A drier must take up 200 lb/hr of H2O. Entering fresh air at 70F and 50% RH (A) is
mixed with recycle air (R) and enters the drier, leaving at 140F and 80% RH (P). What is
the volume of R (at its conditions) per volume of P (at its conditions) ? The barometer
reads 14.62 psia, and P and R each are at 14.77 psia pressure. The dew point of the air
after the heater is 100F. ssee figure P18.26
140F
R
70F 80% RH Udara keluar
50% RH 14.77 psia 140F
80% RH
14.62 psia 14.77 psia
heater 100F
A(ud.segar) B C dew P
D
Dryer
Dried products Wet stuck
E F
Diketahui : P barometer = 14.62 psia
A C P=R

P* H2O 0.3628 (T= 70F) 0.9487 (T=100 F) 2.887 (T = 140F)


Steam table Steam table
PH2O RH X P*H2O RH X P*H2O RH X P*H2O
(0.5)(0.3678) (100/100)(0.9487) 0.8 x 2.887 = 2.3096
0.1814 0.9487
P total 14.62 psia 14.77 (asumsi) 14.77

P Udara= Ptotal PH2O Ptotal PH2O Ptotal PH2O


= 14.62 0.181 = = 14.77 0.9487
14.4386 = 13.8213
= 14.77 2.3096
= 12.4604
Overall all
A+F =E+P
Neracakomponen H2O :
A H2O + F H2O = E H2O + P H2O
0.1814 200 2.3096
A + =0+P
14.62 18 14.77
0.01241 A + 11.1111 = 0.15637P .. (1)
NeracakomponenUdara :
A Udara + F udara = E Udara + P Udara
14.4386 12.4604
A 14.62 + 0 = O + P 14.77
0.98759 A = 0.84363 P (2)
0.01241 A - 0.15637 P = -11,1111 x 79.0967
0.98159 A 0.84363 P = 0 x1

0.98159 A 12.3683P = -878.8513


0.98159 A 0.84363P = 0
0 - 11.52467P = -878.8513
P = 76.2583 lbmol
0.98159 A 0.84363 (76.2583) = 0
0.98159 A = 64.3338
A = 65.5404 lbmol

PV = nRT
..
VRecycle =

36.8176 600 10.73 3/
=
14.77

= 16048.186 ft

. .
Vproduk =

3
76.2583 .10.73

= x 600R
14.77

= 33301.695 ft3
16048.186
Jadi = = 0.481 9
33301.695