The document summarizes the design of a series active power filter, including calculating the voltage, current, and VA ratings of the voltage source converter (VSC). It considers a three-phase 415V supply system with a 25kW nonlinear load. The design calculations include selecting the DC bus voltage and capacitance, rating the IGBTs in the VSC, choosing the turns ratio and rating of the injection transformer, and determining the value of the interfacing inductor. Equations are provided for each component design value.
The document summarizes the design of a series active power filter, including calculating the voltage, current, and VA ratings of the voltage source converter (VSC). It considers a three-phase 415V supply system with a 25kW nonlinear load. The design calculations include selecting the DC bus voltage and capacitance, rating the IGBTs in the VSC, choosing the turns ratio and rating of the injection transformer, and determining the value of the interfacing inductor. Equations are provided for each component design value.
The document summarizes the design of a series active power filter, including calculating the voltage, current, and VA ratings of the voltage source converter (VSC). It considers a three-phase 415V supply system with a 25kW nonlinear load. The design calculations include selecting the DC bus voltage and capacitance, rating the IGBTs in the VSC, choosing the turns ratio and rating of the injection transformer, and determining the value of the interfacing inductor. Equations are provided for each component design value.
Department of Electrical Engineering, COMSATS Institute of Information Technology, Abbotabad
Analysis and Design of Series Active Power Filters The analysis and design of the series active power filters include the detailed analysis for deriving the design equations for calculating the values of different components used in their circuit configurations there are a large number of topologies of the series active power filters; therefore, the design of a large number of circuit configurations is not practically possible to include here due to space constraints The design of a three-phase three-wire series active power filter includes the design of a VSC, interfacing inductors, and a ripple filter The design of the VSC includes the selection of the DC bus voltage level, the DC capacitance, and the rating of IGBTs
2 Department of Electrical Engineering, COMSATS Institute of Information Technology, Abbotabad
Design of a Series Active Power Filter for a Voltage-Fed Nonlinear Load A three-phase series active filter consists of a VSC with an AC series inductor, a coupling transformer, and a DC bus capacitor used in series with a three-phase AC supply feeding a nonlinear load having a three phase diode rectifier with a capacitive filter The series AF is used to reduce the harmonics in AC mains currents and to maintain almost UPF (unity power factor) at the AC mains The design of the series APF includes calculation of the voltage, current, and VA ratings of the VSC of the series AF, value of the AC inductor, value of the DC bus capacitor, and its DC voltage Figure 10.7 shows a schematic diagram of the series active filter connected to a system with a nonlinear rectifier load
3 Department of Electrical Engineering, COMSATS Institute of Information Technology, Abbotabad
Continued…
Figure. 10.7: System configuration of a three-phase series active filter
4 Department of Electrical Engineering, COMSATS Institute of Information Technology, Abbotabad
Continued… A three-phase 415 V (phase voltage Vph = 239.6 V) supply system with a 25 kW load is considered to illustrate the design of the series AF The series AF is connected in series with the supply system through an injection transformer (Tr) The capacitor (CDC) is connected at the DC bus of the VSC to act as a DC voltage source The DC bus capacitor is selected based on the transient energy requirement and the DC bus voltage is selected based on the injection voltage level The series AF acts as a harmonic isolator between the supply and the load It has a ripple filter to absorb current ripples generated by the VSC
5 Department of Electrical Engineering, COMSATS Institute of Information Technology, Abbotabad
Design of a VSC of a Series Active Power Filter The design of the series active power filter is based on the DC bus voltage of the three-phase rectifier load The series active power filter is operated for eliminating harmonics in the supply currents and hence it injects only harmonic voltages It is clear that the fundamental component of load voltage is the PCC voltage as the series AF injects the harmonic component of the load voltage For the series AF, the switching frequency (fs) of 20 kHz is used The DC link voltage of the VSC (VDC) is selected as 700 V and it has to be controlled within 5% range and the ripple current in the inductor is to be constrained to 5% of current flowing through the series APF
6 Department of Electrical Engineering, COMSATS Institute of Information Technology, Abbotabad
