TP48200A PMU operation guide


v1.1

www.huawei.com

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential


PMU Location

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 2


PMU System Introduction
1. If the TP48200A works properly and communicates normally with the
communications equipment, the ALM indicator on the PMU is off and the RUN
indicator is blinking slowly. If the TP48200A works properly but fails to
communicate with the communications equipment, the ALM indicator is off and the
RUN indicator is on. If major faults occur in the TP48200A, the ALM indicator is on
and the buzzer beeps. Check and rectify the fault according to the TP48200A-X3H4
& X3H5 Maintenance Guide.
2. Press and Enter to decrease the LCD contrast when the interface works in
standby mode. Press and Enter simultaneously to increase the LCD contrast.
3. On the menu setting screen, press or to browse the menus and set
parameters. Press Enter on the standby screen to access the main menu. Press
Enter on the main menu to access the submenu. After you set the submenu, press
Enter to save the value. Press Cancel to return to the previous menu without saving
the value.
4. The main screen is displayed when the LCD is left unattended for five minutes and
no alarm is generated. The screen goes dark when the LCD is left unattended for
eight minutes.
5. A customer password is required for accessing the Settings menu, and a Huawei
engineer password is required for accessing the Eng. Setting menu. The default
customer password and Huawei engineer password are 0# and 11# respectively.
Both passwords can be changed.
HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 3
PMU parameters Introduction
Second-
Third-Level
Main Menu Level Forth Menu Value Range Default Value Setting Design
Menu
Menu

Date 0000-00-00~9999-12-31 2001-1-1 Same with the setting date

Time 00:00~23:59 00:00 Same with the setting time

IP Address 0.0.0.0~255.255.255.255 192.168.0.1 n/a


System
Settings
Subnet Mask 0.0.0.0~255.255.255.255 255.255.254.0 n/a

Gateway 0.0.0.0~255.255.255.255 10.70.199.1 n/a

Eng. Settings Rect Sleep Yes or No No n/a

Batt String 0~2 1 2


Batt Selection Cap 1 30~1000 400Ah 100Ah
Settings Cap 2 30~1000 0Ah 100Ah
LLVD enable Yes or No Yes n/a

BLVD enable Yes or No Yes n/a

LVD Settings (BLVD) voltage to DC


Batt Settings LLVD 44.0 V n/a
undervoltage alarm threshold

BLVD 35 V to (LLVD) voltage 43.0 V n/a

Float 43.2 V~57.6 V 53.5 V n/a


Charge Boost 43.2 V~57.6 V 56.5 V n/a
Current Limit 0.05C10~0.25C10 0.10C10 n/a
Temp Coeff High Temp Alarm -50C~100C 50C n/a

AMB. Settings High Alarm -50C~100C 50C n/a

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 4


1. Set the system type

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 5


2. Set the number, capacity of battery
strings

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 6


3. Set temperature alarm parameters

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 7


4. Set the date and time

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 8


5. Querying alarms on PMU

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 9


CAUTION

To avoid damaging storage batteries, connect


mains to the TP48200A only after correctly setting
the storage battery parameters on the PMU.

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 10