Вы находитесь на странице: 1из 9

Realisasi dan prediksi PMT Trip

2015 VS 2016
Penyebab Gangguan PMT 2016
KLASIFIKASI GANGGUAN s/d OKT
GANGGUAN 2015 GANGGUAN 2016
2016
KODE JUMLAH % KODE JUMLAH %
I1 32 11 % I1 50 16 %
I2 30 11 % I2 29 9% 6% 15% 0%
19%
I3 0 0% I3 1 0% 9%
1%
I4 0 0% I4 2 1%
30% 20%
E1 69 24 % E1 63 20 %
E2 57 20 % E2 95 30 %
E3 40 14 % E3 60 19 %
E4 55 19 % E4 20 6%
TOTAL 283 100 % TOTAL 320 100 % I1 I2 I3 I4 E1 E2 E3 E4

2016
No Faktor KODE Klasifikasi Penyebab TAHUN %
JAN FEB MAR APR MEI JUN JUL AGU SEP OKT NOV DES
1 INTERNAL 44b I1.KOMPONEN JUMPER SUTM RUSAK 0 5 0 1 0 3 1 1 1 2 - - 14 4%
2 INTERNAL 44a I1.KOMPONEN SUTM PUTUS 2 0 2 3 0 1 2 0 1 0 - - 11 3%
6 INTERNAL 41d-3 I1.KOMPONEN FCO PUTUS TIDAK DIKETAHUI PENYEBABNYA 1 1 1 2 1 1 0 0 1 0 - - 8 3%
7 INTERNAL 41d-4 I1.KOMPONEN KAWAT JTM TERURAI 2 0 2 0 1 1 0 1 2 3 - - 12 4%
8 INTERNAL 54 I1.KOMPONEN TERMINAL KABEL SKTM ( TERMINATING ) RUSAK 2 0 1 0 0 0 0 0 0 0 - - 3 1%
9 INTERNAL 51 I1.KOMPONEN GANGGUAN KABEL SKTM 0 0 0 1 0 1 0 0 0 0 - - 2 1%
SUB GANGGUAN AKIBAT I1 7 6 6 7 2 7 3 2 5 5 - - 50
10 INTERNAL 45 I2.PERALATAN ISOLATOR RUSAK 2 2 2 0 1 1 0 3 3 4 - - 18 6%
11 INTERNAL 47 I2.PERALATAN POLE SWITCH RUSAK ( ABSW,DS LOSS CONTACT ) 0 2 2 2 0 0 0 0 0 0 - - 6 2%
12 INTERNAL 46 I2.PERALATAN CUT OUT RUSAK 0 0 0 1 1 1 0 0 1 0 - - 4 1%
13 INTERNAL 48 I2.PERALATAN LIGTHNING ARRESTER RUSAK 0 0 0 0 0 0 0 0 1 0 - - 1 0%
SUB GANGGUAN AKIBAT I2 2 4 4 3 2 2 0 3 5 4 - - 29
21 EXTERNAL 37 I4.TIANG TIANG LISTRIK ROBOH KARENA SEBAB LAIN ( TANAH LABIL ) 2 0 0 0 0 0 0 0 0 0 - - 2 1%
SUB GANGGUAN AKIBAT I4 2 0 0 0 0 0 0 0 0 0 - - 2
22 EXTERNAL 41a E1.POHON & LAIN-LAIN GANGGUAN POHON 1 6 3 7 10 7 5 6 3 8 - - 56 18%
23 EXTERNAL 49 E1.POHON & LAIN-LAIN GANGGUAN TIDAK DITEMUKAN 4 0 3 0 0 0 0 0 0 0 - - 7 2%
SUB GANGGUAN AKIBAT E1 5 6 6 7 10 7 5 6 3 8 - - 63
24 EXTERNAL 41c E2.ALAM PETIR 13 3 8 8 7 4 3 5 5 10 - - 66 21%
25 EXTERNAL 81 E2.ALAM ANGIN KENCANG (PUTING BELIUNG ) 0 1 8 0 6 0 0 2 1 1 - - 19 6%
26 EXTERNAL 82 E2.ALAM HUFEB LEBAT 1 0 1 0 0 2 0 1 0 5 - - 10 3%
SUB GANGGUAN AKIBAT E2 14 4 17 8 13 6 3 8 6 16 - - 95
32 EXTERNAL 41b E3.BINATANG BINATANG ( TOKEK ,ULAR ) DLL 11 1 5 3 8 8 3 5 9 6 - - 59 18%
33 EXTERNAL 52 E3.BINATANG GANGGUAN SKTM KARENA PENGGALIAN PDAM DLL 0 0 0 0 1 0 0 0 0 0 - - 1 0%
SUB GANGGUAN AKIBAT E3 11 1 5 3 9 8 3 5 9 6 - - 60
35 EXTERNAL 41d E4.PIHAK LAIN LAYANG-LAYANG ( BALIHO DLL ) 1 4 3 1 0 1 1 4 4 1 - - 20 6%
SUB GANGGUAN AKIBAT E4 1 4 3 1 0 1 1 4 4 1 - - 20
TOTAL PENYEBAB GANGGUAN 42 25 41 29 36 31 15 28 32 41 - - 320 100%
Realisasi Recloser Trip 2015 VS
2016 Prediksi
Penyebab Gangguan Recloser 2016
GANGGUAN 2015 GANGGUAN 2016 RECLOSER TRIP 2016
4% 5%
KODE JUMLAH % KODE JUMLAH %
I1 57 12 % I1 111 18 % 18% 4%
26% 0%
I2 19 4% I2 26 4% 0%
I3 6 1% I3 0 0%
I4 1 0% I4 3 0% 43%
E1 206 44 % E1 264 43 %
E2 100 21 % E2 159 26 %
E3 29 6% E3 22 4%
E4 55 12 % E4 30 5%
TOTAL 473 100 % TOTAL 615 100 % I1 I2 I3 I4 E1 E2 E3 E4

