ENTEC ELECTRIC & ELECTRONIC

CO., LTD

Main Products
PRODUCTS

Gas Insulated Recloser

ENhanced TEChnology 2
PRODUCT

POLE MOUNT SF6 GAS INSULATED LOAD BREAK SWITCH

Load current making and breaking in


SF6 gas with puffer principle.

Stainless steel enclosure and


pressure rupture device.

Porcelain bushing and mold-cone


lead or EPR bushing available.

Manual and motor operation.

The basic mechanism is operator independent quick close and quick open
spring toggle mechanism.

Microprocessor based controller for feeder automation.

ENhanced TEChnology 3
PRODUCT

PAD MOUNT SF6 GAS INSULATED LOAD BREAK SWITCH

Load current making and breaking in


SF6 gas with puffer principle.

Independent quick close and quick


open by the spring toggle mechanism.

Two way to four way application.

Three position switch for close-open-ground and close-open-test ground.

Manual and remote control and monitoring.

Make proof design.

ENhanced TEChnology 4
PRODUCT

PAD MOUNT SF6 GAS INSULATED COMPACT SWITCHGEAR

Compact switchgear with combination of switches and circuit breakers.


Load break switch
- Independent quick close and quick
open by the spring toggle mechanism.
Circuit breaker
- Vacuum interrupter with magnetic
actuator mechanism.
Three position switch of
close-open-ground or close-open-test ground switching.
Microprocessor based three phase over current and a earth fault relay.
Microprocessor based control for SCADA system.

ENhanced TEChnology 5
PRODUCT

SOLID INSULATED VACUUM RECLOSER

Environmentally friendly,
oil free and gas free
Compact, light weight,
easy for transportation
Reliable single moving part with
magnetic actuator.
Vacuum interruption with no
hazardous arcing products.
DNP 3.0 communications protocol and SCADA
capability
RTU and control mounted in one control cabinet
with space for modem, etc.
Voltage, current, power metering and underfrequency load shedding
Record of operation, fault and waveform data for power line
and load profile data
Microsoft Windows-based EVRC2A interface software
Microprocessor based protection.
ENhanced TEChnology 6
PRODUCT

SF6 GAS insulated vacuum circuit breaker for outdoor use

Compact and light weight design.


Maintenance free by adoption of reliable
single moving part with magnetic
actuator.
Verification of interruption capability at
the gas pressure 0 kg/ G.
Vacuum interruption with no hazardous
arcing products.
Pressure rupture device for internal arc withstand.
Easy to access the inner part by removal of bolted assembly of the tank
cover with EPR o-ring.

ENhanced TEChnology 7
PRODUCT

HIGH SPEED DC CIRCUIT BREAKER

DC 900/1800V, 4000A, 50kA for Substation System

High interrupting capacity.

High speed tripping to interrupt fault current.

Compact and light weight design for easy


installation.

Reliable single moving part with magnetic actuator.

The longer guarantee, trouble-free operations used by magnet latch.

ENhanced TEChnology 8
PRODUCT

WIRELESS CURRENT METER FOR DISTRIBUTION LINE

Micro-processor based
control included.

Coreless open CT.

Simple operation.

Low battery alarm.

Load current measuring by radio frequency method with hotstick on the


ground level.

Real current mode and maximum current hold mode are available.

ENhanced TEChnology 9
PRODUCT

FAULTED CIRCUIT INDICATOR

Faulted Circuit Indicator for Medium Voltage Underground Line.

Suitable for separable insulated connector.


Intended for fast fault finding.
Reliable operation.
Flashlight indication.
Self adjusting trip level.
Maintenance free.
Manual trip and reset provision.

ENhanced TEChnology 10
ENTEC ELECTRIC & ELECTRONIC
CO., LTD

Automatic Recloser
GENERAL FEATURES

Ratings
Description EVR1 EVR2 EVR3

Maximum system voltage (kV) 15kV 27kV 38kV

Frequency (Hz) 50/60Hz 50/60Hz 50/60Hz

Rated continuous current (A) 400/630A 400/630A 630/800A

Rated symmetrical interrupting (kA) 12.5kA 12.5kA 12.5/16kA

Asymmetrical making current (kApk) 32.5kApk 32.5kApk 32.5/41.6kApk

150kVpk
Impulse withstand voltage (kV.BIL) 110kVpk 170kVpk
(125kVpk)
Power frequency withstand (kV), Dry (1 min) 50kV 60kV 70kV

Power frequency withstand (kV), Wet (10 sec) 45kV 50kV 60kV

Mechanical operations (times) 10,000 10,000 10,000

Weight (kg) 160 170 210

ENhanced TEChnology 12
GENERAL FEATURES

Type Test Certificate

Ratings
Issue Remarks
Voltage Current Interrupting current
KEMA
15kV 630A 12.5kA
Netherlands
KERI
27kV 630A 12.5kA
KOREA
KEMA
27kV 630A 12.5kA
Netherlands
CESI
38kV 630A 12.5kA
ITALY
KEMA
38kV 800A 16kA
Netherlands

ENhanced TEChnology 13
GENERAL FEATURES

Construction

Dimension
A B C D
15kV 750 415 980 780
27kV 812 460 1100 780
38kV / 630A 841 475 1058 870
38kV / 800A 841 475 1078 870

ENhanced TEChnology 14
GENERAL FEATURES

Installation

600
1000 max.

