unity. For 400 kV lines, it can be higher
than 10 and it increases with voltage rating. From the fundamentals of
circuit analysis, we know that current in an inductive circuit (with finite
resistance) cannot change instantaneously. The abrupt change in current,
if it happens due to switch opening, will result in infinite di/dt and hence will
induce infinite voltage. Even with finite di/dt, the induced voltages will be
quite high. The high induced voltage developed across the CB will ionize
23
the dielectric between its terminals.

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Protection System
(Circuit Breaker)
What is the circuit breaker?
This results in arcing. When the current in CB goes through the natural
zero, the arc can be extinguished (quenched). However, if the interrupting
medium has not regained its dielectric properties then the arc can be
restruck. The arcing currents reduce with passage of time and after a few
cycles
the
current
is
finally
interrupted.
Usually CB opening time lies in the 2-6 cycles range. CBs are categorized
by the interrupting medium used. Minimum oil, air blast, vacuum arc and
SF6 CBs are some of the common examples. CB opening mechanism
requires much larger power input than what logical element relay can
provide. Hence, when relay issues a trip command, it closes a switch that
energizes the CB opening mechanism powered by a separate dc source
(station battery). The arc struck in a CB produces large amount of heat
which also has to be dissipated.
24

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Protection System
(Network Protector)
The network protector, (NP), consists of an air circuit breaker
with a closing and tripping mechanism controlled by relays,
and backup fuses.
The functions of a NP are
Fault isolation with the minimum service interruption for the customers.
Open the circuit if huge instantaneous power flow is reversed

25

Simple Example of Protection Coordination

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Network Protectors

Simple Example for NP for Spot Network


26

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Protection System
(Network Protector)

Simple Example for NP for Spot Network


27

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Network Protectors
(Picture)

Network Protector
28

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Distribution Transformers
The distribution transformers can be mounted on poles or
platforms depending on their sizes and ratings. These
transformers may be three-phase or single-phase

29

Pole Mounted Transformers

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Distribution Transformers

Pad Mounted Transformers


30

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Distribution Transformers

Vaults for Underground Transformers


31

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Secondary Distribution In Sharjah

32

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Secondary Distribution In Sharjah

33

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Voltage Calculations In Secondary Distribution S


Example 1
For the residential secondary distribution system shown in the Figure of the
next slide. Assume the following:
The distribution transformer capacity is 75 kVA,
All secondaries and services are single-phase, three wire, normally 120
/ 240 V, (all loads are connected to 240 V)
All secondary lines are of # 2/0 Al/Cu XLPE cable, (it is the lateral)
Service drops are of # 1/0 Al/Cu XLPE cable, (it is the sub-lateral)
All service drops are 100 ft long, (sub-lateral length)
All secondary lines are 200 ft long, (lateral length)
Average lagging load power factor of 0.9
Assume the drop over the main is neglected
Determine:
The total load on the transformer in kVA and in pu.
34
The total steady-state voltage drop in pu at the most
remote and severe
customers meter for the given annual maximum system load.

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Voltage Calculations In Secondary Distribution S

Sublateral
Main
Lateral

35

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Voltage Calculations In Secondary Distribution S


Table A: Single-phase 7200-120/240 V distribution transformer data
at 65C
Rated
kVA

Core Loss
kW

Copper Loss
kW

Rpu

Xpu

Excitation
Current
Apu

15

0.083

0.194

0.013

0.0094

0.014

25

0.115

0.309

0.0123

0.0138

0.015

37.5

0.17

0.4

0.0107

0.0126

0.014

50

0.178

0.537

0.0107

0.0139

0.014

75

0.28

0.755

0.0101

0.0143

0.014

100

0.335

0.975

0.0098

0.0145
36

0.014

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Voltage Calculations In Secondary Distribution S


Table B: Twin concentric Al/Cu XLPE cable data
~

K cable
*

R(/1000 ft) per conductor


Size

X(/1000
ft)
per phase
conductor

Direct-burial
Ampacity
A

Phase
conductor
90C

Neutral
Conductor
80C

2 AWG

0.334

0.561

0.0299

1 AWG

0.265

0.419

1/0 AWG

0.21

2/0 AWG

(per unit voltage


drop per (A.ft))*10-4

90 % PF

50 % PF

180

0.02613

0.01608

0.305

205

0.02098

0.01324

0.337

0.0297

230

0.01683

0.01089

0.167

0.259

0.029

265

0.0136

0.00905

3/0 AWG

0.132

0.211

0.028

300

0.01092

0.00752

4/0 AWG

0.105

0.168

0.0275

340

0.00888

0.00636

250
kcmil

0.089

0.133

0.028

370

0.00769

0.00573

350
kcmil

0.063

0.085

0.027

445

0.00571

0.00458

500
kcmil

0.044

0.066

0.026

540

0.00424

0.00371

37

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Voltage Calculations In Secondary Distribution S


