Вы находитесь на странице: 1из 218

FIRE FIGHTING

INTRODUCTION (1st Edition)


Eng / Ali Hassan Mohamed
(fire fighting & plumbing design engineer)
• Fire Protection Major Goals:

A N
- Continuity of operation
SS
- Property protection
- Life safety
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• Fire Protection component:

A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• Fire Protection component:
Fire rated wall

A N
Fire detection & alarm system

SS
H A
Fire fighting system
L I Fire fighters

. A
N G
E
Fire Fighting Tech. For You
• FIRE TRIANGLE

A N
SS
*OXYGEN (14-16% at least to start combustion)

H A
L I
. A
N
FUEL G Heat 0C

E
Fire Fighting Tech. For You *Refer to NFPA 921-2001ed-sec 3.1.1.2
• FIRE TETRAHEDRON :

A N
SS
H A
L I

. A
G
The fire tetrahedron represents the addition of a component, the chemical
chain reaction, to the three already present in the fire triangle. Once a fire

N
has started, the resulting exothermic chain reaction sustains the fire and

E
allows it to continue until or unless at least one of the elements of the fire is
blocked.
Fire Fighting Tech. For You *Refer to NFPA 921-2001ed-sec 3.1.1.2
• Fire extinguishment methods :

A N
SS
H A
L I
. A
N G Why?

E
Fire Fighting Tech. For You
• Fire extinguishment methods cont. :

A N
S
 Why we use water as extinguishing agent:

1.
2.
cheap & available.
Large specific heat (Cp = 4.2 kJ/kg.K) .
A S
H
3. Large latent heat of vaporization (2257 KJ/kg) .

I
specific heat (Cp ) Latent heat of vaporization

L
The amount of thermal energy required The amount of thermal energy required

A
to raise unit mass of a substance by one to change unit mass of a substance

.
degree, and its units are kJ/kg·K from phase to another, and its units are
kJ/kg

N G
E
Fire Fighting Tech. For You
• Some definitions used in fire codes :
Item Definition

A N
S
UL Under writers laboratories.

S
FM Factory Mutual research.
Shall Indicates a mandatory requirement .
Should
A
Indicates a recommendation or that which is advised but not
required.

H
I
Approved Acceptable to the authority having jurisdiction.

L
Authority Having An organization , office, or individual responsible for enforcing the
Jurisdiction requirements of a code or standard, or for approving equipment,

A
(AHJ). materials, an installation, or a procedure.

G .
E N
Fire Fighting Tech. For You
• Some definitions used in fire codes :
 Common approvals :

A N
S
Factory Mutual research Under writers laboratories

American
A S
H
approvals

The Loss Prevention


L I Germany approval
Certification Board

. A
N G European
approvals

E
Fire Fighting Tech. For You
• Classifying Fires
Type of Fire
Fires that involve flammable solids such as wood, cloth, rubber, paper, and
A N
Australia European
*North
America

S
Class A Class A Class A
some types of plastics.

S
Fires that involve flammable liquids or liquefiable solids such as
Class B Class B
petrol/gasoline, oil, paint, some waxes & plastics, but not cooking fats or oils
Class B

A
Fires that involve flammable gases, such as natural gas, hydrogen, propane,
Class C Class C
butane

H
Fires that involve combustible metals, such as sodium, magnesium, and
Class D Class D Class D
potassium

I
(Class E)
Fires that involve any of the materials found in Class A and B fires, but with now no

L
the introduction of an electrical appliances, wiring, or other electrically longer in
Class E1 Class C
energized objects in the vicinity of the fire, with a resultant electrical shock the

A
risk if a conductive agent is used to control the fire. European

.
standards
Fires involving cooking fats and oils. The high temperature of the oils when on

G
fire far exceeds that of other flammable liquids making normal extinguishing Class F Class F Class K
agents ineffective.

E N
Fire Fighting Tech. For You *Refer to NFPA 10-2010ed-sec 5.2
• FIRE FIGHTING CODES :
1. AMERICAN CODES :

A N
S
CODE NO TITLE

S
NFPA 1 Uniform Fire Code
NFPA 10 Standard for Portable Fire Extinguishers
NFPA 11
NFPA 12

H A
Standard for Low-Medium-and High-Expansion Foam
Standard on Carbon Dioxide Extinguishing Systems

I
NFPA 13 Standard for the Installation of Sprinkler Systems

L
NFPA 14 Standard for the Installation of Standpipe and Hose Systems
NFPA 15 Standard for water spray fixed system for fire protection
NFPA 16

. AStandard Installation of foam-water sprinkler and foam-Water


spray system

G
NFPA 20 Standard for the Installation of Stationary Pumps for Fire
Protection
NFPA 24

E N Standard for the Installation of Private Fire Service Mains


and Their Appurtenances

Fire Fighting Tech. For You


• FIRE FIGHTING CODES cont. :
CODE NO TITLE

A N
S
NFPA 25 Standard for the Inspection, Testing, and Maintenance of
Water-Based Fire Protection Systems
NFPA 101
NFPA 220
Life Safety Code

A S
Standard on Types of Building Construction

H
NFPA 409 Standard on aircraft hangar
NFPA 418 Standard for helipad
NFPA 750
NFPA 2001

L I
Standard on Water Mist Fire Protection Systems
Standard on Clean Agent Fire Extinguishing Systems

2. BRITISH CODE :
. A
G
-Fire offices committee (FOC)
-British standard (BS)

E N
3. EGYPTIAN CODE: ‫ق‬
- ‫ىلللللحري‬
‫لللاكود لللامصر‬

Fire Fighting Tech. For You


A N
SS
FIRE FIGHTINGH
SYSTEMS
A
L I
. A
N G
E
Fire Fighting Tech. For You
• Course Contents:
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• Course objectives :
1) Good knowledge about fire fighting systems.
A N
S
2) Full design for water based systems.

S
a) Sprinklered system (dry –wet – preaction-deluge).
b) Water curtain system.
c) Foam systems.
d) Water spray systems.
e) Water mist systems.
H A
Advanced

f) Standpipe systems.
g) Fire hydrant.
L I
A
h) Monitors.

G .
3) Full design for gas based systems.
a) Clean agent system (inert gas-halocarbon).
b) CO2 system.

E N
c) Aerosol system.
4) Fire extinguishers.

Fire Fighting Tech. For You


• Course objectives cont. :
A N
5) Selection of proper fire protection system for different application.

6) How to use codes to get design data.

