Академический Документы
Профессиональный Документы
Культура Документы
Ring Bus
The Ring Bus configuration is shown in Fig-F. The
breakers are so connected and forms a ring. There
are isolators on both sides of each breaker. Circuits
terminate between the breakers. The number of
breakers is same as the numbers of circuits. Each of
the circuits in ring bus system is fed from both
sides. Any of the breaker can be opened and
isolated for maintenance without interrupting any of
the circuits. A fault on any of the circuit is isolated
by tripping of two breakers on both sides of the
circuit. By tripping the two breakers only the faulted
circuit is isolated and all other circuits continue to
operate in open ring state. This scheme has good
operational flexibility and high reliability. The main
disadvantage is that when a fault happens and the
ring is split and may result into two isolated
sections. Each of these two sections may not have
the proper combination of source and load circuits.
To avoid this as far as possible the source and load
circuits should be connected side by side (see
figure). The ring bus scheme can be expanded to
accommodate more circuits. The ring bus scheme is
not suitable for more than 6 circuits (although