PD 1185

THE FIRE CODE OF THE


PHILIPPINES
AND REGULATIONS

BACKGROUND
LEVEL OF FIRE SAFETY is defined through
requirements directed at:
Prevention of Ignition
Detection of Fire
Control of the Fire Department
Confinement of the Effects of Fire
Extinguishing of Fire
Provision of Refuge and/or Evacuation Facilities
Staff Reaction
Provision of Fire Safety Information

BACKGROUND
LEVEL OF FIRE SAFETY is defined
through requirements directed at:
Prevention of Ignition
Detection of Fire
Control of the Fire Department
Confinement of the Effects of Fire
Extinguishing of Fire
Provision of Refuge and/or
Evacuation Facilities
Staff Reaction
Provision of Fire Safety Information

BUILDING SERVICE
& FIRE PROTECTION
EQUIPMENT

ARCHITECTURAL
INTERVENTIONS
ARCHITECTURAL
COMPONENTS

BACKGROUND
BUILDING SERVICE AND FIRE PROTECTION
EQUIPMENT:
Utilities
Heating, Ventilation, Air-conditioning
Smoke Control
Elevators, Escalators
Rubbish Chutes, Incinerators and Laundry
Chutes
Fire Detection, Alarm, Communication Systems
Automatic Sprinklers and other Extinguishing
Equipment

BACKGROUND
FIRE CONTAINING ARCHITECTURAL
COMPONENTS
Firewalls
Resistive Floors
Resistive Walls
Curtain Boards
Shutters
Dampers
Self-closing Doors

Title
Declaration of Policy
Scope and
Application
General Building
Requirements
Site Requirements
Definitions

LIGHT & VENTILATION


PD 1096
THE NATIONAL BUILDING CODE/ IRR RULE XI

BACKGROUND
THE FIRE EXIT PLAN
The door in itself is not a fire exit
The Egress System is made up of:
THE EXIT/EGRESS ACCESS:

leads to an exit

THE EXIT: separated from all other spaces of the


building or structure by construction or
equipment to provide a protected way of travel to
the exit discharge
THE EXIT DISCHARGE : means of egress between
the termination of an exit and a public way

CORRIDORS AND EXTERIOR EXIT BALCONIES


any covered or enclosed exit passageways including
walkways, tunnels, walls
can include foyers, lobbies and reception room

Scope
Exit Obstruction
Doors
Corridor and
Exterior Balconies
Stairways

do not include railings and partitions below 1.5m.

Ramps

handrails & fully opened doors should not reduce


width by 8cm; doors in any position should not
reduce width by more than half

Exit Enclosures

required 2m clearance

Exit Passageway

Horizontal Exit
Smoke proof
Enclosures
Exit Courts
Signs and
Illumination

access to all exits

rule 4: MAINTENANCE OF
EXIT WAYS
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Scope

GENERAL SAFETY
REQUIREMENTS:

General Safety
Requirements

Fire Suppression Devices,


Equipment, Systems
Fire Safety Construction

Required Fire
Safety
Programs/Measures
Changes in
Occupancy
Definitions

Fire Protection and Warning


System
rule 1: GENERAL PROVISIONS
division 1- GENERAL
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Scope

CLASSES OF FIRE
Class A- ordinary combustible materials
such as wood, cloth, paper, rubber and
plastics
Class B- flammable liquids and gases

General Safety
Requirements
Required Fire
Safety
Programs/Measures
Changes in
Occupancy
Definitions

Class C- energized electrical equipment


Class D- combustible metals such as
magnesium, sodium, potassium
rule 1: GENERAL PROVISIONS
division 1- GENERAL
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

DEGREE OF HAZARD:
probability that a building, structure or facility may
catch fire

General Safety
Requirements
Required Fire
Safety
Programs/Measures

difficulty in evacuating people


difficulty in suppressing fire

Changes in
Occupancy

Determinants :

