• Presented By:
• Existing buildings
Occupant Notification
In every building where fire itself could not provide adequate occupant warning, fire
alarm systems shall be provided where necessary to warn occupants of the existence
of fire.
System Design/Installation:
Any fire protection system or safeguard provided to achieve the goals of these
Provisions shall be designed, installed, and approved in accordance with applicable
codes and Standards.
Fire Certificate
The owner shall obtain fire certificate from AHJ after every three years.
General Fire Safety Provisions for
Construction
Every new and existing building or structure shall be constructed, arranged, equipped,
maintained, and operated in accordance with these Provisions so as to provide a
reasonable level of life safety, property protection, and public welfare from the actual
and potential hazards created by fire.
Owner/Occupant Responsibilities
• Comply with the Provisions
• Provide tests or test reports as proof of compliance
• Notifying AHJ prior to a change of occupancy
• Should take Corrective action
• Shall keep records of all maintenance, inspections, and testing of fire
protection systems in both hard and soft copies at different locations.
•
Occupancy:
Buildings or portions of buildings, except for routine maintenance or
repair, shall not be occupied during construction, repair, or alteration
without the approval of Authority.
Building Evacuation:
Persons shall be able to leave building when a fire alarm system is
activated as per approved building fire evacuation plan.
Fire Drills:
Drills shall be designed in cooperation with the local authorities and shall
be held at expected and unexpected times and under varying conditions
to simulate the unusual conditions.
Reporting of Fires:
The person discovering any unwanted fire, regardless of
magnitude, shall immediately notify the fire department,
as well as owner, manager and occupant.
Outside Storage:
Outside storage of combustible materials shall not be located
within 10 ft (3 m) of a property line.
Fire Zones based on Fire hazards
The city or area under the jurisdiction of AHJ shall be demarcated into distinct
zones, based on fire hazard inherent in the buildings and structures according to
occupancy, which shall be called as ‘Fire Zones’.
There have the following categories
Fire Zone No. 1. (Low Hazard Area) This shall comprise areas having assembly,
educational, health care, day care, residential, detention and correctional, and
mercantile buildings, or areas which are under development for such occupancies.
Fire Zone No. 2. (Medium Hazard Area) This shall comprise of business and
industrial buildings, except high hazard industrial buildings or areas which are
under development for such occupancies.
Fire Zone No. 3. (High Hazard Area) This shall comprise areas having high hazard
industrial buildings, storage buildings and buildings for hazardous use or areas
which are under development for such occupancies.
Classification on the basis of
Occupancy
Single Occupancy Buildings: A building or structure in which only one
class of occupancy exist. i.e. Educational, Health, Residential etc.
Waste Disposal
Accumulations of combustible waste material, dust, and debris shall be
removed from the structure and its immediate vicinity daily or more
frequently as necessary for safe operations.
Materials susceptible to spontaneous ignition, such as oily rags, shall be
stored in a listed/approved disposal container.
Trash chutes used on the exterior of a building shall be of noncombustible
construction, or protected in accordance with standards
Temporary Heating Equipment
Temporary heating equipment shall be listed/approved.
Temporary heating equipment shall be installed, used, and
maintained in accordance with manufacturer’ instruction
Only personnel familiar with the operation of the temporary heating
equipment shall be allowed to operate such devices.
Temporary heating equipment, where utilized, shall be monitored
for safe operation and maintained by properly trained personnel.
Refueling operations shall be conducted in an approved manner.
Temporary Separation Walls
Protection shall be provided to separate an occupied portion of the
structure from a portion of the structure undergoing alteration,
construction, or demolition operations when such operations are
considered as having a higher level of hazard than the occupied
portion of the building.
Walls shall have at least a 1-hour fire resistance rating.
Opening protective shall have at least a 45-minute fire protection
rating.
Scaffolding, Shoring, and Forms
Accumulations of unnecessary combustible
wood/lumber shall be prohibited.
It shall be brought into the structure only when needed
and removed from the structure as soon as stripping is
complete.
Those portions of the structure where combustible
wood/lumber is present shall not be used for the storage
of other combustible building materials
Asbestos Removal
Approved signs shall be posted at the entrance exit and exit
access door, decontamination areas, and waste disposal
areas for asbestos removal operations.
The signs shall state that asbestos is being removed from
the area and that proper respiratory protection is required.
Signs shall have a reflective surface, and lettering shall be a
minimum of 2 in. (51mm) high.
Fire Safety during Construction
A water supply for fire protection, either temporary or permanent, shall be
made available as soon as combustible material accumulates.
There shall be no delay in the installation of fire protection equipment.
Where underground water mains and hydrants are to be provided, they shall
be installed, completed, and in service prior to commencing construction
work on any structure.
