• Communication
•Control Centre
2
RTU 560 A Basic rack: contains CMU cards where
in all collected real time data is
transmitted to Control Centre through
communication
Extension Rack-1: contains DI
Basic Rack
cards, AI cards and AO card
Extension Rack-2: contains DO cards
EX.rack-1 Annunciation: Shows Feeder
operation status when operated
through SCADA
EX.rack-2
AC/DC converter: Converts 230VAC
to 48VDC
MIC- Meter Interface Card
MIC Annunciation
4 MCB’s ;
48V DC
AC/DC
converters DI- Digital input
DO-Digital output
MCB’s CHR-
UNIT INTERCONNECTIVITY
CMU card
Constant
constant Blinking
ERR flickering
Inform for constant ERR indication
A:Blink
L:Constant
IF (Inter Face )panel
CT connector
DO
Digital Control:
Wired for breakers remote operation
For Feeders it is wired for respective
TNC’s in C&R panel
TNC TC
Switch
CC
Opto coupler:
It is having either 220 or 110V DC for Field input and
48V DC at RTU side
It isolates Input and output voltage
R
From To DI
potential cards of
indication RTU.
point.
SCADA OPERATION & INDICATION to DO OPERATION
To RTU
D+ D-
MIC
RS485
Tx-
Tx+
05/19/18 10
MIC
SUBSTATION AUTOMATION SYSTEM
SAS(Substation Automation System)
Components of SAS:
IED( Like BCU’s, Relay etc)
HMI(Human Machine Inference)
GPS Reciever(Global Positioning System)
FO patch cables (Fiber optic )
SWITCHES for connecting all IED’s with HMI
Software for monitoring and Control of all the
Bays
PROTOCOLS
MODBUS
IEC-103
IEC-61850
IEC-104
G
P
S
IEC-61850
Fiber optic Cables Fiber optic Cables
BCU’s
KPTCL 25 AUG
Substation Automation System for EHV Application
Bay IEDs in Switchyard
ADVANTAGES OF SAS
Realtime information available for
monitoring and Control at Station Level.
Uses
less monitoring interference for the
Measurand and status.
Time Synch of all IED’s.
Alarmand events for any signal can be
configured.