SS
H A
7) How to use calculation software (ELITE) for hydraulic calculation.

8) Full design (drawing & calculation) for project.

L I
. A
N G
E
Fire Fighting Tech. For You
A N
SS
1- WATER BASED
H SYTEMS A
L I
. A
N G
E
Fire Fighting Tech. For You
• MAIN SYSTEM COMPONENTS:
A) Reliable water source & pumps
A N
S
B) Piping network
C) Initiation and control equipment
D) Discharge devices
A S
I H
A L
G .
E N
Fire Fighting Tech. For You
• A) Reliable water source & pumps
Ground tank
A N
Elevated tanks (gravity tanks)

SS
H A
Rivers & lakes
L I Fire pumps

. A
N G
E
Fire Fighting Tech. For You
• B) PIPING NETWORK
Fire protection pipes
A N
Fire protection fittings

SS
H A
Hangers & supports

L I
. A
N G
E
Fire Fighting Tech. For You
• C) Initiation & Control Equipment
Valves in Pump Room.
A N
Alarm Check Valve

SS
H A
Pressure Switch

L I Flow switches

. A
N G
E
Fire Fighting Tech. For You
• C) Initiation & Control Equipment
Supervisory Switches
A N
Pressure Reducing Valves

SS
H A
Pressure Relief Valves
L I Control Panels

. A
N G
E
Fire Fighting Tech. For You
• D) DISCHARGE DEVICES
Sprinklers, Nozzles
A N
Hose valves, Hydrants

SS
H A
Monitors
L IFoam generator , Foam chambers

. A
N G
E
Fire Fighting Tech. For You
A N
SS
H SYTEMS
A. SPRINKLERED
A
L I
. A
N G
E
Fire Fighting Tech. For You
• *Classifying OCCUPANCIES
A N
A) Light hazard
SS
B) Ordinary hazard (group 1)
C) Ordinary hazard (group 2)
H A
D) Extra hazard (group 1)
E) Extra hazard (group 2)
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 5.1
A) LIGHT HAZARD
1) Animal shelters ‫ت‬(‫) ملجئ حيوانا‬
A N
S
2) Churches

S
3) Clubs
4) Educational
5)
6)
7)
Hospitals
Institutional
Kennels ‫ب‬
(‫للل‬
‫ت لل ك‬
H
‫) لللليبللو‬
A
8)
9) Museums
L I
Libraries , except large stack rooms

A
10) Nursing homes
11)
12)
13)
Offices
Residential

G .
Restaurant seating area
14)
15)
E NTheaters , excluding stages & prosceniums
Unused attics (‫تغير مستخدمة‬ ‫للللدرا‬
‫) للنس‬

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec A5.2


B) ORDINARY HAZARD (GROUP 1)
1) Automobile parking and showrooms
A N
S
2) Bakeries

S
3) Beverage manufacturing ‫ت‬
(‫)مصانع لللامشروبا‬
4) Canneries (‫)مصانع للللتعللبئة ط عام‬
5)
6)
Dairy products manufacturing & processing
Electronic plants ‫ت‬

H
(‫)مصانع لللاكترونيا‬ A (‫)مصانع للالللللبان‬

7)
8) Laundries
L I
Glass & glass products manufacturing

A
9) Restaurant service area (kitchens)

G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec A5.3
C) ORDINARY HAZARD (GROUP 2)
1) Agricultural facilities
A N
S
2) ‫ت‬
Barns & stables(‫للل سطبل‬
‫ت& ا‬ ‫) لللا شونا‬

S
3) Cereal mills ‫ب‬
(‫) مطاحن لللاحبو‬
4) Chemical plants
5) Confectionery products(
6) Distillers
‫ت‬‫)مصانع لللاحلويا‬
(‫) م عامللللاتقطير‬

H A
7)
8)
Dry cleaners
Exterior loading docks
L I ‫ل‬
(‫فللللتحللمي‬
‫) رصي‬

A
9) Feed mills ‫ف‬(‫)مصانع عل‬
10)
11)
12)
.
Leather goods manufacturing

G
Libraries – large stack room area
Machine shops
13)
14)
E N
Metal working
Paper & pulp mills

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec A5.3


C) ORDINARY HAZARD (GROUP 2) cont.
16) Paper process plants
A N
(‫)مصانع لللاورق‬

S
17) Plastic fabrication(‫للللل ستيك‬
‫ت ب‬ ‫)مصنع منتجا‬

S
18) Post offices
19) Printing & publishing
20) Racetrack stables / kennel area(
21) Repair garages
22) Resin application area(‫تاصمغية‬
‫ب‬

H A
‫للل حصنة & لللاكل‬

‫)مصانع لللامنتجاللل‬
‫تا‬
‫) اماكن لللاسباقا‬

23) Textile manufacturing


24) Tire manufacturing
L I (‫)مصانعلللانسيج‬

A
25) Tobacco products manufacturing ( ‫)مصانعلللاتبغ‬
26) Wood machining

G .
27) Wood products assembly
28) Mercantile (Malls – markets….)

E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec A5.3
D) EXTRA HAZARD (GROUP 1)
1) Aircraft hangers (except as governed by NFPA 409)
A N
S
2) Combustible hydraulic fluid area

S
3) Die casing ‫)للبس‬
(‫للللاكة‬
4) Metal extruding
5)
6)
7)
Plywood and particleboard manufacturing(

H
‫ب‬
A
Printing (using inks with flash point <100 0F)
rubber material manufacturing
‫للبللس لللاخش‬
‫)مصانع ك‬

8)
9)
Saw mills

L
textile material manufacturing I ( ‫)للللتصللنيع خاملللانسيج‬

A
10) Upholstering with plastic foam (‫للل فايبر‬
‫للللا‬
‫)لللاتنجيد ب‬

G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec A5.4
D) EXTRA HAZARD (GROUP 2)
1) Asphalt saturating
A N
S
2) Flammable liquids spraying

S
3) Flow coating (‫) دهان‬
4) Open oil quenching(‫ت‬‫)للللبتللريد لللازي‬
5)
6)
7)
Plastic manufacturing
‫ف‬
Solvent cleaning(‫تللللتنللظي‬
‫) مذيبا‬
Varnish & paint dipping(‫للل غمر‬ ‫للللا‬
H
‫)لللادهان ب‬
A
(‫)للللتصللنيع خام لللابلستيك‬