Pol e Mount i ng Br a c k et

Hang er Band

Cont r ol Cabl e
Ear t h Cabl e

Cabl e Cl eat s

Cont r ol Cubi c l e

Pole mounted installation Two pole mounted installation

ENhanced TEChnology 15
STRUCTURE

Outer Tank

Anti-corrosion stainless steel (304L)


Surface treatment by Phosphatic
scouring
Fully Tig welded
Tank filled with SF6 gas
Primer and final Epoxy Paint

ENhanced TEChnology 16
STRUCTURE

Interrupter assembly

Vacuum Interrupter
High strength glass fiber insulation
frame
Arrangement relaxing electric field
Simple driving structure

ENhanced TEChnology 17
STRUCTURE

Magnetic actuator

Low energy consumption Magnetic


Actuator
Single Moving Part using Magnet latch by
the magnetic actuator mechanism
High speed response

ENhanced TEChnology 18
STRUCTURE

The operating principle of Magnetic Actuator

ENhanced TEChnology 19
STRUCTURE

Advantage of magnetic actuator

Single moving part


Magnetic Latch, simple mechanical parts involved
Low power consumption
(Low voltage distribution line power source)
Dead line operation possible over 500 times operations without any
external power source supply
Without battery, it is possible to operate the recloser
with the external power source
Maintenance Free as using single moving part
Light weight and small size
10,000 times mechanical operations

ENhanced TEChnology 20
STRUCTURE

Bushing

Epoxy Bushing
EPDM or silicone rubber Housing
Excellent tracking resistance
Vandal proof
Epoxy bushing with the voltage sensor
of C.V.D
Easy handling for carrying, moving,
installation

ENhanced TEChnology 21
STRUCTURE

Manual trip / Locking device

Manual trip and lockout provision


by a hot stick operation on the
ground level in order to prevent to
be operated by local / remote
control during control circuit faults
or line repair.

ENhanced TEChnology 22
STRUCTURE

ON / OFF indicator and operation counter

The indicator displays an


interrupters open / close status
and the operation counter is
located at the bottom of main tank.

Operation Counter ON/OFF Indicator

ENhanced TEChnology 23
ENTEC ELECTRIC & ELECTRONIC
CO., LTD

Recloser Control EVRC2A


Control cubicle for tropical
application
Main Feature & Description Features and advantages
1. Enclosure of all parts are made of stainless steel
- Complete corrosion free in high-humidity condition.
- No additional periodic painting

2.Triple cover cabinet structure


- No penetration of humidity and dust into relay box.
- Deterrence of rapid temperature fluctuation
- Able to check control cubicle under raining condition
-No damage on inner parts by vandalism

3. Digital relay box with Aluminum enclosure


- Dust and moisture proof
- Environmental protection

4. Powder coating of enclosure


- Constant thickness by powder coating and permanent
durability

ENhanced TEChnology 25
Control cubicle for tropical
application
Main Feature & Description Features and advantages
1. Direct sunlight shield outside cover
1. Sunshine cover
(Direct sunlight block)
- Withstand the heating effect of direct solar
2. Three position door lock radiation without causing failure or mal
operation
- Deterrence of rapid temperature fluctuation by
a shadow from direct sunlight shield cover of
main cubicle
- Protection of main cubicle and inner parts
from external impact
- Capable of inspecting control cubicle under
raining condition

2. Three position door lock


- Maintain complete closing between door and
main cubicle

3. Air circulation vent


- Prevention of moisture condensation in
control cubicle by air circulation through vent

4. Seamless door packing 3. Air circulation vent 4. Seamless door packing


- Complete sealing between door and cubicle

ENhanced TEChnology 26
Control cubicle for tropical
application
Main Feature & Description Features and advantages
1. Adiabetic foam insulation
1. Use of Heat insulation material inside of
main cubicle
- Dew point is controled by constraints of rapid
temperature fluctuation for using adiabatic
foam inside cubicle

2. Stainless steel screen


- Vermin proof by meshed stainless steel
- Degree of protection IP54

3. Modem and Users space

3. Modem and users space

2. Stainless steel screen

ENhanced TEChnology 27
USER INTERFACE
PANEL
VOLTAGE SYSTEM
ELEMENTS DIAGNOSTI
SECTION C SECTION

SEQUENCE
BATTERY
STATUS
TEST
SECTION
SECTION
FAULT
LOCAL
CONTROL INDICATIO
SECTION N
SECTION
MENU
OPERATIO CONTRO
N L
SECTION SECTION

ENhanced TEChnology 28
USER INTERFACE PANEL

VOLTAGE CONDITIONS
27 : Under voltage pickup
59 : Over voltage pickup
25 : Synchronism check
81 : Under frequency pickup

SYSTEM STATUS
CONTROL RUN : System status shows normal
SELF CHECK :System status shows warning

ENhanced TEChnology 29
USER INTERFACE PANEL

SEQUCNCE STATUS
RESET : Sequence shows reset
CYCLE : Sequence shows running
LOCKOUT : Sequence shows lockout

ENhanced TEChnology 30
USER INTERFACE PANEL

BATTERY

AC SUPPLY : Status to supply the external AC power


CHARGE : Status on charging the battery.
DISCHARGE : Status on discharging the battery

BATTERY LOAD TEST : To push the button for battery load test

[BATTERY
[BATTERY TEST
TEST MODE]
MODE]
LOAD(V)
LOAD(V) :: 24.48
24.48
CHARGE(V):
CHARGE(V): 27.39
27.39
STATUS:
STATUS: GOOD
GOOD

ENhanced TEChnology 31
USER INTERFACE PANEL

FAULT INDICATION
A,B,C : Shows phase fault occurred
G : Shows ground fault occurred
SEF : Shows SEF fault occurred
FI RESET : Reset fault indication / Lamp test

TRIP TYPE
INST : Shows instantaneous trip
DELAY : Shows delay trip
HIGHCURRENT : Shows high-current trip