Scope

construction materials used


combustibility of contents
type of occupancy and load capacity
height from ground level
firefighters travel distance
fire safety construction ;
protective/warning systems

Definitions

rule 1: GENERAL PROVISIONS


division 1- GENERAL
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Automatic Fire Suppression System:


an integrated system of underground or overhead piping or
both connected to a source of extinguishing agent or
mediumwhich when actuated by its automatic detecting
device suppresses fire.
Fire Alerting System:
a fire alarm system activated by the presence of a fire,
where the signal is transmitted to designated locations
instead of sounding a general alarm, in order to prevent
panic

Scope
General Safety
Requirements
Required Fire
Safety
Programs/Measures
Changes in
Occupancy
Definitions

Fire Protective Assembly:


incorporated in a structure to prevent spread of fire.
Examples are dampers, curtain boards, fire stoppers

rule 1: GENERAL PROVISIONS


division 1- GENERAL
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Dry Standpipe: standpipe system in which pipes are


not filled with water. Water is introduced thru fire
service connections when needed.
Fire Wall: designed to prevent spread of fire, having a
fire resistance of not less than 4 hours with sufficient
structural stability to remain standing even if
construction on either side collapses under fire
conditions.

Scope
General Safety
Requirements
Required Fire
Safety
Programs/Measures
Changes in
Occupancy
Definitions

Means of Egress: a continuous and unobstructed


route of exit from any point in a building, structure or
facility to a public way.

rule 1: GENERAL PROVISIONS


division 1- GENERAL
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Fire Retardant: any compound or mixture, which


when applied properly improves the fire resistant
quality of fabrics and other materials.
Panic Hardware: a mechanical device consisting of
linkages and a horizontal bar across a door, which
when pushed from inside will case the door to open
and facilitate exit from a building.

Scope
General Safety
Requirements
Required Fire
Safety
Programs/Measures
Changes in
Occupancy
Definitions

Organic Coating: a liquid mixture of binders and


combustible solvents, which when spread on a
surface becomes a durable protective and decorative
finish.

rule 1: GENERAL PROVISIONS


division 1- GENERAL
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Fire Resistance Rating:


Scope

time duration that a material or construction can


withstand the effect of a hundred fire test
Flame Spread Rating:
time in which flame will spread over the surface of a
burning material

General Safety
Requirements
Required Fire
Safety
Programs/Measures
Changes in
Occupancy
Definitions

Smoke Developed Rating:


a rating of combustible material based on the density
and volume of smoke developed within a certain
period of time when its surface is ignited

rule 1: GENERAL PROVISIONS


division 1- GENERAL
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

EXIT COMPONENTS shall be constructed as an integral part


of the building or shall be permanently affixed thereto.
Permissible exit
components

SEPARATION OF EXITS:
- 1-hour fire resistance rating for 3 stories or less
- 2-hour fire resistance rating for 4 or more stories
- any opening in the separation shall be enclosed by an approved
self-closing fire door

The TRAVEL DISTANCE to an exit shall be measured on


the floor or other walking surface along the center line of the
natural path of travel, starting 30cm.from the remote point,
curving around any corner or construction with a 30cm.
Clearance therefrom, and ending at the center of the
doorway or other point at which the exit begins.

Protective enclosure
of exits
Width and capacity
of means of egress
Egress capacity and
occupant load
Arrangement of exit
Exit distance and
dead-end limits
Travel distance &
access to exits

rule 1: GENERAL PROVISIONS


div 4- MEANS OF EGRESS
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

A door from a room to an exit


or to a way of exit access
shall be of the side-hinged,
swinging type; It shall swing
with exit travel when
occupied by 50+ persons or
used for high hazard
occupancy

In no case shall access to


exit be through a bathroom,
bedroom or other room
subject to locking, except
where the exit is required to
serve only the bedroom or
other room subject to locking
or adjoining rooms
constituting part of the same
dwelling or apartment used
for single family occupancy.

