Introduction
This Practice provides
requirements for cast-in-place
concrete construction.
Purpose
This Practice describes the
technical requirements for
furnishing and installing materials
and for proportioning, mixing,
placing, testing, and curing of plain
and reinforced concrete.
Scope
References
American Concrete Institute (ACI)
– ACI 117- Standard Specifications for Tolerances for Concrete Construction and Materials
– ACI 211.1- Standard Practice for Selecting Proportions for Normal, Heavyweight, and Mass Concrete
– ACI 301.05- Specifications for Structural Concrete
– ACI 302.1R- Guide for Concrete Floor and Slab Construction
– ACI 304R- Guide for Measuring, Mixing, Transporting, and Placing Concrete
– ACI 304.2R- Placing Concrete by Pumping Methods
– ACI 306.1- Standard Specification for Cold Weather Concreting
– ACI 308R- Guide to Curing Concrete
Cementitious Materials
• Portland cement shall be in accordance with ASTM
C150, Type I or Type II.
Admixtures
• All admixtures, except air entrainment admixtures, shall
require the engineer of record’s authorization for use.
• Only one manufacturer for each admixture shall be
used.
• Calcium chloride and admixtures containing soluble
Add Text
chlorides shall not be permitted.
Simple
PowerPoint
Presentation Aggregate
• Aggregate shall be obtained from a single source.
Reinforcement
• Reinforcing bars shall be deformed billet steel in
accordance with ASTM A615/A615M, grade 60.
Add Text • All reinforcing shall be uncoated.
Simple • Welded wire fabric shall be plain wire fabric.
PowerPoint • Tie wire shall be black annealed wire, 16 gage
Presentation
minimum.
Water
• Water used for mixing water, ice, curing, or any other
function relating to placement of concrete shall be
potable.
• Wash water from mixer washout operations shall not be
used as mixing water.
Add Text
Simple
PowerPoint
Presentation
Execution
Storage, handling, measuring, mixing,
transporting, and placing of concrete
materials shall follow the methods and
General means outlined in ACI 304R and comply
with manufacturer’s recommendation for
handling, storage, and protection.
• 3/4-inch (20-millimeter) chamfer strips shall be
provided at all corners on permanently
exposed surfaces
01 02
Center of bolt group + or – 1/4 inch (6 mm)
Center to center of any two + or – 1/8 inch (3 mm)
S
anchor bolts within a bolt group
W
Center to center between bolt + or – 1/4 inch (6 mm)
groups
Anchor bolt plumbness 1/8 inch in 3 feet (4 mm in 1 meter)
O
Plate insert horizontal and vertical
location
T
+ or – 1/4 inch (6 mm) horizontal and
+ or – 1/32 inch (1 mm) vertical
03 04
Proportioning and Mixing
Slabs and walls less than 8 inches thick 3/4 inch (20 mm)
01 02
Lightweight concrete 3/4 inch (20mm)
S
Underground pipe or electrical encasements W 3/4 inch (20 mm)
O
Fireproofing or structural steel encasements
T 3/8 inch (10 mm)