Академический Документы
Профессиональный Документы
Культура Документы
Approved Materials
All materials and methods for
installation are to conform to
Chapter 6 of NFPA 13- 2007 or
the individual product listings
and approvals. When in
doubt..
Make the installing
contractor prove it to
your satisfaction!!!!
If it looks incorrect, it probably is
Be wary of new products, have
contractor provide cut sheets
when in doubt
Good review with thorough walk
through at hydro at end of job
Your interpretation of the codes
and standards is to be met or
proven incorrect- codes/
standards are in writing- not
inferred
Sometimes corners are cut by
unscrupulous contractors
Some poor installs are mistakes
or human error - BUT.
Report repeat
offenders to the
State Fire
Marshals office!!!
REMEMBER
You are the last line of defense
to ensure the end user gets what
they expect and paid for!!! These
are your customers, you are
their expert!
Poor installs fail annual
inspections and cost the owner
money later for repairs
Shall
3.2.4 Indicates a mandatory
requirement.
Should
3.2.5 Indicates a recommendation
or that which advised but not
required.
System Acceptance
For Environmentally
Sensitive Areas
Computer Rooms
Surgical Suites
Tele-Data Switch Rooms
Fine Art Storage Rooms
Pre Action System
Preaction Requirements
-24.2.3.3
Hydrostatic and Cover
Walkthrough and Final
Operational (Alarms, Tamper,
Main Drain Test)
Confirm Code compliance
Ensure correct number of spare
heads are left on site per NFPA
13-2007 Section 6.2.9- Dry heads
not required. Sprinkler Wrench is.
Preaction Systems Also
Require
Test the preaction valve
operation in accordance with the
manufacturers instructions- ask
for literature if there is any
questions on operation
Test manual and remote control
activation- this can be electric,
pneumatic or a combination
Is the piping supervised? Sec.
7.3.2.4 requires supervision to
ensure system integrity.
If supervisory air or nitrogen is
used- it needs to conform to
7.2.6 for dry systems
30 minute refill requirement.
Also needs to maintain a
minimum supervisory pressure
of 7 psi.
Preaction Riser Reqts
New systems to have White Tag
and Blue ITM Tag
All additions over 20 heads are
to have a new white tag added
Hydraulic Placard and General
Information Sign
PRV test tags on each PRV
Backflow certification and
Inspection by Plumbing Dept
Deluge System
For Highly
Flammable Areas
Aircraft Hangers
Solvent Processing
Dynamite Plants
Deluge System
Deluge System
Requirements -24.2.3.3
Hydrostatic and Cover
Walkthrough and Final
Operational (Alarms, Tamper,
Main Drain Test)
Confirm Code compliance
Ensure correct number of spare
heads are left on site per NFPA
13-2007 Section 6.2.9- Dry heads
not required. Sprinkler Wrench is.
Deluge Systems Also
Require
Test the deluge valve operation
in accordance with the
manufacturers instructions- ask
for literature if there is any
questions on operation
Test manual and remote control
activation- this can be electric,
pneumatic or hydraulic
Flow Testing of the system to
ensure hydraulic performance.
Calibrated gauges are to be
used at different points on the
system
These gauge readings are to be
compared to the hydraulic
calculations
Detection devices are to be
automatically supervised
Deluge Riser Reqts
New systems to have White Tag
and Blue ITM Tag
All additions over 20 heads are
to have a new white tag added
Hydraulic Placard and General
Information Sign
PRV test tags on each prv
Backflow certification and
Inspection by Plumbing Dept
Standpipe System
For Multi-level
Buildings
Per AHJ
Stand Pipe System
Standpipe System Tests
and Requirements
Hydrostatic and Cover
Walkthrough and Final
Operational (Alarms, Tamper,
Main Drain Test)
Confirm Code compliance and
hose thread compatibility
Flow test through roof manifold
testing approved water source- fire
pump, FD pumper truck, etc.
PRV tests. Ask for test log
Main Drain flow tests- record on
material test certificate
Dry and semi automatic shall be
trip tested to deliver 250 GPM at
the hydraulically most remote
hose connection within 3
minutes
Air testing applies per dry
systems in NFPA 13
Open and close each valve
manually- make sure hose caps
are on prior to testing
Check for proper signage
Fire Pump
Fire Pump Tests and
Requirements
Per NFPA 20- 2007 Edition
Chapter 14
Piping to be hydrostatically
tested per NFPA 13 reqs
All piping sizes to be verified per
table 5.25 (a) by rated pump
flow
All factory supplier
representatives are to be in
attendance during field
acceptance tests- AHJ should
be notified
As a minimum, proof of the initial
startup and field acceptance test
report should be provided at Fire
Marshal final
A copy of the certified pump test
characteristic curve shall be
available for comparison of the
field acceptance test.
Compare the curves to ensure
the pump meets its factory
specs.
Pump shall be run at minimum,
rated and peak loads
How is this determined??
Minimum is 0 GPM or churn
Rated is the rating of the pump
i.e.. 1000 GPM pump needs to be
tested at 1000 GPM
Maximum is 150 % of pump
rating- a 1000 GPM rated pump
is capable of 1500 GPM flow
Per NFPA 14- 2007, Section
6.2.1- Pumps shall furnish not
less than 150 percent of rated
capacity at not less than 65
percent of total rated head.
6.2.2- The shutoff head shall not
exceed 140 percent of rated
head for any type of pump.
Example 1- Pump is rated for 750
GPM @ 100 psi
150 percent of load-
1.5 X 750 =1125
65 percent of total rated head-
.65 X 100= 65 psi
Pump should provide 65 psi
MINIMUM at 1125 GPM
Example 2- Maximum Shutoff
100 psi Fire pump
NFPA Codes: 13, 13R, 13D, 14, 20, 22, 24, 25 & 101
UBC
IBC
IFC
Local AHJs
Other Jurisdictions Architect, Engineer & Owner
Insurance Underwriter
Post Construction Inspections and Maintenance