Permissible exit
components
Protective enclosure
of exits
Width and capacity
of means of egress
Egress capacity and
occupant load
Arrangement of exit

Decorations or draperies shall not be placed on exit doors.

Exit distance and


dead-end limits

Mirrors shall not be placed in or adjacent to any exit in such a


manner as to confuse the direction of exit.

Travel distance &


access to exits

rule 1: GENERAL PROVISIONS


div 4- MEANS OF EGRESS
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

All exits shall terminate directly at a public way or at


an exit discharge.

Permissible exit
components
Protective enclosure
of exits
Width and capacity
of means of egress

in no case shall the ceiling height (headroom) be less


than 2.3 meters nor any projection from the ceiling be
less than 2.0 meters from the floor

Egress capacity and


occupant load
Arrangement of exit
Exit distance and
dead-end limits
Travel distance &
access to exits

rule 1: GENERAL PROVISIONS


div 4- MEANS OF EGRESS
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

UNITS OF EXIT WIDTH


only the clear width of the
doorway when the door is in
the open position shall be
measured; any projections
into the doorways by
doorstops or by the hinge
stile shall be disregarded

Permissible exit
components
Protective enclosure
of exits
Width and capacity
of means of egress
Egress capacity and
occupant load

where a doorway is divided


by mullions, the exit width
shall be the sum of the units
of exit width measured
separately for each
individual door

Arrangement of exit
Exit distance and
dead-end limits
Travel distance &
access to exits

rule 1: GENERAL PROVISIONS


div 4- MEANS OF EGRESS
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

UNITS OF EXIT WIDTH


single door in a doorway
shall not be less than .71m
and not more than 1.22m.

panic hardware
maintenance of
locks
power operated
doors

CHANGES IN LEVEL

revolving doors

floor on both sides of a door


shall have the same
elevation on both sides, for
a distance at least equal to
the width of the widest
single door
when a door discharges to
the outside, change in floor
level shall not be more
than .205m.

turnstiles
folding partitions

rule 1: GENERAL PROVISIONS


div 4- MEANS OF EGRESS

PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

TREADS AND RISERS


sum of 2 risers and a tread
exclusive of nosing
projection should be
between .60-.635m

classes of stairs
treads and riser
enclosure of
interior stairs

minimum number of risers


in any 1 flight is 3

stair details
guards and
handrails

treads and landing floor


shall be solid

monumental
stairs

LOADS

outside stairs

Stair, platform, landing, balcony


and stair hallway shall carry a
load of 88 kg.per sq.m. or a
concentrated load of 136 kg.

rule 1: GENERAL PROVISIONS


div 4- MEANS OF EGRESS

PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

HORIZONTAL EXIT
EXIT PASSAGEWAY
is a way of passage from
one building to an area of any hallway, corridor, passage
refuge in another building
or tunnel protected by
on approximately the same
separation, and with solid
level
floor
or a way of passage through
or around a wall or partition
to an area of refuge on
approximately the same
level in the same building

Class A ramp - 8-10% slope


Class B ramp - 10-17%

horizontal exits
egress from area
of refuge
bridges and
balconies
openings through
walls for
horizontal exits
fire partitions
ramps

every fire section shall have, in addition to the


horizontal exit or exits at least 1 stairway, doorway
leading outside, or other standard exit

exit
passageways

rule 1: GENERAL PROVISIONS


div 4- MEANS OF EGRESS
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

HORIZONTAL EXIT

Scope

may be considered as a required exit


fire-resistance, opening protection and discharge
areas shall be maintained

Exit Obstruction
Doors
Corridor and
Exterior Balconies
Stairways
Ramps
Horizontal Exit
Exit Enclosures
Smoke proof
Enclosures
Exit Courts
Exit Passageway
Signs and
Illumination

rule 4: MAINTENANCE OF
EXIT WAYS
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

