Академический Документы
Профессиональный Документы
Культура Документы
2
Contents
Purpose of Line Sizing
Common Sizing Criteria
Liquid Phase Line Sizing
Gas Phase Line Sizing
Two Phase Line Sizing
3
PURPOSE OF LINE SIZING
4
COMMON SIZING CRITERIA
• Liquid Line
Min velocity 3 ft/s Sand deposition & other solids
Max velocity 15 ft/s Minimize flashing ahead of control valves
• Gas Line
Max velocity 60 ft/s Noise problem
• 2 Phase Line
Min velocity 10 ft/s Minimize slugging
5
Liquid Line Sizing
6
• CALCULATE REYNOLD NUMBER
7
• DEFINE MOODY FRICTION FACTOR, f
Re < 2000 Re > 4000
8
• CALCULATE PRESSURE DROP/100 FT (Fanning)
9
• CALCULATE TOTAL PRESSURE DROP
(total DP = DP/100 ft x pipe length)
• CALCULATE OUTLET PRESSURE
(Outlet P = Inlet P + static P - Total DP)
• SELECT LINE SIZE THAT MEET DESIGN CRITERIA
10
Gas Phase Line Sizing
11
• CALCULATE VELOCITY,Vg
12
• CALCULATE REYNOLD NUMBER
13
• DEFINE MOODY FRICTION FACTOR, f
Re < 2000 Re > 4000
14
• CALCULATE PRESSURE DROP/100 FT
15
• CALCULATE STATIC PRESSURE DUE TO ELEVATION CHANGE
16
Two Phase Line Sizing
17
• CALCULATE ERROSIONAL VELOCITY (MAX VELOCITY), Ve
Service C
Continuous 100
Intermittent 125
18
• CALCULATE MINIMUM PIPE CROSS SECTION AREA, A
If f=0.015
20
• CALCULATE STATIC PRESSURE DUE TO ELEVATION CHANGE
21
22