Вы находитесь на странице: 1из 6

Service Port use

Service Port use : Service Port Location


Service Port use : Operational Check

EFM
Valve chamber
Evaporator

EEV
Reheat coil (option)

EMV Economizer

PRV ESV
HSV RSV

CFM
LPT Drier

DMV
HPT Condenser LSV
1 HPS
Receiver

Sight glass

Compressor

2
Service Port use : Refrigerant recovery

EFM Valve chamber


Evaporator

EEV
Reheat coil (option)

EMV
Economizer
PRV ESV
HSV RSV

CFM
LPT ④

HPT DMV Condenser LSV Drier


1 HPS
Receiver

4 Sight glass

Compressor

Red location is refrigerant


location after Auto Pump
Down

Recovery machine
Service Port use : System Evacuation

EFM
Valve chamber
Evaporator

EEV
Reheat coil (option)

EMV
Economizer
PRV ESV
HSV RSV

CFM
LPT ④
DMV
1 HPT Condenser
Receiver
LSV Drier
HPS

Sight glass

Compressor
4

Vacuum pump
Service Port use : Refrigerant Charge
EFM
Valve chamber
Evaporator

! CAUTION
Reheat coil (option)
EEV

Do not charging liquid refrigerant from port ①.


EMV
That causes malfunction of the compressor! Economizer
PRV ESV
HSV RSV

CFM
LPT ④
1 HPT DMV Condenser LSV Drier
HPS Receiver

Sight glass

Compressor
4

Step 1: After evacuating the system, charge liquid refrigerant through Service port ④

Step 2: If the total charge cannot be completed in Step 1, operate the unit & add
remaining vapor gas through Service Port ①