FIRE ESCAPE STAIRS


may be used as required means of egress only for existing
buildings
shall not constitute more than 50% of required exit capacity

fire escape stairs


ladders and slide
escapes

LADDERS: cannot be used as fire escape, spaced at 3m,


positively inclined

SLIDE ESCAPES: where permitted as required exits,


shall be rated at 1 exit unit per slide, with rated travel
capacity of 60 persons per minute

rule 1: GENERAL PROVISIONS


div 4- MEANS OF EGRESS
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

EMERGENCY LIGHTING
shall be arranged to maintain specified level of
illumination in the event of failure of the normal lighting
for a period of at least 1.5 hours in buildings more than
36.5 meters in height

emergency
lighting
exit marking

EXIT SIGNS
every exit shall have
the word EXIT in
plainly legible letters
not less than 15cm
height with principal
strokes of letters at
least 19mm wide

rule 1: GENERAL PROVISIONS


div 4- MEANS OF EGRESS
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

combination of an automatic or smoke detection system,


automatic exhaust system and an automatic water curtain

vertical openings
and concealed
spaces
escalator
openings

sprinkler vent
method
spray nozzle
methods
rolling shutter
method
partial enclosure
method
fire-stopping
concealed
spaces

rule 1: GENERAL PROVISIONS


div 5- FEATURES OF FIRE
PROTECTION

PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

combination of an automatic or smoke detection system,


automatic exhaust system and an automatic water curtain
combination of an automatic fire or smoke detection system
and a system of high velocity water spray nozzle

vertical openings
and concealed
spaces
escalator
openings
sprinkler vent
method

spray nozzle
methods
rolling shutter
method
partial enclosure
method
fire-stopping
concealed
spaces

rule 1: GENERAL PROVISIONS


div 5- FEATURES OF FIRE
PROTECTION

PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

combination of an automatic or smoke detection system,


automatic exhaust system and an automatic water curtain
combination of an automatic fire or smoke detection system
and a system of high velocity water spray nozzle
automatic self-closing rolling shutter which completely
encloses the top of each escalator

vertical openings
and concealed
spaces
escalator
openings
sprinkler vent
method
spray nozzle
methods

rolling shutter
method
partial enclosure
method
fire-stopping
concealed
spaces

rule 1: GENERAL PROVISIONS


div 5- FEATURES OF FIRE
PROTECTION

PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

combination of an automatic or smoke detection system,


automatic exhaust system and an automatic water curtain
combination of an automatic fire or smoke detection system
and a system of high velocity water spray nozzle
automatic self-closing rolling shutter which completely
encloses the top of each escalator
kiosk designed to provide an effective barrier to the spread
of smoke from floor to floor

vertical openings
and concealed
spaces
escalator
openings
sprinkler vent
method
spray nozzle
methods
rolling shutter
method

partial enclosure
method
fire-stopping
concealed
spaces

rule 1: GENERAL PROVISIONS


div 5- FEATURES OF FIRE
PROTECTION

PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

combination of an automatic or smoke detection system,


automatic exhaust system and an automatic water curtain
combination of an automatic fire or smoke detection system
and a system of high velocity water spray nozzle
automatic self-closing rolling shutter which completely
encloses the top of each escalator
kiosk designed to provide an effective barrier to the spread
of smoke from floor to floor
concealed space in which exposed materials with flamespread rating greater than class A are fire-stopped

vertical openings
and concealed
spaces
escalator
openings
sprinkler vent
method
spray nozzle
methods
rolling shutter
method
partial enclosure
method

fire-stopping
concealed
spaces

rule 1: GENERAL PROVISIONS


div 5- FEATURES OF FIRE
PROTECTION

PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Assembly
Educational

Classification of
Occupancy

Institutional

Hazard of Contents

Residential
Mercantile
Business
Industrial
Storage
Mixed
Occupancies
Miscellaneous