In buildings under construction, a standpipe system, either temporary or
permanent in nature, shall be installed in accordance with standards
Standpipes, hose and nozzles shall be provided and made ready for use as
soon as the water supply is available
In combined systems where occupant hose is not required, temporary hose
and nozzles shall be provided during construction.
The standpipes shall be provided marked and readily accessible for fire
department connections on the outside of the building at the street level and
shall have at least one standard hose outlet at each floor.
The standpipes shall be securely supported and restrained at each alternate
floor.
At least one approved hose valve for attaching fire department hose shall be
provided at each intermediate landing or floor level in the exit stairway.
Temporary standpipes shall remain in service until the permanent standpipe
installation is complete.
Fire safety during alteration of buildings
Where the building is protected by fire protection systems, such
systems shall be maintained operational at all times during
alteration.
Where alteration requires modification of a portion of the fire
protection system, the remainder of the system shall be kept in
service and the fire department shall be notified
Fire-resistive assemblies and construction shall be maintained.
• Impediments to Egress: Any device or alarm installed to restrict the improper use
of a means of egress shall be designed and installed so that it cannot, even in case
of failure, impede or prevent emergency use of such means of egress.
Elevator Landing and Lobby Exit Access: Each elevator landing and lobby shall have access to at
least one exit and should not require special key/knowledge or special effort.
Exit Passageways: 8ft width and ventilation is necessary for exit pathways.
• Capacity of Means of Egress: The total load bearing capacity of
the means of egress for any story, balcony, tier, or other occupied
space shall be sufficient for the occupant load using that means.
• External Stairs: Shall be provided for high rise buildings, always be kept
in sound operable conditions. All external stairs shall be directly
connected to the ground and shall have remote entrance than Internal
Stairs.
• Fire Tower: Fire towers are the preferred type of escape route for
storied buildings and these shall be considered as the safest route
for escape. Their number, location and size shall depend on the
building concerned, and its associated escape routes. In high rise
buildings with over 30 m (100 ft) in height, at least one required
means of egress shall be a fire tower.
• Ramps:
The slope of a ramp shall not exceed 1 in 10. For all slopes exceeding 1 in
10 and wherever the use is such as to involve danger of slipping, the ramp
shall be surfaced with approved non-slipping material.
• Fire Lifts: Fire lifts shall be provided with a minimum capacity for 8
passengers and fully automated with emergency switch on ground level.
Buildings 30 m (100 ft) in height or above shall be provided with fire
lifts. In case of fire, only fireman shall operate the fire lift.
Building Services
Services are:
• Electric Supply
• Air conditioning and ventilation
• Gas Supply
• Elevators/Escalators
• Generators
Building Services
Electrical Fire Safety:
– Permanent wiring must be insulated properly
– Hidden and secured contact from all accessible areas : ducts are used
– Prescribed cords must be used to avoid overheating and so fire
– Extension cords shall not be used as a substitute for permanent wiring.
– All panel board and switchboards, pull boxes, junction boxes, switches,
and conduit bodies shall be provided with covers compatible with the
box or conduit and suitable for the conditions of use.
• Utilities: Above ground gas meters, regulators, and piping exposed to vehicular damage shall be
protected.
• Heating Appliances: Portable generators shall be operated, refueled and maintained outside the
building or in a protected area.
• Stationary Generators and Standby Power Systems: Stationary generator sets shall be installed in
accordance with NFPA 37 and NFPA 70 or any approved code/standard while Portable generators
shall be operated, refueled and maintained outside the building or in a protected area.
• Smoke Venting: Smoke venting facilities for safe use of exits in windowless buildings, underground
structures therefore should be automated and maintained.
Building Services
• Emergency Command Center:
– The emergency command center shall be separated from the
remainder of the building by a fire barrier having a fire
resistance rating of not less than 1 hour.
– The emergency command center room shall be a minimum of
96 ft2 (8.9 m2) with a minimum dimension of 8 ft (2.4 m).
– Emergency command center will include the fire department
communication unit and schematic building plans indicating the
typical floor plan and detailing the building core means of
egress, fire protection systems, fire-fighting equipment, and fire
department access.
– Access and spacing requirements shall be required to provide
emergency access to the roof, provide pathways to specific
areas of the roof, provide for smoke ventilation opportunity
areas, and to provide emergency egress from the roof.
Fire Protective Systems
• General Guidelines:
– Permits to be checked by AHJ
– Owner responsible for testing
– Fire Inlets/Hydrants should be visible & without
Obstructions
– Fire Protection System shouldn’t be out of order
for more than four hours
• Stand Pipe System:
The design and installation of standpipe
systems shall be in accordance with NFPA-14
or any approved code/standard.
• Non-Listed/Non-approved
Fire Protection or
Suppression Devices and
Equipment:
It shall be unlawful to market,
sell, advertise, or distribute
any device or equipment as
suitable for fire protection or
fire suppression purposes
unless the device or
equipment is listed/approved
for such purpose by an
internationally recognized
testing laboratory.