Вы находитесь на странице: 1из 27

MiCOM P111

Universal Overcurrent
with Earthfault Protection

RELIABILITY LOW PRICE

P111

SELECTIVITY P111
EASY TO
ASSEMBLE

STABILITY USER
FRIENDLY

2 > Title of presentation - Date - References 2


P111

Relay versions in the range:

P111 model A - Three phase Overcurrent Protection

P111 model B - Three phase Overcurrent and Earth Fault


Protection with Modbus communication

P111 model C - Three phase Overcurrent and Earth Fault


Protection with Modbus communication
and enhanced event record facility and I/O module

3 > Title of presentation - Date - References 3


P111

Application of P111

4 > Title of presentation - Date - References 4


P111

Scope of applications
Replacement of old electromechanical relays

LV switchgear

Low cost backup protection

Profits and more competitive

5 > Title of presentation - Date - References 5


P111

Scope of applications
Refurbishment

Ease of fit in mechanical adapters

6 > Title of presentation - Date - References 6


P111

Scope of applications
Refurbishment:
India service P111 retrofit:
CDG 11,CAG 14, CDG 31
CAG 34, CDAG

Ease of fit in mechanical adapters

7 > Title of presentation - Date - References 7


P111

DIN rail or
flush mounting
Local and remote
setting change
Configurable
inputs and outputs

P111

Dual rated P111 Wide range


CT inputs power supply

Configurable
2 independent
all main functions
setting groups

Small box a lot of function

8 > Title of presentation - Date - References 8


P111

P111

Protection and Control features

9 > Title of presentation - Date - References 9


P111
ANSI P111 P111 P111
FUNCTIONS codes Model A Model B Model
C
Three phase Overcurrent 50/51 X X X

Earth Fault Overcurrent 50N/51N X X

Temperature (PTC) 38 X X X

Output relay latching 86 X X X

Setting groups 2 2 2

Circuit Breaker / Contactor


Control Selectable Mode X X X

Measurement (true RMS value


up to 20th harmonic) X X X

Fault Record X X X

MiCOM S1 software setting X X


Communication via RS485 X X

Protection / automation / ancillary features


10 > Title of presentation - Date - References 10
P111

Line Diagram

52 Trip
P111
S1-S2
T1-T2 Logic
86 inputs
V1-
Phase
CTs 3 C
V2-
50 51 C
P1
Earth P2 Logic
CT
50N 51N P3 outputs
P4

38
RS 485
Remote
Communication
control

11 > Title of presentation - Date - References 11


P111

Physical Features

Front Panel Components


Indicators of phase
current displayed 4 digit LED display

LED indicators: P111


Indicator of displayed
I>> Alarm / Trip current value in kA

I> Alarm / Trip


Ip> Alarm / Trip
Indicator of displayed
Io> Alarm / Trip
time value in seconds
PTC Trip
External Protection Trip

5 button tactile keypad

User friendly HMI


12 > Title of presentation - Date - References 12
P111

Housing
DIN Rail Mounted :
106,5 x 118,0 x 106,5 mm (HxDxW)
Flush Mounted :
75 x 116 x 100 mm (HxDxW)

P111

P111

Flexible mounting method


13 > Title of presentation - Date - References 13
P111
Housing
DIN rail mounted housing
In networks up to 1kV, primary circuit wires can be threaded through openings in the housing
Also, external current transformers can be applied

Flush mounted housing :


standard screw terminals for current connection are implemented here and external current transformers are recommended for use

Ease of installation
14 > Title of presentation - Date - References 14
P111

Auxiliary Supply :

Two ranges of auxiliary supply decided when ordering:


24 Vac/dc to 48 Vac/dc
60 Vac/dc to 230 Vac/dc

Auxiliary supply tolerance:


0.8 to 1.2 Uaux

Hold time at auxiliary supply interruption:


min 2,2s (230Vac)
min 1,3s (230Vdc)
min 0,6s (110Vac)
min 0,3s (110Vdc)

Indulgent requirements regarding aux. supply quality


15 > Title of presentation - Date - References 15
P111

Digital Inputs and Outputs

Programmable Programmable Programmable Programmable


logic inputs logic inputs logic outputs logic outputs
(activated by short) (activated by (Normally Open) (Change Over)
applying voltage)

P111 -
2 - 2
Model A

P111
2 - 2 -
Model B

P111 2 3 1
2
Model C

Ease of fit in any standard application

16 > Title of presentation - Date - References 16


P111

Environment :

Temperature:
Operation: - 20C + 60C
Storage: - 25C + 70C

Humidity:
56 days at 93% and 40C

Enclosure protection:
IP 20 terminals
IP 40 case
IP 54 for front panel of flush mounted housing

Resistance to industrial environment conditions


17 > Title of presentation - Date - References 17
P111

Communication :
RS485 rear communication port:
Protocols available
- Modbus RTU standard

Operations via RS485:


- Contactor/CB control
- Resetting
- Measurement and I/O status readout
- States of protection
- Remote setting via MiCOM S1 (B and C only)

Ease of integration
18 > Title of presentation - Date - References 18
P111

Protection and Control features

3 Phase Overcurrent Protection (50/51)


Three thresholds for one, two or three phase connection
- Overload Ip> (overcurrent stage not thermal replica)
- Overcurrent I>
- Overcurrent I>>

19 > Title of presentation - Date - References 19


P111

Protection and Control features

3 Phase Overcurrent Protection (50/51)

First (Ip>) and second (I>) threshold with:


- definite time delay trip

- or inverse time delay trip

Each threshold set independently

Definite time delay trip for the third (I>>) threshold

20 > Title of presentation - Date - References 20


P111

3 Phase Overcurrent Protection


Available IEC Curves
Operating Time (s)
1000
IEC SI (Standard Inverse)
IEC VI (Very Inverse)
IEC EI (Extremely Inverse)
100

10

0.1
1 10 100
Current (Multiples of Is)

21 > Title of presentation - Date - References 21


P111
3 Phase Overcurrent Protection

Time
tIp>

I>
tI>
I>>
tI>>

Current

Selective operation can be set


22 > Title of presentation - Date - References 22
P111

Protection features

Earth Fault Non-directional Overcurrent Protection (50N/51N)

Two thresholds:
- First Io>
- Second Io>>
First (Io>) threshold with:
- definite time delay trip

- or inverse time delay trip

SI standard inverse
VI very inverse
EI extremely inverse
Definite time delay trip for the second (Io>>) threshold
Each threshold set independently

23 > Title of presentation - Date - References 23


P111

Protection / automation features

Temperature monitoring inside the transformer (PTC sensor


input)

External process monitoring via dedicated input


(e.g. pressure sensor etc.)

Output relays latching (P2, P3)

Two setting groups to be selected via binary input, RS485 or


through the menu

24 > Title of presentation - Date - References 24


P111

Fault Recording Measurements

Record of 3 most recent faults

Flag information (affected phase, tripped or triggered


element, tripping values log) indicated on the relay front
panel display

Fault record transfer (one or all events) via


RS485 rear communication port

25 > Title of presentation - Date - References 25


P111

Measurements
Phase current setting ranges (10 1000Hz true RMS value):
0,4A - 10A
2A - 50A
4A - 100A
8A - 200A
Earth fault current setting ranges (40 70Hz):
0.005A - 0.5A
0.05A - 2.5A
0.2 - 10A

26 > Title of presentation - Date - References 26


P111