L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec A5.4
• SPRINKLERED SYSTEMS
1) Sprinklers :
A N
 Sprinkler parts:
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 3.6.1
• SPRINKLERED SYSTEMS
1) Sprinklers :
A N
Classified according to:
SS
A.
B.
Thermal sensitivity
Temperature rating
H A
C.
D.
K-factor
Installation orientation
L I
A
E. Special service conditions

G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 3.6.1
• A- Thermal sensitivity

A N
• A measure of the rapidity with which the thermal element operates as

S
installed in a sprinkler assembly , one measure of thermal sensitivity is

S
response time index (RTI)

When RTI = 50 (ms)0.5

When RTI ≥ 80 (ms)0.5


H A
fast response

standard

L I
•Sensitive element may be glass bulb or fusible link

. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 3.6.1
• B- Temperature rating
• The temperature at which sprinkler is activated
A N
S
• Indicated by color coding may be for glass bulb or frame arms

A S
I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-table 6.2.5.1
• C- k-factor
Is factor used to calculate the flow required by sprinkler
A N
Q=K√P
SS
Q : flow in GPM
P : pressure in psi
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-table 6.2.3.1
• C- k-factor (according to ceiling height)

A N
In NFPA there isn’t any instruction that connect sprinkler K- factor and ceiling

S
height only reference mention that is FM-global(3-26).

K-factor
Ceiling up to 9m
5.6 8

A S
Ceiling from 9-18m Ceiling above 18m
25.2

I H
A L
G .
E N
Fire Fighting Tech. For You
• D- sprinkler orientation
Pendent sprinkler Upright
A N
S
sprinkler

S
H A
Sidewall sprinkler
L I
. A
N G
E
Fire Fighting Tech. For You
• D- sprinkler orientation
 Pendent sprinkler installation types
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• E- special service condition
Corrosion resistant sprinkler
A
Dry sprinklerN
SS
H A
Institutional sprinkler
L I Rack storage sprinkler

. A
N G
E
Fire Fighting Tech. For You
• E- special service condition cont. :
Decorative sprinkler

A N
Pilot line detector

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• Other sprinkler types (design , performance)
Control mode specific application
A N
Early suppression fast

S
sprinkler (CMSA) (large drop) response sprinkler (ESFR)

A S
I H
Extended coverage sprinkler

A L Conventional sprinkler

G .
E N
Fire Fighting Tech. For You
• Other sprinkler types cont.
Residential sprinkler
A N
Open head sprinkler

SS
H A
Quick response sprinkler
L IStandard sprinkler (K = 5.6)

. A
N G
E
Fire Fighting Tech. For You
• Get sprinkler data from deflector

A N
SS
H A
L I Standard spray
sprinkler pendent

. A
N G
E
Fire Fighting Tech. For You
• Stock of Spare sprinklers

A N
S
No. of spare sprinklers No. of sprinklers in system

S
6 300 >
1000 > & 300 ≤

A
12
24 1000 <

I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 6.2.9.5
• 2) piping :

A N
S
Gridded system Looped system Tree system

A S
I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec A.3.4.6,7
• 2) piping cont. :
A. Pipe Materials
A N
S
B. Pipe dimension

S
C. Joining methods
D. Hangers
E.

A.
valves

Pipe materials
H A
I.
II.
L I
Aboveground (common: seamless black steel sch.40 – galvanized steel)
Underground (common: HDPE - ductile iron)

. A
N G
E
Fire Fighting Tech. For You
I. Aboveground
pipes Fitting
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 6.3 ; 6.4
II. Underground
pipes Fitting
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 10.1 ; 10.2
II. Underground depth of cover
 Underground Fire pipe minimum depth
A N
SS
H
90cm
A 80cm
120cm

L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 10.4.3
• B. Pipe dimension :
Steel pipe
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec A.6.3.2
• B. Pipe dimension cont. :
copper pipe
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec A.6.3.5
• C. Joining methods :
Threaded pipe & fittings
A N
Welded pipe & fittings

SS
H A
L
Groove joining method (Victaulic coupling)I Brazed & soldered

. A
N G
E
Fire Fighting Tech. For You
• C. Joining methods cont. :
Remarks :
 Threaded joints :
A N
S
(a)

I. Thread joining permitted for schedule 40 for sizes less than 8 in.
II.


A S
Thread joining permitted for schedule 30 for sizes 8 in. and larger.

Applicable threaded joints for size ≤ 2 in. , welding or flanged and


grooved for sizes > 2 in.

I H
L
 Pipe bending : (b)

A
I. For schedule 40 and copper tubing

.
For 2 in. and smaller radius of bend ≥ 6 pipe diameter
For 2 ½ in. and larger radius of bend ≥ 5 pipe diameter

N
For all sizes G
II. For other steel pipes
radius of bend ≥ 12 pipe diameter


E Galvanized pipe shall not be bent or welded.
Fire Fighting Tech. For You a. Refer to NFPA 13-2013ed-sec 6.5
b. Refer to NFPA 13-2013ed-sec 6.3.7.9
• D. Hangers
Requirements :
A N
S
A) Support 5 times the weight of water

S
-filled pipe + 114kg.

H
ferrous. A
B) Hangers component shall be

L I
C) Hangers shall not be fastened to
gypsum ceiling or other soft material.

. A D)Distance between hanger and center

G
of upright sprinkler > 76 mm to not to be
an obstruction.

E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 9.1
 Refer to NFPA 13-2013ed-sec 9.2.3.3
• D. Hangers cont. (Trapeze)

A N
A shared support structure is a hanger or support designed for use by multiple

S
systems. Commonly, this is a trapeze that is arranged to support many lines,

S
such as chilled water lines, conduits, piping, or ductwork. With some building
structures, these shared supports are the most efficient way to support the

A
gravitational load of systems installed in the building.

H
L I
. A
N G
E
Fire Fighting Tech. For You
• D. Hangers cont. (Trapeze)

A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 9.1.1.7
• D. Hangers cont. (Rod sizes)

A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 9.1.2
• D. Hangers cont. (Fasteners in concrete)
Horizontal vertical
A N
 Post-installed anchors shall be

S
installed in horizontal position.

A S
 May be installed in vertical under
one of below condition:

I H
A. When concrete having gravel&
can support 4in or less in diameter.

A L B. When alternated with hangers


connected directly to structural

G . members such that trusses or side


of beams.
C. When spaced not more than 3m

E N apart (for ≥ 4in).

