Академический Документы
Профессиональный Документы
Культура Документы
P R E S S U R I Z AT I O N – A N O V E R V I E W
COPYRIGHT © 1976-2015 BUROHAPPOLD ENGINEERING. ALL RIGHTS RESERVED 17th February 2015
Introduction/Objectives
1.) Provide an overview of stairwell and elevator hoist
way pressurization system design and
implementation.
- Smoke containment vs. smoke management
- Evolution of pressurization systems in New York City
(Codes and Standards – ASHRAE, IBC & NFPA)
- Design fundamentals
- Calculation procedures
- Building equipment and controls
- Documentation for submission to DOB and AHJ
- Testing
2.) Encourage technical discussions to develop
design standards for BHNY MEP & FP design teams
in regards to life safety systems.
Number of large loss fires occurred where smoke was deemed a major contributing
factor.
Need to provide occupants a smoke-free escape route in the event of a building fire.
Need to provide a smoke-free staging area for first responders.
And, most importantly, it is required by building codes for certain types of buildings.
And, most importantly, it is required by building codes for certain types of buildings.
Notes:
AS – Sprinklered,
NS – Non-Sprinklered.
Number of open doors
determined by Engineer and
is based on stack effect,
buoyancy, etc.
Series of systems defined by NFPA 92 – Standard for Smoke Control Systems (Annex F)
Injection Type
• Single-Injection System
• Multiple-Injection System
Compensation Type
• Non-compensated
• Compensated
• Modulated supply airflow
• Overpressure relief
• Barometric relief dampers
• Supply fan bypass
Advantages:
• Propeller fans have quick response to
airflow changes.
• Propeller fans have lower installation costs
than other types of fans.
Disadvantages:
• Propeller fans are highly susceptible to
wind pressures (centrifugal fans are
recommended).
• Smoke can enter stairwell through
pressurization fan intake.
• High likelihood for failure if a few doors
are open near air supply injection point.
• Risk for failure increases in bottom-
injection systems when ground floor
stairwell door is open.
Duct can be located in stairwell instead of separate shaft. Inappropriate for densely occupied
buildings where total building evacuation
Pressurization fan intake required to be separated from all by stairwell is planned in event of fire.
building exhausts, outlets from shafts, vents, etc.
Barometric Dampers
• Simplest, least expensive method
• Use adjustable counterweights
• Prone to “chatter” and
weather infiltration
• Should not be placed
close to supply openings.
Motorized Dampers
Stairwell Pressurization
Elevator Pressurization
• Drawbacks
• Limited use
• Not intended to be accurate and reliable for every situation.
• OK for Schematic Design and Design Development only.
• Does not prove to NYC DOB & AHJ’s (e.g. FDNY) that smoke control system has been properly engineered.
• Does not account for construction features (e.g. leakage, dimensions, etc.) of stairwell
. and elevator hoist way.
To account for a number of interior or exterior open doors, calculate flow/leakage areas (walls, closed & open
doors) and use Equation (2) to determine ∆pstack – “Pressure Difference due to Stack Effect.”
Add ∆pstack to “Minimum Design Pressure in Stair” (0.10 in. w.g. – 2009 IBC) to determine ∆pdesign -“Design
Pressure Difference across Flow Path.”
Then, calculate Volumetric Flow Rate (Q) using the following equation:
Since C ranges between 0.60 and 0.70 (use C = 0.65) and ρair = 0.075 lb/ft3, Equation (4) becomes:
5.2 (W A) P
(6) F Fr
2 (W d )
F= Total door-opening force (lb.)
Fr = Force required to overcome door closer & other friction (lb.)
W= Door width (ft.)
A= Door area (ft2)
∆P = Pressure difference across door (in. w.g.)
d= Distance from door knob to knob side of door (ft.)
Figure A.4.4.2.2 – NFPA 92 – 2012 Edition • Solving Equation (6) for ∆P…
2 (W d ) ( F Fr )
(7) P
5.2 (W A)
• Barometric relief dampers should be set to open at ∆P calculated from Equation (7) to prevent over-
pressurization of stairwell and allow doors to be opened.
Flow Area Between Building & Outside: Abo = 6,030 ft2 x 0.21 x 10-3 = 1.27 ft2
Flow Area Between Stairwell & Building: Asb = 0.26 ft2 + 0.06 ft2 = 0.32 ft2
1 sb
Abo
B = 0.00170 in. of water/ft.
∆𝑝𝑠𝑏𝑡 = 0.425 in. w.g. (This is good; ∆psbt should not exceed maximum design pressure in stairwell)
3 3ൗ
0.425 ൗ2 − 0.080 2
𝑄 = 8,200 cfm
𝑄 = 1740 × 20 × 0.32 × [ ]
0.425 − 0.080
Stairwell Pressurization
Stairwell Pressurization
• Single-Injection Systems: Propeller fan (NFPA 92 – 4.6.3.1).
• Multiple-Injection Systems: Centrifugal or inline axial fan (NFPA 92 – 4.6.3.2).
Systems to be provided with two (2) sources of power (2009 IBC – 909.11 Power Systems)
• Primary Power: From normal building power system.
• Stand-by Power: From emergency & stand-by power system complying with Section 2702.1 & NFPA 70 (National Electrical Code).
• Stand-by power equipment to be separated from normal power equipment in minimum 1-hour fire-rated enclosure.
• Transfer between primary power & stand-by power must be automatic.
• Transition to occur within 60 seconds of primary power failure.
All junction boxes, pull boxes, and termination points must be identified as pertaining to smoke control system
(2009 IBC – 909.14 Marking and Identification).
Fire alarm system supplying control input or output signals to smoke control system must have control unit that
complies with U.L.-864 (2009 IBC – 909.12 Detection and Control Systems).
Stairwell Pressurization
• Automatic Activation – Operation of any zone of the fire alarm system must cause all stairwell pressurization fans to start, unless an
engineering analysis determines that activation of all fans is not necessary (NFPA 92 – 6.4.6.1).
• Smoke Detection – A smoke detector must be provided in the stair pressurization supply ductwork, and if it senses smoke it must
shut down the stairwell pressurization fan (NFPA 92 – 6.4.6.2).
• Manual Pull Stations – If the system response is identical for all fire alarm zones, then activation via manual pull station is permitted
(NFPA 92 – 6.4.6.3).
Detailed Design
Operations and
Report (Rational
Maintenance Manual
Analysis)
• Stairwell Pressurization
• Measure pressure differentials across smoke barriers with all interior doors closed.
• Leave exterior door open if it would be open during evacuation.
• Then measure pressure differentials with number of egress doors open per design.
• Measure force to open egress doors with number of doors open per design.
• Elevator Hoist way Pressurization
• Pressure differential across each elevator door with all elevator doors closed shall be
measured and recorded.
• If elevator door(s) on the recall floor would normally be open during system pressurization, it
shall be open during testing too.
• Input/output functions
• Emergency/stand-by power
• Dedicated systems (do not function under normal building operation) – Semi-annual testing
• Non-dedicated systems – Annual testing
• NFPA 90A (Standard for Installation of Air-Conditioning & Ventilating Equipment) contains
additional information on operation and maintenance.
Understand how the systems work and how to design them properly since you
need to prove it to the DOB and AHJ’s.
• ASHRAE, IBC & NFPA are comprehensive references.
It’s good to oversize a life safety system to some extent, but don’t over do it…