Continued… Hence, the fundamental component of load AC voltage is Equation 10 For a given line voltage of 415 V and a DC load voltage (Vd) of 540 V, the voltage rating of the series AF is obtained from the difference of PCC and load voltages and hence the SAF voltage is calculated as
7 Department of Electrical Engineering, COMSATS Institute of Information Technology, Abbotabad
Continued…
Equation 11
(Since the sine wave supply current after compensation results in
continuous conduction of diodes of the three-phase diode rectifier load (each diode conducting for 180°) and it results in a stepped waveform of the phase voltage at the input of the diode bridge with
8 Department of Electrical Engineering, COMSATS Institute of Information Technology, Abbotabad
Continued… (i) the first step of π/3 angle (from 0° to π/3) and a magnitude of Vd/3 (ii) the second step of π/3 angle (from π/3 to 2π/3) and a magnitude of 2Vd/3 and (iii) the third step of π/3 angle (from 2π/3 to π) and a magnitude of Vd/3 and it has both half cycles of symmetric segments of such steps) The voltage rating of the VSC is obtained as 75.6415 V
9 Department of Electrical Engineering, COMSATS Institute of Information Technology, Abbotabad
Continued… Design of Current Rating of a VSC of a Series Active Power Filter The current rating of the series APF depends on the fundamental component of load current and it is obtained as follows The load power is calculated as Equation 12 where R is the equivalent resistance of the DC load at the output of the diode bridge rectifier For a given load of 25 kW at 540 V DC bus voltage of the load, the equivalent resistance is R = 19.6 Ω Considering a UPF supply current and a lossless series AF, the rms supply current is calculated as
Equation 13
10 Department of Electrical Engineering, COMSATS Institute of Information Technology, Abbotabad
Continued… where P is the input power equal to 25 kW. Considering VLL = 415 V, the supply current is 34.78 A The current rating of the VSC is obtained as If = 34.78 A
Design of kVA Rating of a VSC of a Series Active Power Filter
Design of kVA Rating of a VSC of a Series Active Power Filter
Equation 14
Design of Rating of an Injection Transformer of a Series Active
Power Filter The injection transformer is designed considering the optimum voltage level of the VSC
11 Department of Electrical Engineering, COMSATS Institute of Information Technology, Abbotabad
Continued… The maximum AC voltage on the AC side of the VSC of the series APF may be maVDC/(2 √ 2) = 0.8 × 700/(2 × √ 2) = 197.99 V (considering the modulation index ma = 0.8) and on the supply side it must be Vsupply = Vf The turns ratio of the coupling transformer is
Equation 15
The kVA rating of the injection transformer is same as that of the
VSC and is calculated as Equation 16 Hence, the rating of the injection transformer is 7.892 kVA, 197.99 V/75.6415 V
12 Department of Electrical Engineering, COMSATS Institute of Information Technology, Abbotabad
Continued… Design of DC Capacitance of a VSC of a Series Active Power Filter The DC bus capacitance is selected based on the transient energy required during change in the loads Considering that the energy stored in the capacitor is for meeting the energy demand of the load for a fraction of power cycle, the relation can be expressed as Equation 17 where VDC is the rated voltage, VDC1 is the drop in DC bus voltage allowed during transients, Δt is the time for which support is required, and CDC is the DC bus capacitance Considering Δt = 0.1 ms, VDC = 700 V, and VDC1 = 700 - (5% of 700) = 665 V, Equation 10.17 results in Equation 18
13 Department of Electrical Engineering, COMSATS Institute of Information Technology, Abbotabad
Continued… It gives CDC = 3304 μF Hence, a DC bus capacitor of 4000 μF, 700V is selected for the series AF Design of an Interfacing Inductor for a VSC of a Series Active Power Filter The value of the interfacing inductor is selected based on the current ripple in the series AF Considering that ripple current in the inductor is 5% and overloading factor a = 1.2, the inductor is calculated as Equation 19
Substituting the values in Equation 10.18, the value of the interfacing
inductor is estimated as
14 Department of Electrical Engineering, COMSATS Institute of Information Technology, Abbotabad
Continued…
Hence, an interfacing inductor of 6.3 mH and 40 A current-carrying
capacity is selected for the series AF Design of a Ripple Filter The ripple filter is designed for eliminating the switching frequency ripples from the injected voltage of the series APF The ripple filter, a combination of a capacitor (Cf) and a resistor (Rf) connected in series, is generally tuned at half of the switching frequency (fr), which is calculated as Equation 20 Equation 21
15 Department of Electrical Engineering, COMSATS Institute of Information Technology, Abbotabad
Topology-Based Classification of DSTATCOMs Considering Rf = 5 Ω, Cf = 3.2 μF. Hence, Rf = 5 Ω and Cf= 5 μF are selected for designing a ripple filter. Similarly, the design of series active power filters may be carried out for other applications and other configurations.