ENhanced TEChnology 32
USER INTERFACE PANEL

LOCAL CONTROL SECTION

All indicators shows status of control function


The indicators will be continuously ON when control function
is enable, otherwise the indicators will be continuously OFF
when control function is disable

PROTECTION ENABLED : ENABLE / DISABLE


GROUND ENABLED : ENABLE / DISABLE
SEF ENABLED : ENABLE / DISABLE
RECLOSE ENABLED : ENABLE / DISABLE
CONTROL LOCKED : Shows locked local key
REMOTE ENABLED : Shows remote operation is possible
ALTERNATE ENABLED : To use with alternate setting
(When Alternative is disabled, Primary setting is applied)
PROGRAM 1 : Use to optional function (Loop scheme, Etc.)
PROGRAM 2 : Use to optional function (Loop scheme, Etc.)
HOT LINE TAG : ENABLE / DISABLE

ENhanced TEChnology 33
USER INTERFACE PANEL

OPERATION SECTION

OPEN
Press OPEN Push-Button, recloser is opened
When the recloser is open, open indicator will be continuously ON

CLOSE
Press CLOSE Push-Button, recloser is closed.
When the recloser is closed, close indicator will be continuously ON
Recloser status indication is based on the recloser 52a contacts

ENhanced TEChnology 34
USER INTERFACE PANEL

MENU CONTROL & DISPLAY SECTION

, , , : Arrow keys are used for moving between the


menu window and changing the setting value

(METER) : Up arrow key is used to move the meter menu,


operable in menu starting mode

(AWAKE) : Down arrow key is used for panel awaking from


sleep mode

(EVENT) : Left arrow key is used to move the event menu,


operable in menu at starting mode

(SET) : Right arrow key is used to move the setting menu,


operable in menu at starting mode

FUN : To move the main menu when present mode is starting mode
ESC : To cancel for data input mode or return current display to the previous level
ENT : To select sub menu or data input

ENhanced TEChnology 35
USER INTERFACE PANEL

SIDE PANEL OF RELAY PORT2

CN1 Current Input IA, IB, IC, IN, SEF CN8


CN2 Voltage Input VA, VB, VC, VL CN7
CN3 AC24V IN Relay Module AC Power Input
CN6
CN4 BATT IN Relay Module DC Power Input
CN10
User-Available DC Voltage CN5
CN5 POWER OUTPUT
Source
CN6 CONTROL Recloser Open, Close CN4
Open, Close Power CN3
CN7 UPS
Monitoring & Control
RECLOSER
CN8 Open, Close, Lock, Pressure
STATUS
OUT1 ~ OUT5 (A Contacts) CN2
CN9 OUTPUTS OUT6 ~ OUT7 (B Contacts)
OUT8 (ALARM)
CN9 CN1
CN10 INPUTS IN01 ~ IN08
PORT2 SERIAL RS232

ENhanced TEChnology 36
GENERAL FEATURES

Application to industrial and utility distribution feeders

Reduced distribution automation costs

RTU and control mounted in one control cabinet

Microprocessor based monitoring and protection

Voltage, current, power and energy metering

DNP 3.0, Modbus communication protocols and SCADA


capability

ENhanced TEChnology 37
GENERAL FEATURES

Record of operation, fault and waveform data for distribution


feeders

Load profile data

Un-interruptable power supply with trip and close operation

Auxiliary power available for modem, etc.

Microsoft Windows-based EVRC2A interface software

Microsoft Windows-based Time Current Curve editor

ENhanced TEChnology 38
PROTECTION

Phase Instantaneous Over-currents


Phase Time Over-currents
Phase Definite Time High Current Lockout
Ground Instantaneous Over-currents
Ground Time Over-currents
Ground Definite Time High Current Lockout
Sensitive Earth Fault
Negative Instantaneous Over-currents
Negative Time Over-currents
Negative Definite Time High Current Lockout

ENhanced TEChnology 39
PROTECTION

Automatic Reclosing (Up To 4 Shots)


Cold Load Pickup with Voltage Control
Sequence Coordination Control
Two Under-voltages
Two Over-voltages
Under-frequency

ENhanced TEChnology 40
MONITORING

Fault Locator
Demand trip and alarm(Ia, Ib, Ic, Ig, I2)
Trip Counter
Synchronism Check
Recloser main contact Wear(Per Phase)
Recloser Operation Failure
Voltage Transformer Failure
Battery Automatic Load Test
Gas Over and Low pressure
Breaker Failure with Current Supervision

ENhanced TEChnology 41
METERING

Phase, Ground, and Sensitive Ground Current


Line and Phase Voltage
Current and Voltage Symmetrical Component
Frequency Magnitude and Rate
Synchronizing Voltage
Synchronizing Frequency
Synchronizing Delta kV, Delta Hz
Single and Three Phase Power(MW, Mvar, MVA, PF)
Energy(MWh, Mvarh)
Maximum Demand(Ia, Ib, Ic, MW, Mvar, MVA)

ENhanced TEChnology 42
EVENT RECORDING

Fault waveform capture: 16 events with 15 cycles

System event: Last 500 events

Diagnostic event: Last 100 events

Load profile: Last 1024 events, 42 days/60min


(5, 10, 15, 20, 30, 60 min interval)

Counter: Trip, fault, system restart

Recloser Interrupter wear: phase A, B, C

ENhanced TEChnology 43
APPLICABLE SCADA

OUTPUTS

7 Programmable Relays

1 Programmable Alarm Relay

INPUTS

8 Opto-isolated Programmable Inputs

ENhanced TEChnology 44
COMMUNICATION PORTS

COM1 RS232 Serial Port


EVRC2A interface software
(Front Panel)

