Академический Документы
Профессиональный Документы
Культура Документы
Bus Bar
Protection
GE Multilin
Outline
Bus arrangements
Bus components
Bus protection techniques
CT Saturation
Application Considerations:
High impedance bus differential
relaying
Low impedance bus differential
relaying
Special topics
2
GE Consumer & Industrial
Multilin
Mar 6, 2017
Single bus - single breaker
ZONE 1
1 2 3 ---- n-1 n
ZONE 2
ZONE 1
TRANFER BUS
ZONE 2
ZONE 2
ZONE 2
TB1
B1 B2
TB1
L3 L4
BUS 2
ISO 1 ISO 2
CB 1
ISO 3
BYPASS
11
GE Consumer & Industrial
SF6, EHV & HV - Multilin
Mar 6, 2017
Synchropuff
Disconnect switches & auxiliary
contacts BUS 1
BUS 1
BUS 2
+
ISOLATOR 1
7B 7A
BUS 1
ISOLATOR 1
+
CB 1
7B 7A
ISO 3
BYPASS
ISOLATOR 1 CLOSED
F1a Contact Input F1a On
F1c Contact Input F1c On
F1b
- 12
GE Consumer & Industrial
Multilin
Mar 6, 2017
Current Transformers
BUS 1
BUS 2
ISO 1 ISO 2
Bushing type 13
(medium voltage GE Consumer & Industrial
Multilin
switchgear) Mar 6, 2017
Protection Requirements
High bus fault currents due to large number of
circuits connected:
CT saturation often becomes a problem as CTs may not be
sufficiently rated for worst fault condition case
large dynamic forces associated with bus faults require fast
clearing times in order to reduce equipment damage
False trip by bus protection may create serious
problems:
service interruption to a large number of circuits
(distribution and sub-transmission voltage levels)
system-wide stability problems (transmission voltage levels)
With both dependability and security important,
preference is always given to security
14
GE Consumer & Industrial
Multilin
Mar 6, 2017
Bus Protection Techniques
Interlocking schemes
Overcurrent (unrestrained or
unbiased) differential
Overcurrent percent (restrained or
biased) differential
Linear couplers
High-impedance bus differential schemes
Low-impedance bus differential schemes
15
GE Consumer & Industrial
Multilin
Mar 6, 2017
Interlocking Schemes
Blocking scheme
typically used
Short coordination time
required
50
Care must be taken with
possible saturation of
BLOCK
feeder CTs
50 50 50 50 50
Blocking signal could be
sent over
communications ports
(peer-to-peer)
This technique is limited
to simple one-incomer
distribution buses
16
GE Consumer & Industrial
Multilin
Mar 6, 2017
Overcurrent (unrestrained)
Differential Differential signal formed
by summation of all
currents feeding the bus
CT ratio matching may be
required
51 On external faults,
saturated CTs yield
spurious differential
current
Time delay used to cope
with CT saturation
Instantaneous differential
OC function useful on
integrated microprocessor-
based relays
17
GE Consumer & Industrial
Multilin
Mar 6, 2017
Linear Couplers
59
0V
40 V 10 V 10 V 0V 20 V
External
Fault
If =
18
8000 A GE Consumer & Industrial
Multilin
2000 2000 A 0 4000 Mar 6, 2017
Linear
Couplers
E = I *X - secondary voltage on relay terminals
sec prim m
where,
Iprim primary current in each circuit
Xm liner coupler mutual reactance (5V per 1000Amps => 0.005 @
60Hz )
ZR relay tap impedance
ZC sum of all linear coupler
If = self impedances
Internal Bus
8000 A Fault
40 V 59
0V 10 V 10 V 0V 20 V
19
GE Consumer & Industrial
Multilin
Mar 6, 2017
0 2000 2000 0 4000
Linear
Couplers
Fast, secure and proven
Require dedicated air gap CTs, which may not
be used for any other protection
Cannot be easily applied to reconfigurable
buses
The scheme uses a simple voltage detector
it does not provide benefits of a
microprocessor-based relay (e.g.