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 9.1.3


• D. Hangers cont. (Fasteners in concrete cont.)
Powder driven studs:
A N
S
• Representative samples of concrete into

S
which studs are to be driven shall be
tested to determine that the studs will

H A
hold a minimum load of (341 kg) for 2
in. or smaller pipe ; (454 kg) for 2 1/2
in. , 3 in. pipe ; and (545 kg) for 4 in.

L I
• Holes for bolts ≥ Bolt diameter+1.6
mm

A
• Bolts shall be provided with flat washer

G . & nut.

E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 9.1.3.9
• D. Hangers cont. (Fasteners in steel)

A N
Welding studs or other hanger parts shall

S
not attached by welding with steel have

S
thickness < 2.78 mm.
• Holes for bolts ≥ Bolt diameter+1.6 mm

H A
Bolts shall be provided with flat washer
& nut.

L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 9.1.4
• D. Hangers cont. (location of hangers)

A N
SS
H A
L I
. A E

N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-table 9.2.2.1
• D. Hangers cont. (location of hangers cont.)
Requirements :
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec A.9.2.3
• D. Hangers cont. (location of hangers cont.)

A N
SS
H A
I
Hanger supported on I-beam Unobstructed armover to up sp.

A L
G .
E N
Riser supported with pipe clamp
(A)
Flexible sprinkler hose fitting
(Unobstructed armover < 1.8m)
Fire Fighting Tech. For You (A) Refer to NFPA 13-2013ed-sec 9.2.1.3.3
• SPRINKLERED SYSTEM TYPES :
1) Wet system
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• SPRINKLERED SYSTEM TYPES CONT. :
1) Wet system cont.
A N

SS
A sprinkler system employing automatic sprinklers attached to a
piping system contains water and connected to water supply so that

afire.
H A
water discharge immediately from sprinklers opened by heat from


I
Generally used wherever there is no danger of the water in the pipes

L
freezing and no special conditions requiring one of other systems.


. A
Areas such as hotels , offices , hospitals …. etc.

N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 3.4.11
• SPRINKLERED SYSTEM TYPES CONT. :
2) Dry system
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• SPRINKLERED SYSTEM TYPES CONT. :
2) Dry system cont.
A N

SS
A sprinkler system employing automatic sprinklers attached to a piping
system contains air or nitrogen under pressure , when fire occur the

H
valve and out through opened sprinklers. A
sprinkler open making air release so the pressure of water can open the dry


I
Generally used wherever there is danger of the water in the pipes freezing.

L
(where temperature reaches below 40 0F (4.4 0C) )


. A
Areas subject to freezing such as parking garages , coolers , freezers ..etc.


G
Gridded dry pipe system shall not be installed.

N

E
Dry valve shall maintained at temperature ≥ 4 0C

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 3.4.5


• SPRINKLERED SYSTEM TYPES CONT. :
2) Dry system cont.
A N
S
• Time needed to deliver water & most remote sprinkler

A S
I H
1.
A L
Time of water delivery don’t apply for systems ≤ 500 gallon.
2.
3.
4.
.
Time of water delivery don’t apply for systems ≤ 750 gallon with accelerator.

G
For dwelling unit water delivery time ≤ 15 sec (don’t apply EXH. 1 or 2)
We can use accelerator valve to reach required time.
5.
N
*Design area must be increase by 30% of wet system without changes in

E
density.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 7.2.3.6


 *Refer to NFPA 13-2013ed-sec 11.2.3.2.5
• SPRINKLERED SYSTEM TYPES CONT. :
2) Dry system cont.
A N

SS
The air supply shall have capacity of restoring normal air pressure in the
system within 30 minutes.

H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 7.2.6.3.2
• SPRINKLERED SYSTEM TYPES CONT. :
3) Preaction system
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• SPRINKLERED SYSTEM TYPES CONT. :
3) Preaction system cont.
A N

S
A sprinkler system employing automatic sprinklers attached to a piping

S
system contains air that may or may not be under pressure , with

H A
supplemental detection system opens a valve that permits water to flow into
the sprinkler system and to be discharged from any opened sprinkler.


I
Areas where is a concern about accidental discharge such as electronic
rooms and libraries ….etc.
L
.
• System may be activated by:
A
G
I. single interlock (admits water to sprinkler piping when detector activated)
II. Non interlock (admits water to sprinkler piping when detector activated or

E N
automatic sprinkler)
III. Double interlock (admits water to sprinkler system when detector &
automatic sprinkler activated)
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 7.3.2.1
• SPRINKLERED SYSTEM TYPES CONT. :
2) Preaction system cont.
A N
S
• Time needed to deliver water & most remote sprinkler

A S
I H

A L
Time of water delivery don’t apply for systems ≤ 500 gallon.

G .
We can use accelerator valve to reach required time.
*For double interlock pre.system the design area must be increase by 30%
of wet system without changes in density.

E N
• For single & non interlock system one preaction valve with max.1000
sprinklers (this with respect to permitted area according to hazard).

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 7.3.2.3


 *Refer to NFPA 13-2013ed-sec 11.2.3.2.5
• SPRINKLERED SYSTEM TYPES CONT. :
4) Deluge system
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• SPRINKLERED SYSTEM TYPES CONT. :
4) Deluge system cont.
A N

SS
A sprinkler system employing open sprinklers attached to a piping system
connected to water supply through a valve that is opened by the operation

A
of detection system in the same area as the sprinklers.

H
I
• When this valve opens water flow into piping system and discharges from
all sprinkler attached there.


A L
Areas where fast fires anticipated and the intent is to quickly discharge a

storage areas … etc.


G .
lot of water like transformers , aircraft hangars , flammable liquid use and

E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 3.4.4
• SPRINKLERED SYSTEM TYPES CONT. :
5) Combined dry & preaction system.
A N

SS
A sprinkler system employing automatic sprinklers attached to a piping
system contains air or nitrogen under pressure with supplemental

H A
detection system when operate , actuates tripping device that open dry
valve and air exhaust valve at the end of the feed main.


I
If there is failure in detection system it will operate as dry system.

L

A
Combined dry pipe and preaction systems are not as common as they were

.
several decades ago. Such systems are intended to be applied to unusual

G
structures, such as piers or wharves, which require unusually long runs of
pipe.

E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 3.4.3
• SPRINKLERED SYSTEM TYPES CONT. :
6) Antifreeze system.
A N
• Used in small unheated areas

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 7.6.3.4
• SPRINKLERED SYSTEM TYPES CONT. :
Remarks :
A N

SS
For dwelling units (hotels , motels…) we don’t use sprinkler in :

I. Bathrooms with area don’t exceed 5.1 m2.

H A
II. Closets and pantries with area don’t exceed 2.2 m 2.