COM2 RS232 Serial Port


DNP 3.0 Protocol - Option
(Rear Terminal)

COM3 RS485 Serial Port


Modbus - Option
(Rear Terminal)

ENhanced TEChnology 45
EVRC2A FUNCTION BLOCK
DIAGRAM PROTECTIONS
SOURCE
Fast time overcurrent protection(51P1, 51G1, 67P1, 67G1)
EVRC2A
OPTION 1
Delay time overcurrent protection(51P2, 51G2)
CVD
Neg' seq' fast time overcurrent protection(46(51)1)
V1, V2,
VT
3VT
3V0 Neg' seq' delay time overcurrent protection(46(51)2)
VT Directional time overcurrent protection(67P1-2, 67G1-2,
OPTION 2
3CV 27 59 50P 51P 46(67)1-2)
D CVD 81 High current trip(50P1, 50G1, 46(50)1)
TRANSDUCER
1,2 1,2 1,2 1,2
High current trip lockout(50P2, 50G2, 46(50)1)
Metering 67P Sensitive Earth Fault protection(51SEF)
V, I, Watt, var, Hz, PF 1,2
CT Directional sensitive Earth Fault protection(67SEF)
3WYE
Undervoltage and overvoltage protection(27/1-2, 59/1-2)
25 79
1-4 Underfrequence and load shedding(81)
I1 Four shot recloser(79)
46/ 46/ 46/ FUNCTIONS
I2 50 51 67
RECLOSER

1,2 1,2 1,2 Source and load side Synchronism check(25)


3I0 Cold load pickup
Sequence coordination
Fault locator
Demand trip and alarm
MONITORING
Recloser operation, trip and close failure
Battery load test failure
27
OPTION 2
Gas over and low pressure
1CV
D CVD Recloser main contact wear
TRANSDUCER
Trip and fault counter
INPUT/OUTPUTS
OPTION 1
50G 51G 67G 51 67 8 Opto-isolated input, 7 Auxiliary relay and alarm
VT 81 1,2 1,2 1,2 SEF SEF
FET trip and close
1VT
METERING
Voltage, current, frequency, power, var, VA, power factor,
energy
ZCT Demand IA , IB, IC, MW, Mvar, MVA
3I0
USER INTERFACES RECORDER COMMUCATIONS
Functional keypad System event recorder Fault Waveform Port1 RS232, Port2 RS232, Port3 RS485
Diagnostic event Peak
LOAD 32 LED indicators ModBus
20 X 4 character display(LCD or recorder demand
Load profile recorder DNP 3.0
VFD)

ENhanced TEChnology 46
HARDWARE BLOCK
DIAGRAM

ENhanced TEChnology 47
UNINTERRUPTIBLE POWER SUPPLY MODULE FOR
TRIP & CLOSE

EVRC2A
Control
Uninterruptible Power
Supply Module for Trip
& Close

External
Power Step Down AC-DC Converter
Transformer Trip/Close
Source
Capacitor
Devices

DC-DC
Converter

Charge
Backup Backup Battery 24DC
Battery

ENhanced TEChnology 48
External Auxiliary Power Supply

Auxiliary power source is derived from either of the following

From an external power source of 230V, 50Hz supplied by


auxiliary power transformer

From low voltage supply connected to the utility distribution


line

External DC 110V supply for substation application

ENhanced TEChnology 49
The reason why Auxiliary power transformer is
not essential to supply control power

Supply DC constant voltage from AC 230V through AC-DC


converter

Closing and Opening Speed is not affected by voltage variation


in an external power supply

Recloser is used for the minimum 30 hours or 500 times of


operation with the back-up battery only when the AC power
supply is out

External power source of AC Source and Back-up Battery are


adopted for Dual Power Supply System

Recloser operation with using external AC power supply can


affect closing speed due to voltage variation. However, ENTEC
recloser maintains constant closing speed due to using DC
converter although AC power supply is used

ENhanced TEChnology 50
TIME CURRENT
CURVES
The operation and reset times conform to IEEE C37.112
and IEC 255-3

The operation and reset times are defined as follows:

ENhanced TEChnology 51
TIME CURRENT CURVE
COEFFICIENTS
Curve r Rt McGraw-Edison time current curve
ANSI
Phase Ground
Moderately Inverse 0.0107 0.020 0.0231 1.0700
OLD NEW OLD NEW
Normally Inverse 5.9500 2.000 0.18 5.9500
A 101 1 102
Very Inverse 3.985 2.000 0.095 3.985
Extremely Inverse 5.9100 2.000 0.0345 5.9100 B 117 2 135
Short Time Inverse 3.56e-3 0.02 1.95e-2 0.356 C 133 3 140
Short Time Very Inverse 1.9925 2.000 0.0475 1.992 D 116 4 106
IEC
E 132 5 114
Standard Inverse 0.1400 0.0200 0.0 9.700
F 163 6 136
Very Inverse 13.500 1.000 0.0 13.500
Extremely Inverse 80.000 2.000 0.0 80.000
H 122 7 152
Long Time Inverse 135.000 1.000 0.0 135.00 J 164 8 113
ESB KP 162 8* 111
Inverse 0.011 0.02 0.042 9.000 L 107 9 131
Very Inverse 3.985 1.95 0.1084 3.985
M 118 11 141
Long Time Very Inverse 15.94 1.95 0.4336 15.94
N 104 13 142
USER Programmable
User1 - - - - P 115 14 119
User2 - - - - R 105 15 112
User3 - - - - T 161 16 139
User4 - - - -
V 137 17 103
Definite Time
W 138 18 151
Definite Time 1Sec 0.0 - 1.0 1.0
Definite Time 10Sec 0.0 - 10.0 10.0
Y 120 KG 165

