ELECTRICAL SYSTEM DESIGN 1
LLF=0.95X0.85X0.88X0.98=.65
STEP 7.
Calculate the total initial lamp lumen:
TILL= (500X5X6)/(0.65X0.67) 34,400 LUMEN
STEP 8.
# of luminaries =(500x5x6)/(2600x2(0.65x0.67 ))
=6.62 or use 8 luminaries
STEP 9.
Draw &
det. the spacing
OTHER ROOMS
CLINIC AND COUNSELING
Size of room : 6x5m; 2.9 meter ceiling
Height of workplane : .75 m.
Reflectance factor : ceiling 80%, wall 50%, floor
20%
Luminaire type : type 49 w/ 2 lamps
Lamps : F-40 T-12; daylight, rapid
start
Atmosphere : clean
Interval bet cleaning : 12 months
Recommended luminance level is 500 lux
RCR= 3.94
CCR= 0
FRC= 1.375
CU= 0.65 @
LLF= 0.55
# of luminaries =(500x5x6)/(2x3200x.65x.55)
=8.06 OR 8
ACTIVITY AREA
Size of room : 6x5m; 2.9 meter ceiling
Height of workplane : .75 m.
Reflectance factor : ceiling 80%, wall 50%, floor
20%
Luminaire type : type 49 w/ 2 lamps
Lamps : F-40 T-12; daylight, rapid
start
Atmosphere : clean
Interval bet cleaning : 12 months
Recommended luminance level is 500 lux
RCR= 3.94
CCR= 0
FRC= 1.375
CU= 0.65 @
LLF= 0.55
# of luminaries =(500x5x6)/(2x3200x.65x.55)
=8.06 OR 8
KITCHEN & DINING AREA
Size of room : 6x5m; 2.9 meter ceiling
Height of workplane : 0 .75 m.
Reflectance factor : ceiling 50%, wall 30%,
floor 10%
Luminaire type : type 26 w/ 2 lamps
Lamps : F-20 T-12 WW, rapid start
Atmosphere : medium
Interval bet cleaning : 12 months
Recommended luminance level is 150 lux
RCR= 3.94
CCR= 0
FRC= 1.375
CU= 0.51 @
LLF= 0.50
# of luminaries =(150x5x6)/(2x1300x.51x.50)
=6.78 OR 7
BEDROOM- plan A
Size of room : 6x5m; 2.8 meter ceiling
Height of workplane : 0
Reflectance factor : ceiling 70%, wall 30%, floor
10%
Luminaire type : type 7(CFL)
Lamps : 14 W(PHILIPS), warm white,
3U, 300 lumen light output
Atmosphere : medium
Interval bet cleaning : 12 months
Recommended luminance level is 150 lux
RCR= 5.13
CCR= 0
FRC= 0
CU= 0.41 @
LLF= 0.55
# of luminaries =(150x5x6)/(800x.41x.55)
=24.9 OR 24
BEDROOM- plan B
Size of room : 6x5m; 2.8 meter ceiling
Height of workplane :0
Reflectance factor : ceiling 70%, wall 30%,
floor 10%
Luminaire type : type 48 W/ 2 ;AMP
Lamps : F-20 T-12 WW, rapid start
Atmosphere : medium
Interval bet cleaning : 12 months
Recommended luminance level is 150 lux
RCR= 5.13
CCR= 0
FRC= 0
CU= 0.45 @
LLF= 0.55
# of luminaries =(150x5x6)/(1300x0.54X.55)
=6.9 OR 6
HALL WAY
Size of room : 16x5m; 2.8 meter ceiling
Height of workplane : 0
Reflectance factor : ceiling 70%, wall 30%, floor
10%
Luminaire type : type 7(CFL)
Lamps : 14 W(PHILIPS), warm white,
3U, 300 lumen light output
Atmosphere : medium
Interval bet cleaning : 12 months
Recommended luminance level is 150 lux
RCR= 5.13
CCR= 0
FRC= 0
CU= 0.41 @
LLF= 0.55
# of luminaries =(150x5x6)/(800x.41x.55)
=26.6 OR 27