DS Agile CONTROL FUNCTION

Operator Training
Summary

1 – Control Modes
2 – Control Acknowledgement
3 – Control Condition Verifications
4 – Synchrocheck function
5 – Control in Direct Execute Mode
6 – Control in SBO Mode
7 – Device lock function
8 – Device Interlocking function
9 – Counter modification

2 Operator-Control 2
Control Modes

 Two kinds of Control Mode:


 Direct Execute (DE)
 Select Before Operate (SBO)
Direct Execute: a control may be performed directly without selection
SBO: the device must be selected before allowing execution

3 Operator-Control 3
Control Acknowledgement

 Positive acknowledgement: no pop-up window appears

 Negative acknowledgement: a control acknowledgement


pop-up will appear to display negative control
acknowledgement and to allow users with appropriate
rights to by-pass the interlocking control verification.

4 Operator-Control 4
Control Condition Verification

 The control condition verification handled by Operator


Interface are:
 The user rights
 The local/remote substation mode
 The local/remote or SBMC bay mode
 The automatic/ manual state of the associated automation
(typically, raise/lower control on a tap changer are forbidden if the
ATCC is in service)

5 Operator-Control 5
Control Condition Verification

 The user right verification is always active


 Other verifications can be activated or not at configuration
level for each control.

 Access to control buttons in the pop-up is depending of


control condition verifications

6 Operator-Control 6
Synchrocheck function

 Synchrocheck function can be used to close circuit


breaker in order to avoid interconnection of two
unsynchronised systems.

7 Operator-Control 7
Controls in Direct Execute Mode
without control window
A button is configured in a mimic, and can be associated to a
control order (e.g. OFF control order. The control is
immediately sent when the operator click on the button

8 Operator-Control 8
Controls in Direct Execute Mode
without control window

For analog controls, a box appears to allow the operator to


enter control value

After clicking on the button, e.g. “oil temp”, a box is displayed


in front of the button

Enter the value into the box then press Enter key to send the
value. The window will close automatically
9 Operator-Control 9
Controls in Direct Execute Mode
with control window

Two formats are available:


a- Direct Execute window
b- SBO window

10 Operator-Control 10
Controls in Direct Execute Mode
with control window

a- Direct Execute Window has format as follows:

Buttons to send orders

Explanation why the control is


not authorised in case of
negative checks

11 Operator-Control 11
Controls in Direct Execute Mode
with control window

b- SBO Window, after opening, has format as follows:

User must choose the order


before clicking on the Execute
button

Explanation why the control is


not authorised in case of
negative checks

12 Operator-Control 12
Controls in SBO Mode

In this mode, control phase is composed of two phases:


▪ The graphic selection phase
▪ The SBO phase itself

Two SBO modes exist:

. OPERATE ONCE: after selection phase, only one execution


is allowed and the de-selection is done automatically.

. OPERATE MANY: after selection phase, one or several


executions are allowed, and the operator must de-selects the device
manually

13 Operator-Control 13
Controls in SBO Mode
SBO Once

Click to open
Control Pop-up

14 Operator-Control 14
Controls in SBO Mode
SBO Once
After graphic selection phase, the control window is displayed:

User must choose the order


before clicking on the Execute
button

Explanation why the control is


not authorized in case of
negative checks

Click to choose command

Click on Select button to


choose device

15 Operator-Control 15
Controls in SBO Mode
SBO Once

If the selection is successful, Execute and Abort buttons are


highlighted:

Click on Execute button to


send command

Click on Abort button to


send a Cancel order

Depending on configurations, this control popup can be


automatically close or not.

16 Operator-Control 16
Controls in SBO Mode
SBO Many

After graphic selection phase, the control window is displayed:

User must choose the order before


clicking on the Execute button

Explanation why the control is not


authorised in case of negative
checks

Click to choose command

Click on Select button to


choose device

17 Operator-Control 17
Controls in SBO Mode
SBO Many

If the selection is successful:


. The user can choose Unselect button, to send Unselect
order
. Can choose Execute button to send command
. Can choose Abort to send Cancel order

Click on Unselect button


to send Un-select order

Click on Abort button to


send Cancel order

Click on Execute button to


send command

18 Operator-Control 18
Device Lock function

The device lock function, if defined in configuration, allow to refuse


controls on corresponding device from all points.

After locking, controls from all points are refused until unlocking.

The lock/unlock control is accessible using a specific control


window.

19 Operator-Control 19
Device Lock function
How to use

To lock/unlock a device, the user has to:


1. Open lock/unlock window:

20 Operator-Control 20
Device Lock function
How to use

2. Click on the Lock/ Unlock button, so the button is pushed

3. Depending on configuration, popup window is closed


automatically or not.

21 Operator-Control 21
Device Interlocking function

The device interlocking, if defined in configuration, consists adding


conditions to verify during control sequence.

The conditions are defined via logical equations and apply for a kind
of order on a device (close/open).

The association of the logic state true/false to the different variable


states (e.g. jammed, closed, open) is predefined during
configuration.

22 Operator-Control 22
Device Interlocking function

In case of positive result check, the control sequence keeps on.

In case of negative result check, an acknowledgement popup is


displayed, explaining that interlocking conditions are not fulfilled.

23 Operator-Control 23
Device Interlocking function

The corresponding interlocking equation can be viewed by clicking


on this button

User with appropriate rights


can bypass interlock
User can cancel control

Interlock equation result


red=NOK, green=OK

Interlock equation detail tree

24 Operator-Control 24
Counter modification

The user has to click on the value area, enter the value he wants
to send, press Enter then click on Set to send value