Detection
Theory
el
He
Fu
ta
Oxygen
Characteristics of a Fire
Arc Welding
Sunlight
Infrared Energy
Modulation
Reflective
Characteristics of a Fire
Relative
Energy
Suns radiation
reaching the Earth
microns
400nm
800nm
300nm
2 to 3
Wavelength
UV Phototube
Relative
Energy
Suns radiation
reaching the Earth
microns
400nm
800nm
300nm
260nm
135nm
2 to 3
UV Phototube
Ultraviolet
Radiation
Photocathode Anode
Electrons
Gas-Filled
Phototube
-
VDC
+
IR Devices
Relative
Energy
Suns radiation
reaching the Earth
microns
400nm
800nm
300nm
microns
2 to 3
4.35
Wavelength
IR Devices
Hydrogen fires
emit H2O vapors
@ 2.95 microns
Relative
Energy
Suns radiation
400nm reaching the Earth
800nm
2.7 to 3 .2
300nm
microns
microns
4.35
Wavelength
FlameGard 5 UV/IR
FlameGard 5 UV/IR
Assembly
Three Distinct Explosion-proof Housings:
UV/IR
COPM Light Rods (Reflective Coated)
UV - Straight
IR - Curved
O-Ring Sealed Windows
Common Base with Bracket Mounting Holes
Two (2) Bottom Entry Conduit Connections (3/4 NPT)
Drip Lip (3/4 of housing mating surface)
FlameGard 5 UV/IR Specifications
Environmental
Temperature
FlameGard 5 UV/IR -40C to 85C (-40F to 185F)
Ratings
IP 66, Type 4X, Class I, Div 1, Groups B, C & D;
Class II, Groups E, F & G; Class III
FlameGard 5 UV/IR Specifications
Performance
Improved detection and false alarm immunity
Field-of-View
FlameGard 5 UV/IR - 115 Vertical, 120 Horizontal
Optical Sensitivity
1 sq. ft. fire at 50 ft.
FlameGard 5 UV/IR Field of View
(Horizontal)
15 0 15
50'
30 45' 30
40'
45 45
75% 35'
30'
60 25' 60
100% 20'
15'
10'
50%
+60
+45 SENSITIVITY
TABLE CHART
100%
VERTICAL 100% 75% 50%
+30 75%
(5) TABLE CHART
HORIZONTAL HORIZONTAL 100% 75% 50%
(Vertical)
50% 45 50' 30' <5'
+60
+45
SENSITIVITY
TABLE CHART
100%
100% VERTICAL 100% 75% 50%
+30 75%
0 50' 50' 25'
50%
15 50' 50' 25'
75% +15
30 50' 50' 25'
-15
-30
-45
-60
FlameGard 5 UV/IR Specifications
Performance
Spectral Sensitivity
FlameGard 5 UV/IR: 185 to 260 nanometers & 4.35 microns
Outputs
4-20 mA Signal
0 mA, Fault
2 mA, COPM Fault
4 mA, Ready
8 mA, IR Only
12 mA, UV Only
16 mA, Warn
20 mA, Alarm (After time delay)
FlameGard 5 UV/IR Specifications
Outputs
Commands
Read Only
4-20 mA
Alarm, Warning, Fault
UV Only Signal, IR Only Signal
UV Source Lamp Fault, IR Source Lamp Fault
Low Voltage
Communication Faults
Write Only
Auto Test, Reset, Accept
Read and Write
Address, Modbus Setup
Sensitivity (100%, 75%, 50%)
Time Delay, Relay States
FlameGard 5 UV/IR Specifications
Outputs
Relays: (3) SPDT (8-amp, 24 VDC/250 VAC
Resistive)
Warning (Immediate, no time delay)
Alarm (After 2, 4, 8 or 10 Sec. Time Delay)
Dip Switch Selectable
RS-485 Selectable (Non-intrusive over-ride)
Fault (Energized, non-latching )
FlameGard 5 UV/IR Specifications
System
Modes:
Normal
Self Test (Power-up)
Alarm Test (Remote)
Fault Diagnostic -Status Indication (LED)
Approvals
CSA, FM, ATEX, CE Marking
Power
20-36 VDC Nominal @ 150 mA Max.
Input Terminals
Test and Reset
Wiring: 12 AWG to 22 AWG
FlameGard 5 Test Lamp
Rechargeable/replaceable
batteries
Easy grip handle integral
with housing
Spring return on/off
switch to conserve
battery life
Explosion-proof cast
aluminum housing
CSA Approved
ATEX Approved
Key Features / Benefits
Output Capability
Three programmable relays (8 AMP)
0-20 mA stepped output to allow quick
diagnostics for UV only, IR only, COPM
Fault and overall Failures
Modbus for digital communication
HART------Digital Communication protocol.
Communicates via analog output line.