2016
No Faktor KODE Klasifikasi Penyebab TAHUN PERSEN
JAN FEB MAR APR MEI JUN JUL AGU SEP OKT NOV DES
1 INTERNAL 44b I1.KOMPONEN JUMPER SUTM RUSAK 3 1 0 0 1 0 3 0 1 0 0 0 9 1%
2 INTERNAL 44a I1.KOMPONEN SUTM PUTUS 0 0 1 0 0 0 0 0 0 0 0 0 1 0%
6 INTERNAL 41d-3 I1.KOMPONEN FCO PUTUS TIDAK DIKETAHUI PENYEBABNYA 9 13 8 12 14 7 4 5 8 11 0 0 91 15%
7 INTERNAL 41d-4 I1.KOMPONEN KAWAT JTM TERURAI 5 0 1 2 0 0 0 0 0 2 0 0 10 2%
SUB GANGGUAN AKIBAT I1 17 14 10 14 15 7 7 5 9 13 0 0 111
10 INTERNAL 45 I2.PERALATAN ISOLATOR RUSAK 2 1 0 3 0 2 2 2 0 1 0 0 13 2%
11 INTERNAL 47 I2.PERALATAN POLE SWITCH RUSAK ( ABSW,DS LOSS CONTACT ) 0 1 0 0 1 2 1 0 0 2 0 0 7 1%
12 INTERNAL 46 I2.PERALATAN CUT OUT RUSAK 0 0 0 0 0 1 1 1 0 0 0 0 3 0%
13 INTERNAL 48 I2.PERALATAN LIGTHNING ARRESTER RUSAK 1 0 0 0 1 0 1 0 0 0 0 0 3 0%
SUB GANGGUAN AKIBAT I2 3 2 0 3 2 5 5 3 0 3 0 0 26
18 INTERNAL 35 I4.TIANG TIANG LISTRIK ROBOH DILANGGAR KENDARAAN 0 0 1 0 0 0 0 0 1 0 0 0 2 0%
20 INTERNAL 38 I4.TIANG KERUSAKAN PADA TIANG KECUALI ( ISOLATOR & PENGHANTAR ) 0 0 0 0 1 0 0 0 0 0 0 0 1 0%
SUB GANGGUAN AKIBAT I4 0 0 1 0 1 0 0 0 1 0 0 0 3
22 EXTERNAL 41a E1.POHON & LAIN-LAIN GANGGUAN POHON 18 12 20 25 31 25 23 22 28 43 0 0 247 40%
23 EXTERNAL 49 E1.POHON & LAIN-LAIN GANGGUAN TIDAK DITEMUKAN 4 4 9 0 0 0 0 0 0 0 0 0 17 3%
SUB GANGGUAN AKIBAT E1 22 16 29 25 31 25 23 22 28 43 0 0 264
24 EXTERNAL 41c E2.ALAM PETIR 18 7 12 20 11 8 3 1 9 15 0 0 104 17%
25 EXTERNAL 81 E2.ALAM ANGIN KENCANG (PUTING BELIUNG ) 4 1 2 1 4 0 4 3 1 0 0 0 20 3%
26 EXTERNAL 82 E2.ALAM HUFEB LEBAT 2 3 2 1 1 7 3 1 3 12 0 0 35 6%
SUB GANGGUAN AKIBAT E2 24 11 16 22 16 15 10 5 13 27 0 0 159
32 EXTERNAL 41b E3.BINATANG BINATANG ( TOKEK ,ULAR ) DLL 5 1 0 3 3 2 1 3 1 3 0 0 22 4%
SUB GANGGUAN AKIBAT E3 5 1 0 3 3 2 1 3 1 3 0 0 22
35 EXTERNAL 41d E4.PIHAK LAIN LAYANG-LAYANG ( BALIHO DLL ) 1 2 2 1 6 2 3 6 3 4 0 0 30 5%
SUB GANGGUAN AKIBAT E4 1 2 2 1 6 2 3 6 3 4 0 0 30
TOTAL PENYEBAB GANGGUAN 72 46 58 68 74 56 49 44 55 93 0 0 615 100%
Realisasi Pemeliharaan
TARGET 2016 REAL
NO ITEM REAL JULI TOTAL
AGUSTUS
2016 SMT II
Volume 2016
Satuan
KEANDALAN JTM Sem 2
1 Inspeksi Jaringan Kms 6.351 2.428 2.628 5.056
2 Rabas - Rabas / potong pohon Pohon - 140 366 505
3 Normalisasi Konstruksi - - -
A. KONDUKTOR - - -
- Perbaikan Termination Kabel TM 20 kV Titik 5 - - -
- Perbaikan Konduktor yang Terurai Buah - 3 1 4
- Pengencangan Konduktor Gawang - 25 25 50
- Rekonduktor A3C 70 menjadi A3CS 70 Kms - 9 9 18
- Rekonduktor A3C 240 menjadi A3CS 240 Kms - - 1 1
- Rekonektoring JTM Buah 551 26 48 74