I
III.Balconies.


L
For hospital we don’t use sprinkler in clothes closets don’t exceed 0.55
m2.
A
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 8.15.8
• SPRINKLERED SYSTEM TYPES CONT. :
7) Water curtain :
A N
S
• Is a system used to protect walls , windows and roofs from exposure fires.

S
• The directional discharge produce a flat 1800 fan shaped spray pattern.

H A
L I
. A
N G
E
Fire Fighting Tech. For You
• SPRINKLERED SYSTEM TYPES CONT. :
7) Water curtain cont. :
A N
S
• Find building severity :

A S
I H
A L
G .
E N
Fire Fighting Tech. For You
 Refer to NFPA 80A-2001ed-sec 4.3
• SPRINKLERED SYSTEM TYPES CONT. :
7) Water curtain cont. :
A N
S
• Find building width & height & opening percentage

A S
I H
A L
G .
E N
 Building to building separation= guide No. X lesser dimension + 1.5m

Fire Fighting Tech. For You


 Refer to NFPA 80A-2001ed-sec 4.3
• SPRINKLERED SYSTEM TYPES CONT. :
7) Water curtain :
A N
S
• Find application rate

A S
I H
A L
G .
E N
Fire Fighting Tech. For You
 Refer to NFPA 13-2013ed-sec 23.7.1
• SPRINKLERED SYSTEM TYPES CONT. :
7) Water curtain :
A N
S
• Nozzle distribution and calculate flow rate

A S
I H
A L


G .
Flow rate (1) (gpm) =zone (1) application rate X zone (1) area
Flow rate (2) (gpm) =zone (2) application rate X zone (2) area


E N
Flow rate (3) (gpm) =zone (3) application rate X zone (3) area
Total flow = flow rate (1+2+3)
 Refer to NFPA 13-2013ed-sec 23.7.1
Fire Fighting Tech. For You
• SPRINKLERED SYSTEM TYPES CONT. :
7) Water curtain cont. :
A N
S
• If building to building less than calculated fire protection shall be

S
provide.
• Nozzles spaced not more than 2.44 m.

• Minimum residual pressure is 0.5 bar.
H A
Water curtain piping connected to deluge or manual operating system.

I
• The water supply shall be capable of simultaneously supplying the total
demand of sprinklers along an exposure to a maximum length of 300 ft
(91.4 m) with duration 60 min.

A L
G .
E N  Refer to NFPA 13-2013ed-sec 11.3.3
Fire Fighting Tech. For You
 Refer to NFPA 13-2013ed-sec 8.15.4
 Refer to NFPA 13-2013ed-sec 23.7.4
• SPRINKLERED SYSTEM TYPES CONT. :
8) Commercial kitchens:
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• SPRINKLERED SYSTEM TYPES CONT. :
8) Commercial kitchens cont. :
A N
 Wet chemical system for hoods

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• E. valves
Classification :

A N
S
Flow control valves Flow control valves

S
OS&Y gate valve Zone control station
Butterfly valve Backflow prevention valves
Post indicator valve
Sectional valve
H A
Drain valve
Test valve

I
Fire department connection
dry valve
Wet alarm valve

A L Pressure control valves

.
Relief valve
Deluge valve

G
Pressure reducing valve (PRV)
Preaction valve

N
Accelerator

E
Check valve

Fire Fighting Tech. For You


• E. valves
A. OS&Y gate valve
A N
Remarks :
I.
SS
when working pressure > 12.1 bar

A
extra heavy valves must be used.

I H
II. Tamper switch used to prevent
valve from locking (give alarm).

A L III. We may be use chain with lock to

.
confirm that no one can close it.

N G
E
Fire Fighting Tech. For You
• E. valves
B. Butterfly valve
A N
Remarks :

SS
I. valve may be with hand lever so the

A
space for operation need to be
checked.

I H
II. Tamper switch used to prevent

L
valve from locking (give alarm).

. A III. We may be use chain with lock to


confirm that no one can close it.

N G IV. when working pressure > 12.1 bar

E
extra heavy valves must be used.

Fire Fighting Tech. For You


• E. valves
C. Post indicator valve (PIV)
A N
Remarks :
I.
SS
when working pressure > 12.1 bar

A
extra heavy valves must be used.

I H
II. Tamper switch used to prevent
valve from locking (give alarm).

A L III. We may be use chain with lock to

.
confirm that no one can close it.

N G
E
Fire Fighting Tech. For You
• E. valves
D. sectional valve
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 8.16.1.6
• E. valves
D. sectional valve
A N
SS
H A
L I
. A
N G
Large private fire service main systems shall have sectional controlling valves
at appropriate points in order to permit sectionalizing the system in the event
of a break or for the making of repairs or extensions.

E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 8.16.1.6
• E. valves
E. Fire department connection (Siamese connection)
A N
Remarks :

SS
I. Shall consist at least of 2×2 1/2 in.

A
II. Single inlet only accepted for riser with
diameter ≤ 3in.

I H
III. Shall be approved. (UL – FM)
IV. Shall be located between 457-1200 mm

L
above grade level.
V. There shall be no shut off valve .

. A VI.Pipe size ≥ 4 in. for engine connection.


VII.Pipe size ≥ 6 in. for boat connection.

N G VIII.Pipe size shall not less than riser size.


IX.When system pressure < 150psi sign shall

E
not be required.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 8.17.2


 Refer to NFPA 13-2013ed-sec 8.17.2.3
• E. valves
E. Fire department connection (Siamese connection) cont.
A N
SS Remarks :

H A X= 457 – 1219 mm

L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 8.17.2
• E. valves
E. Fire department connection (Siamese connection) cont.
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 8.16.1
• E. valves
E. Fire department connection (Siamese connection) cont.
A N
Remarks :

SS
A
• Systems shall not required FDC:

I H
A. Building located in remote area that are
inaccessible for fire department support.

A L B. single story building with area < 186m2.

G . C. large capacity deluge system that


exceed the pumping capacity of fire

E N defense.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 8.17.2.2


• E. valves
F. Dry valve
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• E. valves
G. wet alarm check valve
A N
SS
H A
L I
A
Remarks :

G
 One alarm check for all
building risers.
.
 Located at the pump room.