rule 3: FIRE SAFETY IN BUILDINGS,


STRUCTURES AND FACILITIES
div 3- CLASSIFICATION OF OCCUPANCY &
HAZARD OF CONTENTS

PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Assembly
Educational

main exit must accommodate 1/2 of occupant


load

Institutional travel distance not to exceed 46 meters if not


Residential

protected by automatic fire suppression; 61


meters if protected

Mercantile

Multiple Seating

Business

rows of seats between aisles shall not have more than 14


seats; 7 if row opens to 1 aisle only

Industrial

back to back spacing, not less than .83 m

Storage

seats w/o dividing arms must allow .60m per person

Mixed
Occupancies

aisle width:
0.91-1.00 for more than 60 seats;
0.76 for less than 60 seats

Miscellaneous

rule 3: FIRE SAFETY IN BUILDINGS,


STRUCTURES AND FACILITIES
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Assembly

Class AEducational
Class BInstitutional
Residential
Mercantile

1000 or more
600 or more
300-600

4 exits
3 exits
2 exits

Classification of
Occupancy
Hazard of Contents

Class C- OCCUPANT
50- 300 LOADS
2 exits

Business
Industrial
Storage
Mixed
Occupancies

concentrated use w/o fixed seats such as an auditorium,


church, dance floor, lodge room
- .65sq.m./person
less concentrated use such as conference room, dining
room, exhibit room, gymnasium
- 1.4 sq.m./person
standing room or waiting space

Miscellaneous

- 0.28 sq.m./person

rule 1: GENERAL PROVISIONS


div 7- PLACES OF ASSEMBLY

PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Assembly
Educational
Institutional
Residential
Mercantile
Business
Industrial
Storage
Mixed
Occupancies
Miscellaneous

every room or space with a capacity of


over 50 persons or over 93 sq.m. in area
shall have at least 2 doorways providing
access to separate exits; where egress is
through corridors, shall open to a
common corridor leading to separate exits
in opposite directions

Classification of
Occupancy
Hazard of Contents

OCCUPANT LOADS
classroom

- 1.80 sq.m./person

shops, laboratories, vocational rooms - 1.40 sq.m./person


dry nurseries w/ sleeping facilities

- 3.25 sq.m./person

rule 1: GENERAL PROVISIONS


div 8- EDUCATIONAL OCCUPANCIES

PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Assembly

CLASSIFICATION

Educational

Health Care Facilities (Hospitals and Nursing Homes)

Institutional
Residential
Mercantile
Business

Residential Custodial Care (Nurseries, Home for the


Aged, Mentally-retarded Care)

Definitions
Classifications
General
requirements

Residential-Restrained Care (Penal Institutions,


Reformaries, Jails)

OCCUPANT LOADS
sleeping departments

- 11 sq.m./person

Industrial

in-patient treatment departments - 22 sq.m./person


Storage dry nurseries w/ sleeping facilities - 3.25 sq.m./person
elevators and revolving doors shall not be
Mixed
Occupancies counted as required exits

Miscellaneous

New/ Existing
hospital, nursing
homes & residential
custodial care

rule 1: GENERAL PROVISIONS


div 9- INSTITUTIONAL OCCUPANCIES

PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Assembly

CLASSIFICATION

Educational

Hotels (more than 15 sleeping accommodations for hire


Apartment Buildings (3 or more living units w/
independent cooking and bathroom facilities)

Institutional
Residential
Mercantile
Business
Industrial

Definitions
Classifications
General
requirements

Dormitories (group sleeping accommodations for persons


not members of the same family)

Lodging or Rooming Houses (separate rented living


rooms for 15 or less, on transient or permanent basis)
Single and 2-family Dwelling (detached dwellings where
each unit is occupied by family members)

Storage

OCCUPANT LOAD

Mixed
Occupancies

18.60/ person (except for single & 2-family dwellings

Miscellaneous

New/ Existing
hospital, nursing
homes & residential
custodial care

rule 1: GENERAL PROVISIONS


div 10- RESIDENTIAL OCCUPANCIES

PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Assembly

CLASSIFICATION

Educational

Class A: stores with gross area of 2,787 sq.m. or more or


utilizing more than 3 levels for sales purposes

Institutional
Residential
Mercantile
Business

Class B: stores with gross area of 287 to less than 2787


sq.m. Utilizing floor above or below street floor level for
sales purposes

Class C: stores with gross area of less than 287sq.m.


utilizing street floor only for sales.