B. KOMPONEN/PERALATAN
- Penggantian Isolator Tumpu Buah - 18 20 38
- Penggantian/Pemasangan Cut Out Polymer 24 kV Buah - 4 7 11
- Penggantian Cross Arm Buah - 9 9 18
- Pemasangan LBS Motorized Buah 3 1 1 2
- Pemeliharaan ABSW Buah 60 1 4 5

C. TIANG
- Penegakan Tiang Miring/Roboh buah - 13 17 30
KEANDALAN TRAFO 306 306
1 Inspeksi dan Pengukuran Gardu 8.127 - 18 18
2 Penyeimbangan beban Trafo Gardu 51 - - -
3 Manajemen Trafo (Spoor, Revolving, Uprating, Sisip Trafo) Unit - 6 6 12
6 Normalisasi Konstruksi - -
- Perbaikan Arde Buah 171 1 1 2
JTR &SR
8 PerbaikanPengencangan Konduktor A3C/BC/LVTC gawang - 5 5 10
10 Perbaikan Schoor buah - 14 14 28
13 Perbaikan/Penggantian Assembly 50-70 mm2 buah - 5 5 10
18 Ganti SR lapuk Plg - 2 2 4
Rencana Aksi
• potong pohon dan row
• maksimalkan
PREDIKSI
BULAN BULAN
I1 E1
SEP OKT NOV DES SEP OKT NOV DES
2014 1 5 2 7 2014 8 3 2 14
2015 1 1 9 8 2015 2 3 10 12
PREDIKSI I1 2016 1 3 6 8 PREDIKSI E1 2016 5 3 6 13

BULAN BULAN
I2 E2
SEP OKT NOV DES SEP OKT NOV DES
2014 1 3 1 0 2014 1 1 16 8
2015 3 0 3 6 2015 0 1 8 12
PREDIKSI I2 2016 2 2 2 3 PREDIKSI E2 2016 1 1 12 10

BULAN BULAN
I3 E3
SEP OKT NOV DES SEP OKT NOV DES
2014 0 0 0 0 2014 0 3 3 1
2015 0 0 0 0 2015 3 1 7 6
PREDIKSI I3 2016 0 0 0 0 PREDIKSI E3 2016 2 2 5 4

BULAN BULAN
I4 E4
SEP OKT NOV DES SEP OKT NOV DES
2014 0 0 0 0 2014 2 2 2 0
2015 0 0 0 0 2015 6 3 6 2
PREDIKSI I4 2016 0 0 0 0 PREDIKSI E4 2016 4 3 4 1
WORKPLAN

2016
SEPTEMBER OKTOBER NOVEMBER DESEMBER
NO RENCANA AKSI 2016 SATUAN TOTAL KET
CLP MJG GBG KBM KRY SDJ CLP MJG GBG KBM KRY SDJ CLP MJG GBG KBM KRY SDJ CLP MJG GBG KBM KRY SDJ
MJG01,MJG02,MJG03,MJG05,LMS02,LMS03,LMS06,
LMS07,MJG06,MJG05,MJG02,LMS02,KSG03,KBM03,
1 Potong Pohon Pohon 80 80 80 150 80 80 190 260 271 606 262 260 210 265 260 527 270 265 173 200 213 400 256 220 5658
KBM06,WLD04,WLD03,WDL02,GBG05,GBG10,GBG0
2
2 Proteksi Petir
TERSEDIA DI AREA 216
- Pemasangan Arrester Titik 60 58 28 30 40 216 KEBUTUHAN ARRESTER = 240 +360 = 600
KSG01,SNT01,SNT02,GBG07,MJG06
Pemasangan Grounding gas
- Titik 36 50 30 30 60 34 240 KSG1,SNT1,SNT2,GBG7,LMS3,LMS7,SNT4,MJG3
pipe 1,5' x 6 mtr

Pemasangan groundrood MJG3,GBG1,KSG2,KBM6,KBM4,SNT5,SNT6,LMS6,


- Titik 30 30 30 30 60 60 30 30 30 30 360
cooper weld 16mm x 3 mtr MJG6,GBG4,MJG4,KBM1