E N
 Have two devices for alarm
a.Water motor with gong.
b.Pressure switch.
Fire Fighting Tech. For You
• E. valves
H. Deluge valve
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• E. valves
I. Preaction valve
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• E. valves
J. Accelerator
A N
Remarks :

SS
A
I. Used for reducing time of dry and

H
preaction valve opening (< 60 sec).

L I
II. shall be located as close as practical to
the dry pipe valve.

. A III. Antiflooding devices associated with a

G
dry pipe valve accelerator are activated
when the dry pipe valve trips.

E N IV. May be mechanical or electrical.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 7.2.4


• E. valves
J. Check valve
A N
Remarks :

SS
A
I. May be swing or butterfly check valve.

II.

I H
Must be used after Siamese connection.

A L
III. Must be used after fire pump (electric or
diesel or jockey pump)

G .
E N
Fire Fighting Tech. For You
• E. valves
K. Zone control station
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec A.8.17.4.2
 Refer to NFPA 13-2013ed-sec A.8.17.5.2.2
• E. valves
K. Zone control station (Cont’d)
A N
Remarks :
I.
SS
Multistory buildings exceeding two stories in height shall be provided with

A
a zone control station on each floor level.

II.
H
Zone control station shall not be required where sprinklers on the top level

I
of a multistory building are supplied by piping on the floor below.

A L
III. Zone control station shall not be required where the total area of all floors

.
combined does not exceed the system protection area limitations.

Extra hazard
25000

N G
Ordinary hazard
52000
Light hazard
52000
unit
ft2 Maximum protection

E
2323 4831 4831 m2 area by one floor ZCS

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 8.16.1.5


• E. valves
L. Backflow prevention

A N
S
Remarks :

S
I. Used when private fire system
connected to public water

II.
H A
Backflow prevention devices are not a

I
requirement of NFPA 13 and serve no

L
benefit to the sprinkler system.
Backflow prevention devices are

. A typically required by public health


authorities for non–fire protection

G
purposes.

E N III. Means shall be provided downstream of


all backflow prevention valves for flow
tests at system demand.
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 23.1.8
• E. valves
L. Backflow prevention cont.
A N
Remarks :

SS
A
III. Used with antifreeze systems.

I H
IV. Used when there is cross connection
between fire system and potable water.

A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 7.6.3.3
• E. valves
M. Drain valve
A N
Remarks :

SS
A
I. Drain valves shall be approved.

I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 8.16.2.4
• E. valves
M. Drain valve cont.
A N
Remarks :

SS
A
III. In dry pipe & preaction systems , branch
lines shall be pitched at least 4 mm/m ,

I H
and mains shall be pitched at least 2
mm/m in non refrigerated areas.

A L
IV. Where subject to freezing, a minimum

.
1.22 m of exposed drain pipe shall be
in a heated area between the drain valve

N G and the exterior wall when drain


piping extends through the wall to the

E
outside.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 8.16.2.3.1


 Refer to NFPA 13-2013ed-sec 8.16.2.4.8
• E. valves
N. Test valve

A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec A.8.17.4.2
• E. valves
N. Test valve cont.

A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 20-2013ed-sec A.6.3.1
• E. valves
O. Pressure Relief Valves

A N
Remarks :

SS
A
Shall be installed with diesel drive
pump when 121% of shutoff (churn)

I H
pressure plus static pressure exceed.
component rating pressure.

A L Shall be installed between the pump

.
and discharge check valve.

N G
E
Fire Fighting Tech. For You  Refer to NFPA 20-2013ed-sec4.18.1.2
 Refer to NFPA 20-2013ed-sec4.18.3
• E. valves
P. Pressure Reducing Valve (PRV)

A N
Remarks :

SS
A
I. In portions of systems where all
P1
H
P2 components are not listed for
pressure greater than 175 psi (12.1

L I bar) and the potential exists for


normal water pressure in excess of

A
175 psi (12.1 bar), a listed pressure-
P2 < P1
.
reducing valve shall be installed.

N G II. Used with fire hose cabinet to avoid


exceeding the maximum permissible

E
pressure.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 8.16.1.2


• F. Water flow alarm devices
Flow switch

A N
Water motor &Gong

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
A N
SS
H A
Installation REQUIREMENTS
I
A L
G .
E N
Fire Fighting Tech. For You
A N
SS
H A
A. Standard
I sprinkler
A L
G .
E N
Fire Fighting Tech. For You
• Installation REQUIREMENTS :
A. Standard upright & pendant sprinkler coverage
A N
Extra hazard
90
Ordinary hazard
130
Light hazard
200
SS
unit
ft2

A
Max. sprinkler protection
8.4 12.1 18.6 m2 area (pipe schedule)

H
100 130 225 ft2 Max. sprinkler protection

I
9.3 12.1 20.9 m2 area (hydraulic calc.)

L
12 15 15 ft Maximum distance
3.7 4.6 4.6 m between sprinkler
6
1.8
.
6
1.8
A 6
1.8
ft
m
Minimum distance
between sprinkler

N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.2.2
 Refer to NFPA 13-2013ed-sec8.6.3.4
• Installation REQUIREMENTS :
A. Standard upright & pendant sprinkler
A N
Remarks :
SS
A
 L=room length
 W=room width


X = distance between sprinkler , wall.
2X = distance between sprinklers.
I H

 X ≥ 4 in.
A L
Y = distance between deflector , ceiling

 For upright sprinklers :

G .
For unobstructed ceiling 1 in. < Y < 12 in.

E N
 Minimum distance between sprinklers
is 1.8 m to avoid intercooling.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.3.3


 Refer to NFPA 13-2013ed-sec8.6.4.1
• Installation REQUIREMENTS :
A. Standard upright & pendant sprinkler
A N
 Exhibition : Small Rooms

SS
H A
L I
. A
N G
 Small room exhibition limited to light hazard and have area ≤ 74.3m 2 and wall opening

E
width doesn’t exceed 2.4m for each.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.3.2


• Installation REQUIREMENTS CONT. :
 (sprinkler performance)
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-secA.8.7.5.5
• Installation REQUIREMENTS CONT. :
 Obstructed ceiling
A
2) Concrete Tee
N
S
1) Beams (spaced 0.9 : 2.3m)

A S
I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-secA.3.7.1
• Installation REQUIREMENTS CONT. :
 Obstructed ceiling (cont’d)
A N
S
3) Wood Joist

A S
I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-secA.3.7.1
• Installation REQUIREMENTS :
A. Standard upright & pendant sprinkler
A N
 For obstructed ceiling
Option -
SS Option - 2
1

H A
L I
. A
N G
I - Install sprinkler below structural II - Install sprinkler in each bay.