Classification
General
requirements
Protection
Building service
equipment
Special provisions

OCCUPANT LOAD

Industrial

street floor/ below street floor

- 2.8 sq.m./person

Storage

upper floors

- 5.6 sq.m./person

floors not open to public


Mixed
covered malls
Occupancies

- 9.3 sq.m./person

Miscellaneous

- 2.8 sq.m./person

rule 1: GENERAL PROVISIONS


div 11- MERCANTILE OCCUhPANCIES

PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Assembly

Classification

Educational
Institutional CLASSIFICATION
Residential office occupancy shall be classified as Light Hazard
Occupancy
Mercantile
Business
Industrial

OCCUPANT LOAD
business

Storage

General
requirements
Exit details
Protection
Building service
equipment
High-rise buildings

- 9.3 sq.m./person

HIGH-RISE BUILDINGS
Buildings over 15 meters shall be provided

Mixed
throughout with automatic sprinkler protection
Occupancies
Miscellaneous

rule 1: GENERAL PROVISIONS


div 12- BUSINESS OCCUPANCIES

PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Assembly

CLASSIFICATION

Classification

Educational General Industrial: all except high hazard


manufacturing operations

General
requirements

Institutional
Special Purpose: contents liable to burn with extreme
Residential
rapidity or from which poisonous fumes or explosions

are feared
Mercantile

Special Purpose
Open industrial

Open Industrial: operations conducted in open air

Business
Industrial

General industrial

OCCUPANT LOAD
industrial

Storage
Mixed
Occupancies
Miscellaneous

- 9.3 sq.m./person

every high hazard occupancy shall have


automatic fire suppression system
protection or such other protection
appropriate to the particular hazard

rule 1: GENERAL PROVISIONS


div 13- INDUSTRIAL OCCUPANCIES

PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Assembly

CLASSIFICATION of CONTENTS

Educational ordinary hazard


Institutional high hazard
Residential low hazard
Mercantile
Parking garages of closed or open type, above or
Business

below ground

Industrial

storage of servicing areas

Classification
Occupancy
General storage
Special provisions
for garages
Special provisions
for aircraft hangars
Special provisions
for grain elevators

Storage
Mixed
Occupancies
Miscellaneous

rule 1: GENERAL PROVISIONS


div 14- STORAGE OCCUPANCIES

PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

EXIT OBSTRUCTION

Scope
Exit Obstruction

obstruction

Doors

overcrowding

Corridor and
Exterior Balconies

aisles

Stairways

fire escapes

Horizontal Exit

Ramps
Exit Enclosures

storage of materials

Smoke proof
Enclosures
Exit Courts
Exit Passageway
Signs and
Illumination

rule 4: MAINTENANCE OF
EXIT WAYS
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

DOORS

Scope

openable from inside w/o keys,


effort and special knowledge
approved bolting devices

Exit Obstruction
Doors
Corridor and
Exterior Balconies
Stairways
Ramps

readily distinguishable

Horizontal Exit
Exit Enclosures
Smoke proof
Enclosures
Exit Courts
Exit Passageway
Signs and
Illumination

rule 4: MAINTENANCE OF
EXIT WAYS
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

STAIRWAYS

Scope

handrail projection up to 9cm from each side

Exit Obstruction
Doors

headroom clearance of 195cm

Corridor and
Exterior Balconies

1-hour resistive construction for storage underneath

Stairways
Ramps
Horizontal Exit
Exit Enclosures
Smoke proof
Enclosures
Exit Courts
Exit Passageway
Signs and
Illumination

rule 4: MAINTENANCE OF
EXIT WAYS
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