oscillography, breaker failure protection,
other functions)
20
GE Consumer & Industrial
Multilin
Mar 6, 2017
High Impedance Differential
Operating signal created by
connecting all CT secondaries in
parallel
o CTs must all have the same ratio
o Must have dedicated CTs
Overvoltage element operates
on voltage developed across
resistor connected in secondary
59
circuit
o Requires varistors or AC
shorting relays to limit energy
during faults
Accuracy dependent on
secondary circuit resistance
o Usually requires larger CT
cables to reduce errors higher
cost
Percent characteristic
used to cope with CT
saturation and other
errors
87
51
Restraining signal can
be formed in a number
of ways
No dedicated CTs
needed
Used for protection of
re-configurable buses
I DIF I1 I 2 ... I n possible
23
GE Consumer & Industrial
Multilin
Mar 6, 2017
Digital Differential Algorithm
Goals
Improve the main differential algorithm operation
o Better filtering
o Faster response
o Better restraint techniques
o Switching transient blocking
Provide dynamic bus replica for reconfigurable bus bars
Dependably detect CT saturation in a fast and reliable
manner, especially for external faults
Implement additional security to the main differential
algorithm to prevent incorrect operation
o External faults with CT saturation
o CT secondary circuit trouble (e.g. short circuits)
24
GE Consumer & Industrial
Multilin
Mar 6, 2017
Low Impedance Differential
(Distributed) Data Acquisition Units
(DAUs) installed in bays
Central Processing Unit
52 52 52
(CPU) processes all data
DAU DAU DAU from DAUs
Communications between
DAUs and CPU over fiber
using proprietary protocol
Sampling synchronisation
between DAUs is required
CU Perceived less reliable
copper (more hardware needed)
fiber Difficult to apply in retrofit
applications
25
GE Consumer & Industrial
Multilin
Mar 6, 2017
Low Impedance Differential
(Centralized)
All currents applied to a
52 52 52 single central processor
No communications,
external sampling
synchronisation necessary
Perceived more reliable
(less hardware needed)
Well suited to both new
CU
and retrofit applications.
copper
26
GE Consumer & Industrial
Multilin
Mar 6, 2017
CT Saturation
27
GE Consumer & Industrial
Multilin
Mar 6, 2017
CT Saturation Concepts
CT saturation depends on a number of factors
o Physical CT characteristics (size, rating, winding
resistance, saturation voltage)
o Connected CT secondary burden (wires + relays)
o Primary current magnitude, DC offset (system X/R)
o Residual flux in CT core
Actual CT secondary currents may not behave in the same
manner as the ratio (scaled primary) current during faults
End result is spurious differential current appearing in the
summation of the secondary currents which may cause
differential elements to operate if additional security is
not applied
28
GE Consumer & Industrial
Multilin
Mar 6, 2017
CT Saturation
No DC Offset
Waveform remains
fairly symmetrical
With DC Offset
Waveform starts off
being asymmetrical,
then symmetrical in
Ratio Current CT Current
steady state
29
GE Consumer & Industrial
Multilin
Mar 6, 2017
External Fault & Ideal CTs
differential
t1
t0 restraining
Fault starts at t0
Steady-state fault conditions occur at t 1
Ideal CTs have no saturation or mismatch
errors thus produce no differential current 30
GE Consumer & Industrial
Multilin
Mar 6, 2017
External Fault & Actual CTs
differential
t1
t0 restraining
Fault starts at t0
Steady-state fault conditions occur at t 1
Actual CTs do introduce errors, producing some
differential current (without CT saturation) 31
GE Consumer & Industrial
Multilin
Mar 6, 2017
External Fault with CT
Saturation
t2
differential
t1
t0 restraining
Fault starts at t0, CT begins to saturate at t1
CT fully saturated at t2
CT saturation causes increasing differential
current that may enter the differential 32
33
GE Consumer & Industrial
Multilin
Mar 6, 2017
High-
Impedance
Bus
Differential 34
GE Consumer & Industrial
Multilin
Mar 6, 2017
High Impedance Voltage-
operated
Relay
59 element
External set above max possible voltage
Fault
developed across relay during external fault causing
worst case CT saturation
For internal faults, extremely high voltages (well
above 59 element pickup) will develop across relay
35
GE Consumer & Industrial
Multilin
Mar 6, 2017
High Impedance Voltage
Operated
36
GE Consumer & Industrial
Multilin
Mar 6, 2017
High Impedance Voltage
Operated
37
GE Consumer & Industrial
Multilin
Mar 6, 2017
Electromechanical High
Impedance Bus Differential
Relays
Single phase relays
High-speed
High impedance voltage sensing
High seismic IOC unit
38
GE Consumer & Industrial
Multilin
Mar 6, 2017
P -based High-Impedance Bus
Differential Protection Relays
39
GE Consumer & Industrial
Multilin
Mar 6, 2017
High Impedance Module for
Digital Relays
41
GE Consumer & Industrial
Multilin
Mar 6, 2017
High Impedance Bus Protection -
Summary
Fast, secure and proven
Requires dedicated CTs, preferably with the same
CT ratio and using full tap
Can be applied to small buses
Depending on bus internal and external fault
currents, high impedance bus diff may not provide
adequate settings for both sensitivity and security
Cannot be easily applied to reconfigurable buses
Require voltage limiting varistor capable of
absorbing significant energy
May require auxiliary CTs
Do not provide full benefits of microprocessor-
based relay system (e.g. metering, monitoring,
oscillography, etc.)