Short Time Inverse 0.0500 0.0400 0.0 0.500 Z 134

ENhanced TEChnology 52
COMPLETE METERING

Phasor
Currents Voltages Power Energy Frequency Demands Others
Sequence

MW A Ia,Ib,Ic Battery voltage


MWh A Source side Charge voltage
Source side MW B Positive current I1
Ia,Ib,Ic Va,Vb,Vc MW C
MWh B Hz
Positive voltage V1 System voltage
MWh C Hz/Sec
MW3 Phase
Ig
Gas pressure

MVar A egative current I2


Load side
Source side MVar B Pos' MWh 3Phase Negative current I2
Ig,Isg Vab,Vbc,Vca MVar C Neg' MWh 3Phase
Hz
Negative voltage V2
Temperature
Hz/Sec
MVar 3Phase
MW A
MW B
MW C

Power factor A
MVarh A
Currents Load side Power factor B Zero current 3I0
MVarh B MW 3Phase
Phase Angle Vl Power factor C Zero voltage 3V0
Mvarh C
Power factor 3Phase

MVar A
MVar B
MVar C

Voltages Pos' MVarh 3Phase


Phasor Angle
Phase Angle Neg' MVarh 3Phase
MVar 3Phase

ENhanced TEChnology 53
METERING ACCURACY
The harmonic components of current and voltage are removed from the input voltage
and current parameters, so all measurements based on these quantities respond to
the fundamental component only.
ACCURACY
MEASUREMENTS PARAMETERS UNIT RANGE
CVD VT

Phase A RMS Current


Phase B RMS Current
CURRENT A 1% of 2XCT 1% of 2XCT 20 X CT
Phase C RMS Current
Phase G RMS Current

AN (AB) RMS Voltage


VOLTAGE BN (BC) RMS Voltage KV 2.5% 1% -
CN (CA) RMS Voltage
SYMMETRICAL COMPONENTS I1, I2,3I0 V1,V2,3V0 A, KV 1% of 2XCT 1% of 2XCT -
POWER FACTOR Phase A,B,C 3 Phase Rate 0.05 0.02 -1.00 to 1.00
3REAL POWER Phase A,B,C 3 Phase MW 3% 2% 320.00 to 320.00
3REACTIVE POWER Phase A,B,C 3 Phase Mvar 3% 2% 320.00 to 320.00
3APPARENT POWER Phase A,B,C 3 Phase MVA 3% 2% 320.00 to 320.00
WATT-HOURS Phase A,B,C 3 Phase MW/h 5% 3% 32000 to 32000

Phase A/B/C/G Current A


A/B/C, 3 Real Power MW
DEMAND 3% 2%
A/B/C, 3 Reactive Power Mvar
A/B/C, 3 Apparent Power MVA

A-N (A-B) Source and


FREQUENCY Hz 0.05Hz 0.02Hz 40.00 to 65.00
Load Voltage

ENhanced TEChnology 54
MENU STRUCTURE

MAIN MENU RECLOSER


RECLOSER CONTROL
CONTROL
EVERC2A
EVERC2A

ENTEC
ENTEC E&E
E&E CO.
CO. Vx.xx
Vx.xx

MAIN
MAIN MENU
MENU

PRIMARY
PRIMARY SETTING
SETTING ALTERNATE
ALTERNATE SETTING
SETTING STATUS
STATUS METERING
METERING MAINTENANCE
MAINTENANCE EVENT
EVENT RECORDER
RECORDER

1.RELAY
1.RELAY SETUP
SETUP 1.RELAY
1.RELAY SETUP
SETUP 1.OPTO
1.OPTO INPUTS
INPUTS 1.CURRENT
1.CURRENT 1.COUNTERS
1.COUNTERS 1.FAULT
1.FAULT CYCLE
CYCLE
2.SYSTEM
2.SYSTEM SETUP
SETUP 2.SYSTEM
2.SYSTEM SETUP
SETUP 2.RELAY
2.RELAY OUTPUTS
OUTPUTS 2.VOLTAGE
2.VOLTAGE 2.WEAR
2.WEAR MONITOR
MONITOR 2.SYSTEM
2.SYSTEM STATUS
STATUS
3.PROTECTION
3.PROTECTION 3.PROTECTION
3.PROTECTION 3.CLOCK
3.CLOCK 3.FREQUENCY
3.FREQUENCY 3.OUTPUT
3.OUTPUT RELAY
RELAY 3.LOAD
3.LOAD PROFILE
PROFILE
4.MONITORING
4.MONITORING 4.MONITORING
4.MONITORING 4.SYNCHRO
4.SYNCHRO VOLTAGE
VOLTAGE TEST
TEST 4.DIAGNOSTIC
4.DIAGNOSTIC
5.SAVE
5.SAVE SETTING
SETTING 5.SAVE
5.SAVE SETTING
SETTING 5.POWER
5.POWER
6.ENERGY
6.ENERGY
7.DEMAND
7.DEMAND
8.SYSTEM
8.SYSTEM

