Академический Документы
Профессиональный Документы
Культура Документы
D E S I G N & M AT E R I A L S
DESIGN
Introduction
For all building construction or remodeling projects, the owner
or occupant must first create a concept for the new design, and then
the architect or designer can produce a set of building plans. These
plans convey all the required information to the local inspection
authority and associated building trades so that construction or
remodeling can take place. Because commercial and industrial
buildings contain a number of electrical systems, these plans include
specific electrical designs and additional documentation to verify that
the design conforms to all required building codes.
Definition of Terms
Electrical systems - are groups of electrical
components connected to carry out some
operation.
National Electrical Code (NEC), or NFPA 70 - is a
regionally adoptable standard for the safe
installation of electrical wiring and equipment in
the United States.
Circuit node - refers to
any point on a circuit
where two or more
circuit elements meet.
Definition of Terms
One-line diagram or
single-line diagram
(SLD) - is a simplified
notation for
representing a three-
phase power system.
Definition of Terms
Functional Flow Block Diagram (FFBD) - is a
multi-tier, time-sequenced, step-by-step flow
diagram of a systems functional flow.
Electrical system design
is the design of electrical systems. This can be
as simple as a flashlight cell (battery)
connected through two wires to a light bulb or
as involved as the space shuttle.
The Design Process
An electrical design goes through several important
stages of development. First, the designer must
understand the scope of the project. Then, the
designer defines and designs each component
(such as general office areas, specialized
machinery, and power distribution equipment) to
recognized industry standards. These individual
components are compiled to form the final
presentation for the design.
Design
The following would be appropriate for the design of a moderate to
large electrical system:
1. A specification docume
nt is written. Probably
would have been written
by the client. The
specification document
states in plain language
and numerical detail what
the customer expects. If it
is well written, it will be
used as a reference
throughout the electrical
system design.
Design
Dimmer Switches
= devices used to lower the brightness of a light. By changing
the voltage waveform applied to the lamp, it is possible to
lower the intensity of the light output.
Connected load
It is the Sum of all the loads connected to the electrical system, usually expres
sedin watts.
Demand load
It is the electric load at the receiving terminals averaged over a specified dem
and
interval of time, usually 15 min., 30 min., or 1 hour based upon the
particular utilitys demand interval. Demand may be expressed in amperes,
kiloamperes, kilowatts, kilovars, or kilovoltamperes.
Demand Interval
It is the period over which the load is averaged, usually 15 min., 30 min., or 1
hour.
LOAD ESTIMATION
DEFINITION OF IMPORTANT TERMS IN LOAD ESTIM.
Maximum demand
It is the greatest of all demands that have occurred during a specified period o
f time such as 5 minutes, 15 minutes, 30 minutes or one hour. For utility
billing purposes the period of time is generally one month.
Demand factor
The demand factor is the ratio of the maximum demand on a system to the
total connected load of the system.
Example
5 storeys apartment building with 25 consumers, each having 6 kVA of
installed load. Calculate the following:
Solution:
The current entering the third floor (the third level service size) = sum of
currents delivered to third and fourth floors
The number of consumers in the third and fourth floors = 4+6=10 consumers
So, the current entering the third floor = (36+24) x 0.63 x 1000 / (400 x 3) =
55A