RAMPS

Scope
Exit Obstruction

1/8 or 12.5% slope

Doors

handrails required for slopes of 1/10 or higher

Corridor and
Exterior Balconies

rough, non-slip material

Stairways
Ramps
Horizontal Exit
Exit Enclosures
Smoke proof
Enclosures
Exit Courts
Exit Passageway
Signs and
Illumination

rule 4: MAINTENANCE OF
EXIT WAYS
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

EXIT ENCLOSURES

Scope

include landings, floors connecting flights of


stairs, ground floor corridor from stairs to
building exterior
no openings except doorways and exterior wall
openings
self-closing and automatic doors
should not continue beyond grade level
no enclosed usable space under stairs in exit
enclosure

Exit Obstruction
Doors
Corridor and
Exterior Balconies
Stairways
Ramps
Horizontal Exit
Exit Enclosures
Smoke proof
Enclosures
Exit Courts
Exit Passageway
Signs and
Illumination

rule 4: MAINTENANCE OF
EXIT WAYS
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

SIGNS AND ILLUMINATION

Scope

light intensity of at least 1 footcandle at floor


level
main exit doors need not be sign posted
exit signs illuminated with 2 electric lamps of
not less than 5 watts each

Exit Obstruction
Doors
Corridor and
Exterior Balconies
Stairways
Ramps
Horizontal Exit
Exit Enclosures
Smoke proof
Enclosures
Exit Courts
Exit Passageway
Signs and
Illumination

rule 4: MAINTENANCE OF
EXIT WAYS
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

DEFINITIONS
Installation
Removal

COMBINATION STANDPIPE: a fire line system


with a constant water supply and installed for
the use of the Fire Service and the occupants of
the building

Maintenance

DRY STANDPIPE: a fire line system without a


constant water supply, is equipped with a fire
service inlet and outlet connections and installed
exclusively for the use of the Fire Service

Detailed installation
requirements

Foam fire protection


Vaporizing liquid
Parking stations

Buildings under
construction

rule 6: FIRE PROTECTION


APPLIANCES
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

DEFINITIONS

Installation
Removal

WET STANDPIPE: is an auxilliary fire line


system with a constant water supply installed
primarily for emergency fire use by the
occupant of the building
FIRE DEPARTMENT HOUSE CONNECTION:
is a hose connection at grade or street level for
use by the Fire Service only

Maintenance
Foam fire protection
Vaporizing liquid
Parking stations
Detailed installation
requirements
Buildings under
construction

rule 6: FIRE PROTECTION


APPLIANCES
PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

a device that contains within it chemicals,


fluids, or gases for extinguishing fires, the
means for application of its contents for
that purpose, and is capable of being
readily moved from place to place
servicing portable fire extinguishers includes any
or all of the following- charging, filling,
maintaining, recharging, refilling, repairing and
testing

rule 37: FIRE EXTNGUISHER


PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

HIGH RISE BUILDING- one which is


at least 15 meters high measured from the
floor of the topmost level to the ground
level

rule 40: HIGH RISE BUILDINGS


PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Automatic fire suppression


systems- high rise buildings shall be
protected with approved type of automatic
fire suppression systems installed in
accordance with internationally recognized
standards
must protect all spaces including every
closet and concealed spaces

rule 40: HIGH RISE BUILDINGS


PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Exits- all stairwells shall be enclosed and


protected
all doors on stairwells shall be kept closed
First aid protection- each floor shall
be provided with at least 19mm lightweight
flexible hose providing water at 19-38liters
per minute for 30 minutes

rule 40: HIGH RISE BUILDINGS


PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

Emergency escape- capable of


attachment and use for escape from
windows
this means of escape shall not exceed 25%
of the required number of units of exit
widths

rule 40: HIGH RISE BUILDINGS


PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS

rule 40: HIGH RISE BUILDINGS


PD 1185
THE FIRE CODE OF THE PHILIPPINES
AND REGULATIONS