ENhanced TEChnology 55
MENU STRUCTURE

PRIMARY SETTING MENU


PRIMARY
PRIMARY SETTING
SETTING

RELAY
RELAY SETUP
SETUP SYSTEM
SYSTEM SETUP
SETUP PROTECTION
PROTECTION MONITORING
MONITORING SAVE
SAVE SETTING
SETTING

1.PASSCODE
1.PASSCODE 1.CURRENT
1.CURRENT SENSING 1.OPERATIONS
1.OPERATIONS 1.DEMAND
1.DEMAND SETTING
SETTING VALUE
VALUE SAVE
SAVE
2.COMMUNICATION 2.LINE
2.LINE VT
VT SENSING 2.INTERVALS
2.INTERVALS 2.SYNCHROCHECK
2.SYNCHROCHECK
3.CLOCK 3.LINE
3.LINE VL
VL SETTING 3.PICKUP
3.PICKUP CURRENT
CURRENT 3.TRIP
3.TRIP COUNTER
COUNTER <ENT>:SETTING
<ENT>:SETTING SAVE
SAVE
4.EVENT RECORDER
RECORDER 4.SYSTEM
4.SYSTEM POWER
POWER 4.PHASE
4.PHASE FAST
FAST 4.RECLOSER
4.RECLOSER WEAR
WEAR
5.CLEAR SAVED DATA
DATA 5.PANEL
5.PANEL SLEEP TIME
TIME 5.PHASE
5.PHASE DELAY
DELAY 5.BATTERY
5.BATTERY TEST
TEST
6.FACTORY DEBUG 6.OPTO
6.OPTO INPUT
INPUT SET
SET 6.GROUND
6.GROUND FAST
FAST 6.DIGNOSTIC
6.DIGNOSTIC
7.OUTPUT
7.OUTPUT RELAY
RELAY SET
SET 7.GROUND
7.GROUND DELAY
DELAY
8.SEF
8.SEF ELEMENT
ELEMENT
9.NEGATIVE
9.NEGATIVE FAST
FAST
10.NEGATIVE
10.NEGATIVE DELAY
DELAY 16.H/C
16.H/C LOCKOUT-NEG
LOCKOUT-NEG
11.H/C
11.H/C TRIP-PHA
TRIP-PHA 17.COLD
17.COLD LOAD
LOAD PICKUP
PICKUP
12.H/C
12.H/C TRIP-GND
TRIP-GND 18.DIRECTION
18.DIRECTION
13.H/C
13.H/C TRIP-NEG
TRIP-NEG 19.VOLTAGE
19.VOLTAGE
14.H/C
14.H/C LOCKOUT-PHA
LOCKOUT-PHA 20.FREQUENCY
20.FREQUENCY
15.H/C
15.H/C LOCKOUT-GND
LOCKOUT-GND 21.OTHER
21.OTHER ELEMENT
ELEMENT
22.USER
22.USER CURVE
CURVE SET
SET

ENhanced TEChnology 56
MENU STRUCTURE

STATUS MENU

STATUS
STATUS

OPTO
OPTO INPUTS
INPUTS RELAY
RELAY OUTPUTS
OUTPUTS CLOCK
CLOCK

1.INPUT
1.INPUT 11 :: OPEN
OPEN 1.OUTPUT
1.OUTPUT 11 :: OPEN
OPEN << CURRENT
CURRENT TIME
TIME >>
2.INPUT
2.INPUT 22 :: OPEN
OPEN 2.OUTPUT
2.OUTPUT 22 :: CLOSE
CLOSE
3.INPUT
3.INPUT 33 :: OPEN
OPEN 3.OUTPUT
3.OUTPUT 33 :: OPEN
OPEN 2002/05/03
2002/05/03 12:25:50
12:25:50
4.INPUT
4.INPUT 44 :: OPEN
OPEN 4.OUTPUT
4.OUTPUT 44 :: OPEN
OPEN
5.INPUT
5.INPUT 55 :: OPEN
OPEN 5.OUTPUT
5.OUTPUT 55 :: CLOSE
CLOSE
6.INPUT
6.INPUT 66 :: CLOSE
CLOSE 6.OUTPUT
6.OUTPUT 66 :: OPEN
OPEN
7.INPUT
7.INPUT 77 :: CLOSE
CLOSE 7.OUTPUT
7.OUTPUT 77 :: OPEN
OPEN
8.INPUT
8.INPUT 88 :: OPEN
OPEN 8.OUTPUT
8.OUTPUT 88 :: OPEN
OPEN

ENhanced TEChnology 57
MENU STRUCTURE

MAINTENANCE MENU

MAINTENANCE
MAINTENANCE

COUNTERS
COUNTERS RECLOSER
RECLOSER WEAR
WEAR (%)
(%) OUTPUT
OUTPUT RELAY
RELAY TEST
TEST

TRIP
TRIP :: 00549
00549 CONTACT
CONTACT AA :: 98.70
98.70 SELECT
SELECT RELAY
RELAY :: RLY
RLY xx
FAULT
FAULT :: 00514
00514 CONTACT
CONTACT BB :: 97.60
97.60 Press
Press <FUN>
<FUN> :: Start
Start
RESTART
RESTART :: 00021
00021 CONTACT
CONTACT CC :: 96.58
96.58 Press
Press <ESC>
<ESC> :: Cancel
Cancel

ENhanced TEChnology 58
MENU STRUCTURE

EVENT RECORDER MENU


EVENT
EVENT RECORDER
RECORDER

FAULT
FAULT CYCLE
CYCLE SYSTEM
SYSTEM STATUS
STATUS LOAD
LOAD PROFILE
PROFILE DIAGNOSTIC
DIAGNOSTIC

[NO-01]
[NO-01] AA GG [NO-001]
[NO-001] LOCAL
LOCAL FI/R
FI/R [NO-006]
[NO-006] SLEEP
SLEEP MODE
MODE
IA
IA :: 1520
1520 IB:
IB: 00 STATUS
STATUS :: HI/ASSERT
HI/ASSERT STATUS
STATUS :: FI/ASSERT
FI/ASSERT
IC
IC :: 00 IG:
IG: 1510
1510 DATE
DATE :: 02/05/03
02/05/03 DATE
DATE :: 02/05/02
02/05/02
02/05/03
02/05/03 12:51:02
12:51:02 TIME
TIME :: 15:21:32:452
15:21:32:452 TIME
TIME :: 18;23:49:234
18;23:49:234