E
member.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.4.1.2


• Installation REQUIREMENTS :
A. Standard upright & pendant sp.
A N
 For obstructed ceiling (cont’d)
Option -
SS
3

H A
L I
. A
N G
III - Install sprinkler at or above

E
structural member.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.4.1.2


• Installation REQUIREMENTS :
A. Standard upright & pendant sprinkler
A N
 For obstructed ceiling (cont’d)
Option -
SS
4

H A
L I
. A
N G
IV - Install sprinkler below wood

E
joists.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.4.1.2


• Installation REQUIREMENTS CONT. :
A. Standard upright & pendant sprinkler
A N
 For obstructed ceiling (cont’d)
 Wood truss
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.5.2
• Installation REQUIREMENTS CONT. :
A. Standard upright & pendant sprinkler
A N
May be pipe

S
with D ≥ 3in.
 For obstructed ceiling (cont’d)

S
 Wood truss

H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.5.2
• Installation REQUIREMENTS CONT. :
A. Standard upright & pendant sprinkler
A N
 For obstructed ceiling (cont’d)
 Wood truss
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.5.2
• Installation REQUIREMENTS CONT. :
A. Standard upright & pendant sprinkler
A N
S
 For obstructed ceiling (cont’d)

S
Remarks :

A
H
ceiling  Sprinklers shall be installed under

I
fixed obstructions over 4 ft (1.2 m)
wide, such as ducts, decks, open

A L
Duct
grate flooring, cutting tables, and
overhead doors.

G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.5.3.2
• Installation REQUIREMENTS CONT. :
A. Standard upright & pendant sprinkler
A N
 For obstructed Floor

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.5.2
• Installation REQUIREMENTS CONT. :
A. Standard upright & pendant sprinkler
A N
 For vertical change in ceiling

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.4.1
• Installation REQUIREMENTS CONT. :
A. Standard upright & pendant sprinkler
A N
 For ceiling pockets

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.7
• Installation REQUIREMENTS CONT. :
A. Standard upright & pendant sprinkler
A N
 For pitched roof

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.4.1.3
• Installation REQUIREMENTS CONT. :
A. Standard upright & pendant sprinkler
A N
 For pitched roof (cont’d)

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.4.1.3
• Installation REQUIREMENTS CONT. :
A. Standard upright & pendant sprinkler
A N
 For pitched roof

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.4.1.4
• Installation REQUIREMENTS CONT. :
A. Standard upright & pendant sprinkler
A N
 For skylight

SS
A
 Sprinklers shall be permitted to be omitted from skylights not exceeding 32
ft2 (3 m2) in area, regardless of hazard classification

I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.5.7
• Installation REQUIREMENTS CONT. :
A. Standard upright and pendant sprinkler
A N
SS
H A
L I
. A
N G
E
 The sprinkler system shall extend at least 24 ft (7.2 m) into the space
above the ceiling.
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.7.15.22.3
• Installation REQUIREMENTS :
A. Standard Sidewall sprinkler coverage
A N
Light hazard
Noncombustible
SS Ordinary hazard
Noncombustible

A
Combustible
Combustible or limited or limited
Unit ceiling finish
ceiling finish combustible combustible

H
ceiling finish ceiling finish

I
Max. distance ft 14 14 10 10

L
along the wall m 4.3 4.3 3 3

A
Max. room ft 12 14 10 10

.
width m 3.7 4.3 3 3

G
Max. protection ft2 120 196 80 100
area m2 11.2 18.2 7.4 9.3

E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-table8.7.2.2.1
• Installation REQUIREMENTS :
A. Standard sidewall sprinkler
A N
Remarks :
SS
A
 L=room length
 W=room width


X = distance between sprinkler , wall.
2X = distance between sprinklers.
I H

 X ≥ 4 in.
A L
H = distance between deflector , ceiling

 For sidewall sprinklers :


4 in. < H < 6 in.
Otherwise listed for > 6in.
G .
E N
 Minimum distance between sprinklers
is 1.8 m to avoid intercooling.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.7.3.3


 Refer to NFPA 13-2013ed-sec8.7.4.1
• Installation REQUIREMENTS CONT. :
A. Standard sidewall sprinkler
A N
Remarks :

SS
I. From ceiling sidewall sprinkler 4 to 6 in.

A
II. From walls sidewall sprinkler min. 4 in.
III. From wall at which sidewall sprinkler

I H
mounted may be less than 4 in.

A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.7.3
 Refer to NFPA 13-2013ed-sec8.7.4
• Installation REQUIREMENTS CONT. :
A. Standard sidewall sprinkler
A N
S
 For obstructed ceiling

A S
I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.7.5.1.4
• Installation REQUIREMENTS CONT. :
A. Standard sidewall sprinkler
A N
S
 For obstructed ceiling

A S
I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.7.5.1.4
• Installation REQUIREMENTS CONT. :
A. Standard sidewall sprinkler
A N
May be pipe
with D ≥ 3in.

S
 For obstructed ceiling

A S
I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.7.5.2.1
• Installation REQUIREMENTS CONT. :
A. Standard sidewall sprinkler
A N
S
 For obstructed Floor

A S
I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.7.5.2.2
A N
SS
B. CONTROL MODE
H SPECIFIC A
I
L (CMSA)
APPLICATION
. A
N G
E
Fire Fighting Tech. For You
• Installation REQUIREMENTS CONT. :
B. CMSA upright & pendant sprinkler
A N
Construction type
ft2
SS
Protection area
m2
Maximum spacing
ft m
Noncombustible unobstructed
Noncombustible obstructed
130

H
130 A12.1
12.1
12
12
3.7
3.7

I
combustible unobstructed 130 12.1 12 3.7

L
combustible obstructed 100 9.3 10 3.1

A
Rackstorage combustible obstructed 100 9.3 10 3.1
Rackstorage combustible

G .
unobstructed , noncombustible
100 9.3 12 3.7

E N COMMON

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-table8.11.2.2.1


• Installation REQUIREMENTS CONT. :
B. CMSA upright & pendant sprinkler
A N
Remarks :
SS
A
 L=room length
 W=room width


X = distance between sprinkler , wall.
2X = distance between sprinklers.
I H

 X ≥ 4 in.