42
GE Consumer & Industrial
Multilin
Mar 6, 2017
Low-
Impedance
Bus
Differential 43
GE Consumer & Industrial
Multilin
Mar 6, 2017
P-based Low-Impedance Relays
No need for dedicated CTs
Internal CT ratio mismatch compensation
Advanced algorithms supplement percent differential
protection function making the relay very secure
Dynamic bus replica (bus image) principle is used in
protection of reconfigurable bus bars, eliminating the
need for switching physically secondary current
circuits
Integrated Breaker Failure (BF) function can provide
optimal tripping strategy depending on the actual
configuration of a bus bar
44
GE Consumer & Industrial
Multilin
Mar 6, 2017
Small Bus Applications
2-8 Circuit
Applications
Up to 24 Current Inputs Different CT Ratio
4 Zones Capability for Each
Zone 1 = Phase A Circuit
Zone 2 = Phase B Largest CT Primary is
Zone 3 = Phase C Base in Relay
Zone 4 = Not used
45
GE Consumer & Industrial
Multilin
Mar 6, 2017
Medium to Large Bus
Applications
9-12 Circuit
Applications
Relay 1 - 24 Current Inputs Relay 2 - 24 Current Inputs
4 Zones 4 Zones
Zone 1 = Phase A (12 currents) Zone 1 = Not used
Zone 2 = Phase B (12 currents) Zone 2 = Not used
Zone 3 = Not used Zone 3 = Phase C (12 currents)
Zone 4 = Not used Zone 4 = Not used
Different CT Ratio Capability for Each Circuit
Largest CT Primary is Base in Relay
CB CB
11 12
46
GE Consumer & Industrial
Multilin
Mar 6, 2017
Large Bus Applications
87B phase A
87B phase B
87B phase C
Logic relay
(switch status,
optional BF)
47
GE Consumer & Industrial
Multilin
Mar 6, 2017
Large Bus Applications
For buses with up to 24 circuits
48
GE Consumer & Industrial
Multilin
Mar 6, 2017
Summing External Currents
Not Recommended for Low-Z 87B relays
CT-1
Relay becomes
combination of
CT-2
restrained and
unrestrained elements
CT-3 In order to parallel CTs:
I 1 = Error
CT performance must be
closely matched
CT-4
o Any errors will appear as
I 2 =0
differential currents
Associated feeders must be
I 3 =0
iR i1 i2 i3 ... in
1
scaled sum of
n
50
GE Consumer & Industrial
Multilin
Mar 6, 2017
Sum Of vs. Max Of Restraint
Methods
Sum Of Approach Max Of Approach
More restraint on external Less restraint on external faults;
faults; less sensitive for internal more sensitive for internal faults
faults Breakpoint settings for the
Scaled-Sum Of approach percent differential
takes into account number of characteristic easier to set
connected circuits and may Better handles situation where
increase sensitivity one CT may saturate completely
Breakpoint settings for the (99% slope settings possible)
percent differential
characteristic more difficult to
set
51
GE Consumer & Industrial
Multilin
Mar 6, 2017
Bus Differential Adaptive
Approach
Region 2
(high differential
currents)
differential
Region 1
(low differential
currents)
restraining
52
GE Consumer & Industrial
Multilin
Mar 6, 2017
Bus Differential Adaptive Logic
Diagram
DIFL
AND
DIR
OR
87B BIASED OP
OR
SAT
AND
DIFH
53
GE Consumer & Industrial
Multilin
Mar 6, 2017
Phase Comparison Principle
Internal Faults: All fault (large) currents are
approximately in phase.