CURRENT
CURRENT (A)
(A) [0001]
[0001] REAL
REAL POWER
POWER (MW)
(MW) [0001]
[0001] REACTIVE
REACTIVE POW(MVar)[0001]
POW(MVar)[0001]
AA :: 00 B:
B: 820
820 AA :: 00 BB :: 00 AA :: 0.00
0.00 BB :: 0.00
0.00
CC :: 00 G:
G: 812
812 CC :: 00 3P
3P :: 00 CC :: 0.00
0.00 3P
3P :: 0.00
0.00
02/03/24
02/03/24 13:02:04
13:02:04 02/04/23
02/04/23 14:26:16
14:26:16 02/04/23
02/04/23 15:28:02
15:28:02

ENhanced TEChnology 59
ENTEC ELECTRIC & ELECTRONIC
CO., LTD

Recloser Control EVRC2A Interface Program


PROGRAM FEATURES

Management of Load Profile


Recloser
Date of event
Mfg. Serial. No. Load Current
Date of Manufacture Real Power
Date of Equipment Reac. Power
Area of Equipment Max. 1024 recorded
Specification Search events of specific period
File DB of History Waveform

Setting Main Function


Fault Event
Primary Setting
Management of Recloser Summary
Setting
Alternate Setting
System Status Date of event
Relay Setting
Fault Event Summary Trip Count
System Setting
Fault Waveform Capture Fault Waveform
Protection Setting
Load Profile Max. 16 Recorded
Monitoring Setting
Diagnostic

System Status Diagnostic


Type of event Type of event
Status of event Status of event
Date of event Date of event
Max. 500 recorded Max. 100 recorded
Search events of specific period Search events of specific period

ENhanced TEChnology 61
RECLOSER INTERFACE
PROGRAM
Recloser Registration

Register the nowly installed Recloser


- Mfg. Serial Number
- Date of Manufacture
- Date of Equipment
- Area of Equipment
- Specification
Every installed Recloser can be
managed separately in the individual
stored DB files.

ENhanced TEChnology 62
DOWNLOAD
HISTORY
System Event

Trigger Time : each 1/4 Cycle

Trigger type : Pick up and Dropout

Storage Capacity : Last 500 Events

ENhanced TEChnology 63
DOWNLOAD
HISTORY
System Event
Element Explanation Element Explanation
Phase fast protection element 52A contact 52A contact status
Phase delay protection element Sequence reset status

Ground fast protection element Sequence status Sequence cycle status


Sequence lockout status
Ground delay protection element
Front Panel CLOSE pushbutton
Neutral fast protection element
Front Panel OPEN pushbutton
Neutral delay protection element
Front Panel FI RESET pushbutton
Negative Sequence fast protection element
Front Panel BATTERY LOAD TEST pushbutton
Negative Sequence fast protection element Front Panel PROTECTION ENABLED pushbutton
Phase High Current lockout protection element Front Panel GROUND ENABLED pushbutton
Ground High Current lockout protection element Front Panel SEF ENABLED pushbutton
Front panel control
Neutral High Current lockout protection element Front Panel REECLOSE ENABLED pushbutton
Negative Sequence High Current lockout protection element Front Panel CONROL ROCK pushbutton
Protection Phase High Current Trip protection element Front Panel REMOTE ENABLED pushbutton
Front Panel ALT ENABLED pushbutton
Ground High Current Trip protection element
Front Panel PROG1 ENABLED pushbutton
Neutral High Current Trip protection element
Front Panel PROG2 ENABLED pushbutton
Negative Sequence High Current Trip protection element
Front Panel HOTLINE ENABLED pushbutton
Sensitive Earth Fault protection element
AC supply AC supply status
Phase demand Trip element External OPEN element
External control
Phase demand Trip element External CLOSE element
Frequency Protection element Circuit Breaker (Recloser) LOCK
Under-voltage 1 protection element Fail operation FAIL TRIP
FAIL CLOSE
Under-voltage 2 protection element
External input status External INPUT01-08 Active
Over-voltage 1 protection element System alarm System Alarm Active
Over-voltage 2 protection element TRIP/CLOSE Trip Signal / Close Signal

ENhanced TEChnology 64
DOWNLOAD
HISTORY
Load profile

Trigger Source
Demand Current (A,B,C,G)
Demand Real Power (A,B,C,3)
Demand Reactive Power (A,B,C, 3)
Trigger Time : 5, 10, 15, 20, 30, 60 Min

Storage Capacity
Total 1024 Events
42 days/60 Min.

ENhanced TEChnology 65
DOWNLOAD HISTORY
Fault and Waveform Data

Data Channels
4 currents, 3 voltages, Frequency , 32 logic
input states , 8Ch output relays, 8Ch Input
Sampling Rate : 16 per cycle
Trigger Position : 1 to 15Cycle
Storage capacity : 16 events with 15Cycle
Trigger Source
Protection pickup Elements
Trip Occured

ENhanced TEChnology 66
DOWNLOAD HISTORY
Fault and Waveform
A phase voltage drop
B phase voltage drop
C phase voltage normal

Fault occured
A phase fault occured
B phase fault occured
C phase normal
Fault cleared

ENhanced TEChnology 67
DOWNLOAD
HISTORY
Diagnostic

Trigger Time: each 1/4 Cycle

Trigger type: Pick up and Dropout

Storage Capacity: Last 100 Events

ENhanced TEChnology 68
DOWNLOAD HISTORY
Diagnostic
Trigger Source
Element Explanation Element Explanation

