Types
Capacitance Voltage Transformer
The errors due to harmonic voltages can
be eliminated by the use of capacitive
voltage dividers.
Usually, a standard compressed air or gas
condenser is used as C1.
C2 may be any large capacitor (mica,
paper, or any low loss condenser).
C1 is a three terminal capacitor and is
connected to C2 through a shielded cable,
and C2 is completely shielded in a box to
avoid stray capacitances.
Cm-Capacitance of the meter and
connecting cable
V2-meter reading
Capacitance divider with a suitable matching or
isolating potential transformer tuned for
resonance condition is often used in power
systems for voltage measurements.
CVT is connected to a low impedance device
like a wattmeter or pressure coil or relay coil .
Supply to few KV load
C1 is made with few numbers of capacitor
banks with the limit of pico farads and total
become few thousands of pico farads.
Matching transformer is connected between C1
and C2.
The h.v. winding rating may be 10 to 30
kV with the Lv. winding rated from 100 to
500 V.
The value of the tuning choke L is chosen
to make the equivalent circuit of the CVT
purely resistive or to bring resonance
condition.
Condition for Resonance is,
Schematic Representation
Equivalent Circuit
The advantages of a CVT are: