Handbook
ABB Group - 1 -
Sep 16, 2017
Capacitor protection
Capacitor banks- General
Phase compensation of loads
Reactive generation for voltage control
400 kV
130 kV
D-connected
Single Y-connected
Double Y-connected
Earthed or unearthed
ABB Group - 5 -
Sep 16, 2017
Capacitor protection
Earthing of Shunt Capacitors
Inrush currents
Transient over voltages
Temporary over voltages
Out rush currents
ABB Group - 10 -
Sep 16, 2017
Capacitor protection
General conditions as per IEC 60871-1 (1997)
S
ABB Group - 12 -
Sep 16, 2017
Capacitor protection
Unit Overcurrent Protection
ABB Group - 14 -
Sep 16, 2017
Capacitor protection
Short- circuit protection
A B C
ABB Group - 16 -
Sep 16, 2017
Capacitor protection
Ground- fault protection
I>
I>
I>
I>
ABB Group - 18 -
Sep 16, 2017
Capacitor protection
Capacitor bank overload relay
This protection prevents capacitor overload due to
overvoltage and/or harmonic currents. The overload
protection is measuring in three phases for banks
with grounded neutral. For banks with insulated
neutral it is usually measuring in two phases.
The SPAJ 160C is actually a maximum-value-
detecting voltage protection whereby the relay
converts measured capacitor currents, including
harmonics up to the 13th, to a maximum voltage
value. Its characteristic corresponds to the voltage
tolerance levels according to ANSI/IEE std. 18 and
IEC 60871-1.
ABB Group - 19 -
Sep 16, 2017
Capacitor protection
Under current relay
I>
ABB Group - 23 -
Sep 16, 2017
Capacitor protection
SPAJ 160 C : Unbalance , Overload and
Under current functions
ABB Group - 24 -
Sep 16, 2017
Capacitor protection
Questions to be answered
What is the % of allowable unbalance current in a healthy
bank. Is there any standard IS or IEC for this?
Capacitor failure rates is very high compared to other devices
(e.g: NDPL). Why?
With internal fuses replacement not possible. Why not provide
them external to capacitor.
Often clearance between terminal of capacitor and other live
parts is not enough.
ABB Group - 25 -
Sep 16, 2017
Protection Application Capacitor Protection
Handbook -settings
ABB Group - 26 -
Sep 16, 2017
Capacitor protection
Phase over current relays
The pick up current seting must be set above highest possible
load current
It shall also serve as overload protection
Capacitor is designed to withstand 30% of rated current ( IEC
70)
The lowest setting value can be written as
I pickup = 1.2 . I max/K ( K is resetting ratio)
The high set relay should be set so as to be selective wrt
other relays
I high > 1.2. K t .I efmax
K t is transient overreach and I efmax is largest fault current
from capacitor bank in case of external fault or a phase to
phase fault
If the bank is not earthed it can be taken 6 times rated current
Time setting should be set as to get shortest fault time with
maintained selectivity wrt external faults
ABB Group - 27 -
unwanted tripping
Capacitor protection
Unbalance current relays
Current Setting
The current setting must be chosen so that normal unbalance
will not result in operation of relay and unbalances dangerous
for the capacitor elements will cause operation of the relay
Time setting
Must be so short that it operates before any other relay in the
system
ABB Group - 28 -
Sep 16, 2017
Capacitor protection
Over voltage protection relay
Voltage setting
The capacitor elements are designed to withstand up to 1.1 times
rated voltage. Therefore voltage setting should be chosen
accordingly
Time setting
Must be chosen so that short time overvoltages will not trip the
bank. Reasonable setting is 0.2 to 0.6 sec.
ABB Group - 29 -
Sep 16, 2017
ABB Group - 30 -
Sep 16, 2017
Capacitor protection