P. R. Dhamangaonkar
Factor Information
Jc correction factor for baffle configuration (baffle cut and
spacing). Its value is 1.0 for an exchanger with no tubes in the
windows and increases to 1.15 for small baffle cuts and
decreases to 0.65 for large baffle cuts.
For a typical well-designed heat exchanger, its value is near 1.0.
Jl correction factor for baffle leakage effects, including both tube-
to-baffle and baffle to-shell leakages. It is a function of the ratio
of the total leakage area per baffle to the cross-flow area
between adjacent baffles, and also of the ratio of the shell-to-
baffle leakage area to tube-to-baffle leakage area.
A typical value of Jl is in the range 0.7 to 0.8
The combined effect of pressure drop corrections reduces the ideal total shell-side
pressure drop to 20 to 30% of the pressure drop that would be calculated for flow
through the corresponding exchanger without baffle leakages and bundle bypass