LZ96a Distance Relay

ABB India
Utilities - Automation
LZ96a Distance Relay

Non - switched

distance relay

type LZ 96a

Lines and cables in

Solidly grounded networks

Series - compensated lines

ABB India
Utilities - Automation
LZ96a Distance Relay

Starter
- Phase selector
- Fault detector to start the zone
timers
- Avoids load encroachment

Measurement
- Directional

- Accurate impedance reach

ABB India
Utilities - Automation
LZ96a Distance Relay

New features versus LZ96


More flexible standard versions
Casing with terminals on the back
Protection classes IP10 to IP50
Microprocessor based binary logic for
- tripping logic
- timers
- Communication schemes
- self-diagnosis

All parameters adjustable by means of a clearly structured menu


All usual communication schemes
Local alarms on alphanumerical display
Storage of up to 9 events
Signal matrix for remote signalling

ABB India
Utilities - Automation
LZ96a Distance Relay

Application & Features


Transmission lines and cables
Solidly grounded networks
Single or double circuit lines
Series-compensated lines
Heavy or low current faults
High-resistance earth faults
During power swings
Single or three-pole tripping
Rapid or slow auto reclosure
Close-onto fault
Weak infeed end

ABB India
Utilities - Automation
LZ96a Distance Relay

Starting RN SN TN 2PH

Measurement M1 RN SN TN 2PH

Measurement M2 RN SN TN 2PH

Reverse
RN SN TN 2PH
measurement MB

Simultaneous measurement by up to 16
distance elements

ABB India
Utilities - Automation
LZ96a Distance Relay

Ph-Ph
element

Phase
& selection
logic
Ground
detector

Phase-to-phase starter
No adjustment of 1
0

ABB India
Utilities - Automation
LZ96a Distance Relay

ABB India
Utilities - Automation
LZ96a Distance Relay
LZ 96a-MAIN COMPONENTS

ABB India
Utilities - Automation
LZ96a Distance Relay

Two standard versions, 3 racks high,


are prepared for

Starting with different characteristics


(ZA91)
Measurement M1, 3 zones
Measurement M2, 1 zone
Reverse measurement MB for carrier
schemes
Polygon supplement KE91
Power swing blocking UP92
Directional earth fault relay RE93
Autorecloser WT96a (only version 34)
Tripping contacts for 2 circuit breakers
30 programmable signaling relays

ABB India
Utilities - Automation
LZ96a Distance Relay

Functional features
- Starting
- Measurement
- Logic

Design
- Standard versions
- Casing

ABB India
Utilities - Automation
LZ96a Distance Relay

ABB India
Utilities - Automation
LZ96a Distance Relay
LZ96-STARTING ELEMENT

ABB India
Utilities - Automation
LZ96a Distance Relay
LZ96-STARTING CHARACTERISTICS 2-1

ABB India
Utilities - Automation
LZ96a Distance Relay
LZ96-STARTING CHARACTERISTICS 2-2

ABB India
Utilities - Automation
LZ96a Distance Relay
LZ96-STARTING ANCILLARY ELEMENT

ABB India
Utilities - Automation
LZ96a Distance Relay

ADVANTAGE OF CHOSEN
PH-PH-STARTER

- Not sensitive to load

- Not sensitive to power swings;


thus allows tripping for faults during
the time the power swing blocking unit
has operated

- Permits a ground fault criterion, which is


to large extent independent of the zero
sequence current and needs no setting.

ABB India
Utilities - Automation
LZ96a Distance Relay
LZ96a-STARTING CHARACTERISTICS WITH ANCILLARY ZA91

ZA91

ZA91-1

ABB India
Utilities - Automation
LZ96a Distance Relay
LZ 96-STARTING CHARACTERISTICS

ABB India
Utilities - Automation
LZ96a Distance Relay
METHOD OF VECTOR LOCI POLAR CHARACTERISTICS GENERAL 1-4

ABB India
Utilities - Automation
LZ96a Distance Relay

METHOD OF VECTOR LOCI STRAIGHT LINE-CHARACTERISTICS 2-4

ABB India
Utilities - Automation
LZ96a Distance Relay

METHOD OF VECTOR LOCI STRAIGHT LINE-CHARACTERISTICS 2-4

ABB India
Utilities - Automation
LZ96a Distance Relay
METHOD OF VECTOR LOCI CIRCLE-CHARACTERISTICS 3-4

ABB India
Utilities - Automation
LZ96a Distance Relay
METHOD OF VECTOR LOCI CIRCLE-CHARACTERISTICS 4-4

REMARK :
IF C _I_ D THE CHARACTERISTICS POINTS PO AND P ARE
SITUATED ON THE DIAMETER.

3) DETERMINATION OF THE CENTRE-VECTOR

ON = A D* - B C *

C D* - D C*
4) DETERMINATION OF THE RADIUS

R=BC -AD

REMARK : C D* - D C*

- THE VECTORS WITH INDEX [ * ] ARE COMPLEX CONJUGATES


[E.G., D = 3 + J2; D* = 3 - J2]

-THE CALCULATION OF THE RADIUS R IS EASILY DETERMINATED


ABB India IF WE TAKE ITS ABSOLUTE VALUE
Utilities - Automation
LZ96a Distance Relay
GENERAL EQUATIONS FOR COMPARATORS

ABB India
Utilities - Automation
LZ96a Distance Relay

LZ 96 a-STARTING CHARACTERISTICS

ABB India
Utilities - Automation
LZ96a Distance Relay
LZ 96a-STARTING CHARACTERISTICS

ABB India
Utilities - Automation
LZ96a Distance Relay
LZ 96a-STARTING CHARACTERISTICS

ABB India
Utilities - Automation
LZ96a Distance Relay
ALICURA- RELAY SETTING DIAGRAM e.g.

ABB India
Utilities - Automation
LZ96a Distance Relay

REFERENCE VOLTAGE

ABB India
Utilities - Automation
LZ96a Distance Relay
LZ96-MEASUREMENT ELEMENT

ABB India
Utilities - Automation
LZ96a Distance Relay

Digital Step Timer

ABB India
Utilities - Automation
LZ96a Distance Relay

ABB India
Utilities - Automation
LZ96a Distance Relay

ABB India
Utilities - Automation
LZ96a Distance Relay

ABB India
Utilities - Automation
LZ96a Distance Relay
MEASURING CHARACTERISTIC WITH ANCILLARY KE91

ABB India
Utilities - Automation
LZ96a Distance Relay
LZ96-RESISTANCE ANCILLARY (POLYGON)

ABB India
Utilities - Automation
LZ96a Distance Relay
LZ96-TRIPPING CHARACTERISTIC FOR SINGLE-POLE FAULTS, WHEN USING THE RESISTANCE ANCILLARY

ABB India
Utilities - Automation
LZ96a Distance Relay
RX - CHARACTERISTICS

ABB India
Utilities - Automation
LZ96a Distance Relay
LZ 96a-STARTING AND MEASUREMENT CHARACT. (WITH MEMORY WITHOUT MEMORY)