Solution
Assume perfectly balanced loading in all three-wires single-phase
circuits, and nominal operating voltage of 240 V when computing
currents from kVA loads.
The total load of the transformer is
ST = (3+2+8+6) + (5+6+7+4) + (6+7+8+10) = 72 kVA.
ST, pu = ST / Sbase = 72 / 75 = 0.96 pu.
To calculate the total steady-state voltage drop in pu at the most remote
and service customers meter. We have to calculate the per unit voltage
drops in the transformer, the service line (over lateral), and that of the
most remote and severe customer (over sub-lateral). This is carried out
as follows:
38

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Voltage Calculations In Secondary Distribution S


For the transformer:
Solution
VDTr = ZI = (0.0101+j0.0143)*0.96
= 0.0168 angle(26.9) and the angle can be neglected
where R = 0.0101 pu and X = 0.0143 pu are found from Table A.
For the service lines (lateral):
Ilateral = Smax / Voperating = (6+7+8+10)kVA / 240 V =31k / 240 = 129.17 A.
K= 0.0136 from Table B.
VDlateral=Kcable(Ilateral x l) x 10-4 = 0.0136 (129.17 x 200) x 10-4 = 0.03513 pu.
For the service drops (Sub-lateral):
Isub-lateral = Ssub-lateral-max / Voperating = 10 kVA / 240 V =41.67 A.
K = 0.01683 from Table B.
VDsub-lateral = Kcable (Isub-lateral x l) x 10-4 = 0.01683 (41.67 x 100) x 10-4 =
0.007 pu.
Total voltage drop:
39
VDtotal = VDTr + VDlateral +VDsub-lateral=0.0168+ 0.03513 + 0.007 = 0.0589 pu.

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Voltage Calculations In Secondary Distribution S


It can be noticed from the previous example that the voltage was
Solution
assumed
to be constant along the feeder. (i.e., 240V)
This is not correct as there will be voltage drop in the line.
However, the voltage drop will be very small and the exact
calculation will be as in the coming slide:
Vlateral = 1 0.0168 = 0.9832
For the service lines:
Ilateral = Slateral-max / Voperating = (6+7+8+10)kVA / (0.9832*240) V =
131.1 A.
K = 0.0136 from Table B.
VDlateral = K (Ilateral x l) x 10-4 = 0.0136 (131.1 x 200) x 10-4 =
0.035pu.
For the service drops:
V sub-lateral= 0.9832 .03566 = 0.9475
40

Isub-lateral = Ssub-lateral-max / Voperating = 10 kVA / (.9475*240) V =43.88 A.

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Voltage Calculations In Secondary Distribution S


Total voltage drop:
VDtotalSolution
= VDTr + VDlateral +VDsub-lateral=0.0168 + 0.03566 + 0.0074 = 0.0599 pu.

41

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Voltage Calculations In Secondary Distribution S


Solution
Example
2
The system, shown below, is a single phase AC. Assume the
impedance of the feeder is 0.001+j0.005 /m, the voltage at point
A is 2500 V and at point B is 2401.5 V, find the voltage drop
between points C and D.

0.8 lagging

0.9 lagging

Solution
The current in segment AC is assumed to be IT,
so the current is segment CD will be IT (40-j30),
and the current in segment DB will be IT (40-j30) 42
(9-j4.35)

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Voltage Calculations In Secondary Distribution S


The impedances of each line segment will be:

Z AC 200 0.001 j 0.005 0.2 j1.0

Z CD 700 0.001 j 0.005 0.7 j 3.5


Z DB 100 0.001 j 0.005 0.1 j 0.5

V AB 2500 2401.5 10 j 6.28 11.8 32.12V


Apply KVL:

V AB I T (0.2 j 1) I T 50 36.9 (0.7 j 3.5)


I T 50 36.9 10 25.8 (0.1 j 0.5)

43

Sharjah University
Electric Power Distribution System Engineering
Dr. Amr El Nady

Voltage Calculations In Secondary Distribution S


Solving the above equation will result in:

I T 37.64 48
So, the voltage drop between C and D:

V drop I T 50 36.9 0.7 j 3.5 53.4251

Solution
Special
Case (ring bus-bar)

44

Вам также может понравиться