convection
warm air
radiation
1 lb
water 1 Btu
60F 61F
1 kg
water
1 kcal
15C [4.19 kJ] 16C
What is BTU?
BTU refers to British Thermal Unit.
Sensible Heat
60F 212F
[15.6C] [100C]
Latent Heat
212F 212F
[100C] [100C]
Human Comfort
Conditions at which most people are likely to
feel comfortable most of the time.
Humidity Ratio
A
comfort zone
70F 80F
[21.2C] [26.7C]
Dry-bulb Temperature
Cooling Load Estimation Procedure
Cooling Load Components
roof
lights partition
people wall
infiltration
glass solar
equipment
glass
conduction
exterior
wall
floor
Cooling Load Components
cooling load components Sensible latent space coil
Load load load load
Conduction through roof, walls,
windows, and skylights
Solar radiation through windows, skylights
Conduction through ceiling, interior
partition walls, and floor
People
Lights
Equipment/ Appliances
Infiltration
Ventilation
System Heat Gains
Time of Peak Cooling Load
East-facing
window roof
Heat gain
12 6 12 6 12
mid a.m. noon p.m. mid
Example Office Space (Room 101)
North
Plan view
Outdoor Design Conditions
0.4% 1% 2%
DB WB DB WB DB WB
Q = U A T
U Overall heat transfer coefficient of the surface
A Area of the surface
T Dry bulb temperature difference across the surface
U-factor
wood studs
insulation
concrete block
gypsum
board
aluminum
siding
U-factor for Example Wall
B
Solar Effect
12 6 12 6 12
mid a.m. noon p.m. mid
Conduction through Sunlit Surfaces
Q = U A CLTD
CLTD : Term used to account for the added heat
transfer due to the sun shining on exterior walls,
roofs, and windows, and the capacity of the wall
and roof to store heat.
CLTD Factors for West-Facing Wall
hour
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
CLTD
35 30 25 21 17 14 11 8 7 6 6 7 8 10 12 16 22 30 37 44 48 48 45 41
(F)
CLTD
19 17 14 12 9 8 6 4 4 3 3 4 4 6 7 9 12 17 21 24 27 27 25 23
(C)
Conduction through Sunlit Surfaces
Qwindows = U A x CLTD
Q = A SC SCL
Where,
SC Shading Coefficient
Equipment
People
Lights
Appliances
Heat Generated by People
Metabolism of the human body normally
generates more heat than it needs
2 0.65 0.74 0.16 0.11 0.08 0.06 0.05 0.04 0.03 0.02 0.02 0.01
4 0.65 0.75 0.81 0.85 0.24 0.17 0.13 0.10 0.07 0.06 0.04 0.03
6 0.65 0.75 0.81 0.85 0.89 0.91 0.29 0.20 0.15 0.12 0.09 0.07
8 0.65 0.75 0.81 0.85 0.89 0.91 0.93 0.95 0.31 0.22 0.17 0.13
10 0.65 0.75 0.81 0.85 0.89 0.91 0.93 0.95 0.96 0.97 0.33 0.24
outdoor-air
supply duct
intake
diffuser
air handler
with fan and
cooling coil
Outdoor Air Requirements
Type of Space Outdoor Air/ person Outdoor Air/ ft2 (m2)
air handler
fan motor
Components of Fan Heat
blow-through
configuration
draw-through
configuration
Heat Gain in Ductwork
Summary of Cooling Loads
sensible load latent load
Btu/hr [W] Btu/hr [W]
conduction through roof 12,312 [3,563]
conduction through exterior wall 502 [144]
conduction through windows 1,310 [359]
solar radiation through windows 22,733 [6,447]
people 4,500 [1,350] 3,600 [990]
lights 22,097 [6,480]
equipment 8,184 [2,404] 1,540 [450]
infiltration 2,988 [876] 3,969 [1,159]
total space cooling load 74,626 [21,623] 9,109 [2,599]
ventilation 6,640 [2,047] 8,820 [2,709]
total coil cooling load 81,266 [23,670] 17,929 [5,308]
Psychometric Analysis
74,626
SHR = = 0.89
74626 + 9109
21623
SHR = = 0.89
21623 + 2599
Single-Space Analysis
outdoor
supply cooling
coil air
fan
supply
air
return
exhaust
air
air
space
Determine Supply Airflow
supply 74,626
airflow = = 2,990 cfm
1.085 (78 55)
supply 21,623
= = 1.40 m3/s
airflow 1,210 (25.6 12.8)
Calculate Entering Coil Conditions
ventilation airflow
% outdoor air =
total supply airflow
360 cfm
%OA = = 0.12
2990 cfm
0.18 m3/s
%OA = = 0.12
1.40 m3/s
Calculate Entering Coil Conditions
95F 0.12 = 11.4F
78F 0.88 = 68.6F
mixture = 80.0F
76F
[24.4C]
humidity ratio
35C 0.12 = 4.2C
25.6C 0.88 = 22.5C 66.5F
B
mixture = 26.7C [19.2C]
A C
78F 80F 95F
[25.6C] [26.7C] [35C]
dry-bulb temperature
Determine Supply Air Temperature
B 0.6
C 0.8
1.0
D A
59F
[15C]
dry-bulb temperature
Recalculate Supply Airflow
supply 74,626
= = 3,620 cfm
airflow 1.085 (78 59)
supply 21,623
= = 1.69 m3/s
airflow 1,210 (25.6 15)
Total Cooling Load on Coil
Room 101
Btu/hr [W]
total space sensible load 74,626 [21,623]
total space latent load 9,109 [2,599]
ventilation 15,460 [4,756]
supply
fan
cooling
coil
Sum-of-peaks
supply airflow = 6,648 CFM [3.10 m3/s]
Block
supply airflow = 6,303 CFM [2.95 m3/s]
Block Cooling Load
Room 101 Room 102
loads at 4 p.m. Btu/hr [W] Btu/hr [W]
total space sensible load 74626 [21623] 55313 [16158]
total space latent load 9109 [2599] 9109 [2599]
ventilation 15460 [4756] 15460 [4756]