Secondary Current of
Faulted Circuit
No Voltages are required or (Severe CT Saturation)
needed
54
GE Consumer & Industrial
Multilin
Mar 6, 2017
Phase Comparison Principle
Continued
External Fault Conditions Internal Fault Conditions
Ip Ip
imag imag
ID I p OPERATE ID I p OPERATE
BLOCK BLOCK
Ip Ip
I D -I p real I D -I real
Ip ID I p p
ID I p
Ip
BLOCK
BLOCK
OPERATE OPERATE
55
GE Consumer & Industrial
Multilin
Mar 6, 2017
CT Saturation
t2
differential
t1
t0 restraining
Fault starts at t0, CT begins to saturate at t1
CT fully saturated at t2
56
GE Consumer & Industrial
Multilin
Mar 6, 2017
CT Saturation Detector State
Machine NORMAL
SAT := 0
The differential
current below the saturation
first slope for condition
certain period of
time EXTERNAL
FAULT
SAT := 1
The differential-
The differential restraining trajectory
characteristic out of the differential
entered characteristic for
certain period of time
EXTERNAL
FAULT & CT
SATURATION
SAT := 1
57
GE Consumer & Industrial
Multilin
Mar 6, 2017
CT Saturation Detector
Operating Principles
The 87B SAT flag WILL NOT be set during
internal faults, regardless of whether or not
any of the CTs saturate.
The 87B SAT flag WILL be set during
external faults, regardless of whether or not
any of the CTs saturate.
By design, the 87B SAT flag WILL force the
relay to use the additional 87B DIR phase
The Saturation
comparison Detector
for Region WILL
2 NOT Block the
Operation of the Differential Element it will
only Force 2-out-of-2 Operation
58
GE Consumer & Industrial
Multilin
Mar 6, 2017
CT Saturation Detector -
Examples
The oscillography records on the next two slides were
captured from a B30 relay under test on a real-time digital
power system simulator
First slide shows an external fault with deep CT saturation
(~1.5 msec of good CT performance)
o SAT saturation detector flag asserts prior to BIASED PKP
bus differential pickup
o DIR directional flag does not assert (one current flows
out of zone), so even though bus differential picks up, no
trip results
Second slide shows an internal fault with mild CT saturation
o BIASED PKP and BIASED OP both assert before DIR
asserts
o CT saturation does not block bus differential
More examples available (COMTRADE files) upon request
59
GE Consumer & Industrial
Multilin
Mar 6, 2017
CT Saturation Example
External Fault 200
150
100 ~1 ms
50
current, A
0
-50
-100
-150
-200
0.06 0.07 0.08 0.09 0.1 0.11 0.12
time, sec
Despite heavy CT
saturation the
external fault current
The element is seen in the
The
does not opposite direction
directional flag
maloperate 60
is not set
GE Consumer & Industrial
Multilin
Mar 6, 2017
CT Saturation Internal Fault
Example
The
The element directional
operates in flag is set
10ms 61
GE Consumer & Industrial
Multilin
Mar 6, 2017
Applying Low-Impedance
Differential Relays for Busbar
Protection
Basic Topics
Configure physical CT Inputs
Configure Bus Zone and Dynamic Bus
Replica
Calculating Bus Differential Element settings
Advanced Topics
Isolator switch monitoring for
reconfigurable buses
Differential Zone CT Trouble
Integrated Breaker Failure protection
62
GE Consumer & Industrial
Multilin
Mar 6, 2017
Configuring CT Inputs
For each connected CT circuit enter Primary
rating and select Secondary rating.
