ELECTRICAL SYSTEM DESIGN 1

Engr. Lorenzo l. Moricho


Instructor
DESIGN OF LIGHTING SYSTEM
PILOT ROOM TO BE LIGHTED

Type of building : Drop-in Center(orphanage)


Type of room : Head office
Average age of worker : 45
Size of room : 6x5 m; 2.9 ceiling
Height of workplane : 0.75 m
Reflectance factor : Ceiling 80%, walls 50%,floor 20%
Luminaire type : Type 49, with 2 lamps
Lamps : F 40 T-12 D; 40 W, Daylight, rapid
start tubular fluorescent lamp
Atmosphere : Clean
Interval between cleaning : 12 month
STEP 1.
From table 5-3 level of illumination for various types
of occupancies, recommended level is 500 lux.
STEP 2. Calculate cavity
ratios:
STEP 3.
RCR= (5X1.99)X((6†5)/(6X5))= 3.65
CCR= (5X0)X((6†5)/(6X5))= 0
FCR = (5X0.75)X((6†5)/(6X5))= 1.38
STEP 4.

Det. the effective floor cavity reflectance


from table. At 20%= 18.25 ; that by
interpolation.
STEP 5 .
Det. Coefficient of utilization. By interpolating, CU= 0.67
STEP 6.
Calculate light loss factor:
Ballast factor= 0.95
LLD= 0.85(for individual replacement)
LDD= 0.86(from category on fig.20.36)
RSDD= 0.94(from table on RSDD, for clean atmosphere
@12 month)

LLF=0.95X0.85X0.88X0.98=.65
STEP 7.
Calculate the total initial lamp lumen:
TILL= (500X5X6)/(0.65X0.67) 34,400 LUMEN

STEP 8.
# of luminaries =(500x5x6)/(2600x2(0.65x0.67 ))
=6.62 or use 8 luminaries
STEP 9.
Draw &
det. the spacing
OTHER ROOMS
CLINIC AND COUNSELING
Size of room : 6x5m; 2.9 meter ceiling
Height of workplane : .75 m.
Reflectance factor : ceiling 80%, wall 50%, floor
20%
Luminaire type : type 49 w/ 2 lamps
Lamps : F-40 T-12; daylight, rapid
start
Atmosphere : clean
Interval bet cleaning : 12 months
Recommended luminance level is 500 lux
RCR= 3.94
CCR= 0
FRC= 1.375
CU= 0.65 @
LLF= 0.55
# of luminaries =(500x5x6)/(2x3200x.65x.55)
=8.06 OR 8
ACTIVITY AREA
Size of room : 6x5m; 2.9 meter ceiling
Height of workplane : .75 m.
Reflectance factor : ceiling 80%, wall 50%, floor
20%
Luminaire type : type 49 w/ 2 lamps
Lamps : F-40 T-12; daylight, rapid
start
Atmosphere : clean
Interval bet cleaning : 12 months
Recommended luminance level is 500 lux
RCR= 3.94
CCR= 0
FRC= 1.375
CU= 0.65 @
LLF= 0.55
# of luminaries =(500x5x6)/(2x3200x.65x.55)
=8.06 OR 8
KITCHEN & DINING AREA
Size of room : 6x5m; 2.9 meter ceiling
Height of workplane : 0 .75 m.
Reflectance factor : ceiling 50%, wall 30%,
floor 10%
Luminaire type : type 26 w/ 2 lamps
Lamps : F-20 T-12 WW, rapid start
Atmosphere : medium
Interval bet cleaning : 12 months
Recommended luminance level is 150 lux
RCR= 3.94
CCR= 0
FRC= 1.375
CU= 0.51 @
LLF= 0.50
# of luminaries =(150x5x6)/(2x1300x.51x.50)
=6.78 OR 7
BEDROOM- plan A
Size of room : 6x5m; 2.8 meter ceiling
Height of workplane : 0
Reflectance factor : ceiling 70%, wall 30%, floor
10%
Luminaire type : type 7(CFL)
Lamps : 14 W(PHILIPS), warm white,
3U, 300 lumen light output
Atmosphere : medium
Interval bet cleaning : 12 months
Recommended luminance level is 150 lux
RCR= 5.13
CCR= 0
FRC= 0
CU= 0.41 @
LLF= 0.55
# of luminaries =(150x5x6)/(800x.41x.55)
=24.9 OR 24
BEDROOM- plan B
Size of room : 6x5m; 2.8 meter ceiling
Height of workplane :0
Reflectance factor : ceiling 70%, wall 30%,
floor 10%
Luminaire type : type 48 W/ 2 ;AMP
Lamps : F-20 T-12 WW, rapid start
Atmosphere : medium
Interval bet cleaning : 12 months
Recommended luminance level is 150 lux
RCR= 5.13
CCR= 0
FRC= 0
CU= 0.45 @
LLF= 0.55
# of luminaries =(150x5x6)/(1300x0.54X.55)
=6.9 OR 6
HALL WAY
Size of room : 16x5m; 2.8 meter ceiling
Height of workplane : 0
Reflectance factor : ceiling 70%, wall 30%, floor
10%
Luminaire type : type 7(CFL)
Lamps : 14 W(PHILIPS), warm white,
3U, 300 lumen light output
Atmosphere : medium
Interval bet cleaning : 12 months
Recommended luminance level is 150 lux
RCR= 5.13
CCR= 0
FRC= 0
CU= 0.41 @
LLF= 0.55
# of luminaries =(150x5x6)/(800x.41x.55)
=26.6 OR 27