External power FAIL A/D Conversion FAIL

Battery charge circuit FAIL A/D Conversion A/D Converter reference voltage 1 FAIL

Battery Discharge (Value < 21V) A/D Converter reference voltage 2 FAIL

NO Battery (Value < 15V) SETTING Setting Changed

SYSTEM POWER Battery Discharge or No Battery SYSTEM RESTART System restarted

System power FAIL Parallel EEPROM FAIL

System power +12V FAIL Serial EEPROM FAIL

System power +5V FAIL Data RAM FAIL

System power -12V FAIL Setting RAM FAIL


MEMORY
SLEEP MODE Panel sleep mode RTC NVRAM FAIL

POWER DOWN MODE Power down mode RTC Time FAIL

Gas pressure LOW (Value < 0.1 Bar) Initial Value FAIL
GAS STATUS
Gas pressure LOW (Value > 1.5 Bar) Initial Setting Value FAIL

ENhanced TEChnology 69
CHANGE SETTINGS
Change Primary / Alternate setting groups

Relay Setting Protection Setting

System Setting Monitoring Setting

ENhanced TEChnology 70
FEATURE OF TIME CURRENT CURVE
EDITOR

Time Current curves may be selected for


viewing or modification
Standard Curves and user programmable
curves can be modified to provide TCC
equation.
- Non-standard Curve (McGraw-Edison)
- IEC Curves
- ANSI Curves
- User programmable Curves

ENhanced TEChnology 71
TIME CURRENT CURVE
MODIFICATION
The following examples show Time-Current curve modification step by
step that the basic TCC of very inverse curve is easily modified with time
dial, additional delay and various functions

(1) The IEC Very Inverse Curve (IEC-VI) is selected

(2) IEC-VI is modified to IEC-VI(D) with 0.1s time dial

(3) IEC-VI(D) is modified to IEC-VI(DA) with 0.2s additional delay

(4) IEC-VI(DA) is modified to IEC-VI(DAM) with 0.7s M.R.T

(5) IEC-VI(DAM) is modified to IEC-VI(DAMH) with 600% High Current Trip

(6) IEC-VI(DAMH) is modified to IEC-VI(DAMHA) with 0.4s additional delay

(7) IEC-VI(DAMHA) is modified to IEC-VI(DAMHAT) with 900% High Current Lockout

(8) IEC-VI(DAMHAT) is modified to IEC-VI(DAMHATA) with 0.1s additional delay

ENhanced TEChnology 72
TIME CURRENT CURVE MODIFICATION

1. The standard inverse curve(IEC-VI) is


selected for the protection coordination

ENhanced TEChnology 73
TIME CURRENT CURVE
MODIFICATION

2. IEC-VI is modified to IEC-VI(D) with


0.1s time dial

3. IEC-VI is modified to IEC-VI(DA) with


0.1s time dial and 0.2s additional
delay.

ENhanced TEChnology 74
TIME CURRENT CURVE
MODIFICATION
Clearing Time vs Current Ratio
( Min Response Time = 0.7s )
100

10

4. IEC-VI(DA) is modified to IEC-VI(DAM)


TIME ( SEC ONDS)

1 with 0.7s minimum response .


IE C- V I(DAM)

0.1

0.01

CURRENT(PERCENTAGE OF MINIMUM TRIP)

ENhanced TEChnology 75
TIME CURRENT CURVE
MODIFICATION

5. IEC-VI(DAM) is modified to IEC-


VI(DAMH) with 600% High Current Trip

6. IEC-VI(DAMH) is modified to IEC-


VI(DAMHA) with 0.4s additional delay.

ENhanced TEChnology 76
TIME CURRENT CURVE
MODIFICATION
Clearing Time vs Current Ratio
( High Current Lockout at 9X , Added Delay = 0.1s )
100

10
7. IEC-SI(DAMHA) is modified to IEC-
SI(DAMHAT) with 900% High Current
Lockout
TIME( SE C ONDS)

1
8. IEC-SI(DAMHAT) is modified to IEC-
SI(DAMHATA) with 0.1s additional
delay
IE C - VI(DAMHATA)
0.1

IE C- V I(DAMHAT)

0.01

CURRENT(PERCENTAGE OF MINIMUM TRIP)

ENhanced TEChnology 77
RECLOSER TEST
KIT
GENERAL VIEW

ENhanced TEChnology 78
RECLOSER TEST
KIT
FEATURES

Present Current Display


CT Ratio Current Display
Voltage Va,Vb,Vc Display

Reclose Sequence Setting


Phase Select
Present Current Display
Total Sequence Time Display
Trip Time Display Reclosing Interval Display
Trip Current Display Time Second or Cycle Display

ENhanced TEChnology 79
RECLOSER TEST KIT

SPECIFICATION
Power AC230V/2A 50/60HZ
Output Current Maximum 10Arms / 25VA(10A/0.25)

Output Voltage Maximum 20Vpkpk / 200


Continuous / 1A 10second
Recloser Control Interface Cable 6M(23.6")
AMMETER / VOLTMETER 1% (3 digit)
TIME Tolerance cycle
Scope Terminal Max Voltage 10V (3%, 10% at <50 )
System : -25+70(-13+158)
Operating Temperature
LCD : 0+70(+32+158)

Weight Body(11 ) / Aluminum Case(6 )


Cable(2 ) / Total weight(19 )
Aluminum Case size :
Dimensions 500500240(19.68"19.689.45")
Body size : 450300200(17.72"11.827.88")

ENhanced TEChnology 80