Each 3-phase bank of CT inputs must be
assigned to a Signal Source that is used to
define the Bus Zone and Dynamic Bus Replica
66
GE Consumer & Industrial
Multilin
Mar 6, 2017
Dual Percent Differential
Characteristic
High Set
(Unrestrained)
High Slope
Low Slope
High
Breakpoint
68
GE Consumer & Industrial
Multilin
Mar 6, 2017
Calculating Bus Differential
Settings Minimum Pickup
69
GE Consumer & Industrial
Multilin
Mar 6, 2017
Calculating Bus Differential
Settings Low Slope
70
GE Consumer & Industrial
Multilin
Mar 6, 2017
Calculating Bus Differential
Settings Low Breakpoint
Defines the upper limit to restraint currents that will
be biased according to the Low Slope setting
Should be set to be above the maximum load but
not more than the maximum current where the CTs
still operate linearly (including residual flux)
Assumption is that the CTs will be operating linearly
(no significant saturation effects up to 80% residual
flux) up to the Low Breakpoint setting
71
GE Consumer & Industrial
Multilin
Mar 6, 2017
Calculating Bus Differential
Settings High Breakpoint
72
GE Consumer & Industrial
Multilin
Mar 6, 2017
Calculating Bus Differential
Settings High Slope
Defines the percent bias for the restraint currents
IRESTHigh Breakpoint
Setting determines the stability of the differential
element for high current external faults
Traditionally, should be set high enough to
accommodate the spurious differential current
resulting from saturation of the CTs during heavy
external faults
Setting can be relaxed in favour of sensitivity and
speed as the relay detects CT saturation and applies
the directional principle to prevent maloperation
Range: 50% to 100% in 1%. increments
73
GE Consumer & Industrial
Multilin
Mar 6, 2017
Calculating Unrestrained Bus
Differential Settings
74
GE Consumer & Industrial
Multilin
Mar 6, 2017
Dual Percent Differential
Characteristic
High Set
(Unrestrained)
High Slope
Low Slope
High
Breakpoint
CT-1 CT-7
CT-2 B-2 CT-3 B-3 CT-4 B-4 CT-5
B-7
CT-6
CT-8
B-6
S-2 S-4 S-6
SOUTH BUS
B-7
CT-6
CT-8
B-6
S-2 S-4 S-6
SOUTH BUS
B-7
CT-6
CT-8
B-6
S-2 S-4 S-6
SOUTH BUS
CT-1 CT-7
CT-2 B-2 CT-3 B-3 CT-4 B-4 CT-5
B-7
CT-6
CT-8
B-6
S-2 S-4 S-6
SOUTH BUS
80
GE Consumer & Industrial
Multilin
Mar 6, 2017
Isolator Typical Open/Closed
Connections
81
GE Consumer & Industrial
Multilin
Mar 6, 2017
Switch Status Logic and
Dyanamic Bus Replica
Isolator Isolator Isolator Alarm Block
Open Closed Position Switching
Auxiliary Auxiliary
Contact Contact
Off On CLOSED No No
82
GE Consumer & Industrial
Multilin
Mar 6, 2017
Differential Zone CT Trouble
Each Bus Differential Zone may a dedicated CT
Trouble Monitor
Definite time delay overcurrent element operating
on the zone differential current, based on the
configured Dynamic Bus Replica
Three strategies to deal with CT problems:
1. Trip the bus zone as the problem with a CT will
likely evolve into a bus fault anyway
2. Do not trip the bus, raise an alarm and try to
correct the problem manually
3. Switch to setting group with 87B minimum
pickup setting above the maximum load
current.
83
GE Consumer & Industrial
Multilin
Mar 6, 2017
Differential Zone CT Trouble
Strategies 2 and 3 can be
accomplished by:
Using undervoltage supervision to ride through
the period from the beginning of the problem
with a CT until declaring a CT trouble condition
Using an external check zone to supervise the
87B function
Using CT Trouble to prevent the Bus Differential
tripping (2)
Using setting groups to increase the pickup
value for the 87B function (3)
84
GE Consumer & Industrial
Multilin
Mar 6, 2017
Differential Zone CT Trouble
Strategy #2 Example
87B operates
Undervoltage condition
CT OK
pv.
Phase B AC signals Phase C AC signals Su
wired here, current wired here, current e nt
BF status monitored here status monitored here urr
In C
iti &
a e
te at
& n iti
Cu I
rre BF
n tS
up Breaker Failure
v. elements
configured here
88
GE Consumer & Industrial
Multilin
Mar 6, 2017
Example Architecture Breaker
Trip
Failure Tripping
Bre
Op ak
er
Fail Fai
r l
a ke Op
Bre Phase A AC signals
wired here, current Trip
Trip status monitored here
90
GE Consumer & Industrial
Multilin
Mar 6, 2017
91
GE Consumer & Industrial
Multilin
Mar 6, 2017