A L
Y = distance between deflector , ceiling

 For upright sprinklers :

G .
For Unobstructed ceiling … 6 in. < Y < 8 in.
 Minimum distance between sprinklers

E N
is 2.4 m to avoid intercooling.
 Minimum distance between deflector and
storage is 36in.
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.11.3
 Refer to NFPA 13-2013ed-sec8.11.4
• Installation REQUIREMENTS CONT. :
B. CMSA upright & pendant sprinkler
A N
 For obstructed ceiling
Option -
SS Option - 2
1
6in to
H A
I
12in.

L
Max.
22in.

. A
N G
I - Install sprinkler below ceiling. II - Install sprinkler below wood

E
Fire Fighting Tech. For You
joists.

 Refer to NFPA 13-2013ed-sec8.11.4.1.2


• Installation REQUIREMENTS CONT. :
B. CMSA upright & pendant sprinkler
A N
 For obstructed ceiling (cont’d)
Option -
SS
3

H A
L I
. A
N G
III - Install sprinkler at or above

E
structural member.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.11.5.2


• Installation REQUIREMENTS CONT. :
B. CMSA upright & pendant sprinkler
A N
 For obstructed ceiling (cont’d)

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.11.5.3
• Installation REQUIREMENTS CONT. :
B. CMSA upright & pendant sprinkler
A N
 For obstructed ceiling (cont’d)

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.11.5.3
• Installation REQUIREMENTS CONT. :
B. CMSA upright & pendant sprinkler
A N
 For obstructed ceiling (cont’d)

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.11.5.3
• Installation REQUIREMENTS CONT. :
B. CMSA upright & pendant sprinkler
A N
May be pipe
 For obstructed ceiling (cont’d)
S
with D ≥ 2in.

A S
I H
A L
G .
E N
A ≤ 24in.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.11.5.2


A N
SS
C. EARLY SUPRESSION
H A
L I
FAST RESPONSE (ESFR)
. A
N G
E
Fire Fighting Tech. For You
• Installation REQUIREMENTS CONT. :
C. ESFR upright & pendant sprinkler
A N
Construction type

SS
Ceiling/Roof Height ≤ 9.1m Ceiling/Roof Height > 9.1m

Protection area

ft2 m2
H
ft m A
Max. spacing Protection area

ft2 m2
Max. spacing

ft m
100

L
9.3
I12 3.7 100 9.3 10 3.1

. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-table8.12.2.2.1
• Installation REQUIREMENTS CONT. :
C. ESFR upright & pendant sprinkler
A N
Remarks :
 L=room length
SS
 W=room width
 X = distance between sprinkler , wall.
H A
I
 2X = distance between sprinklers.

L
 Y = distance between deflector , ceiling
 X ≥ 4 in.
 For upright sprinklers :

. A
obstructed ceiling ……. 3 in. < Y < 12 in.

G
 Minimum distance between sprinklers

N
is 2.4 m to avoid intercooling.
 Minimum distance between deflector and

E
storage is 36in.
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.12.3.3
 Refer to NFPA 13-2013ed-sec8.12.3.4.1
• Installation REQUIREMENTS CONT. :
C. ESFR upright & pendant sprinkler
 For obstructed ceiling
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.12.5.1
A N
SS
D. EXTENDEDH
COVERAGE A
I
L (ECS)
SPRINKLER
. A
N G
E
Fire Fighting Tech. For You
• Installation REQUIREMENTS CONT. :
D. Extended coverage upright & pendant sprinkler coverage
A N
Construction type Light hazard

SS Ordinary hazard

A
Protection area spacing Protection area spacing

H
ft2 m2 ft m ft2 m2 ft m

I
400 37.2 20 6.1 196 18.2 14 4.3

A L
.
Construction type Extra hazard High piled storage

G
Protection area spacing Protection area spacing

N
ft2 m2 ft m ft2 m2 ft m

E
196 18.2 14 4.3 196 18.2 14 4.3

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-table8.8.2.1.2


• Installation REQUIREMENTS CONT. :
D. Extended coverage upright & pendant sprinkler coverage
A N
Remarks :
 L=room length
SS
 W=room width
 X = distance between sprinkler , wall.
H A
I
 2X = distance between sprinklers.

L
 Y = distance between deflector , ceiling
 X ≥ 4 in.
 For upright sprinklers :

. A
For unobstructed ceiling …1 in < Y < 12
in.

N G
 Minimum distance between sprinklers

E
is 2.4 m to avoid intercooling.
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-table8.8.2.1.2
• Installation REQUIREMENTS CONT. :
 Sprinkler performance
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-secA.8.7.5.5
• Installation REQUIREMENTS :
D. Extended coverage upright & pendant sprinkler coverage
A N
 For obstructed ceiling (cont’d)
Option -
SS Option - 2
1

H A
L I
 For obstructed ceiling
. A
N G
I - Install sprinkler below structural II - Install sprinkler in each bay.

E
member.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.8.5.2


• Installation REQUIREMENTS :
D. Extended coverage upright & pendant sprinkler coverage
A N
S
 For obstructed ceiling (cont’d)

Option -
3
A S
I H
A L
.
8.8.5.2

N G
III - Install sprinkler at or above

E
structural member.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.8.5.2


• Installation REQUIREMENTS CONT. :
D. Extended coverage upright & pendant sprinkler coverage
A N
S
 For obstructed ceiling (cont’d) May be pipe

S
with D ≥ 3in.

H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.8.5.2
• Installation REQUIREMENTS CONT. :
D. Extended coverage upright & pendant sprinkler coverage
A N
S
 For obstructed ceiling (cont’d)

S
Remarks :

A
H
ceiling  Sprinklers shall be installed under

I
fixed obstructions over 4 ft (1.2 m)
wide, such as ducts, decks, open

A L
Duct
grate flooring, cutting tables, and
overhead doors.

G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.7.5.3.2
• Installation REQUIREMENTS CONT. :
D. Extended coverage upright & pendant sprinkler coverage
A N
S
 For obstructed floor

A S
I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.8.5.2
• Installation REQUIREMENTS CONT. :
D. Extended coverage upright & pendant sprinkler coverage
A N
 For vertical change in ceiling

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.8.4.1.1.4
• Installation REQUIREMENTS CONT. :
D. Extended coverage upright & pendant sprinkler coverage
A N
 For ceiling pockets

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.8.7.2
• Installation REQUIREMENTS CONT. :
D. Extended coverage upright & pendant sprinkler coverage
A N
 For skylight

SS
A
 Sprinklers shall be permitted to be omitted from skylights not exceeding 32
ft2 (3 m2) in area, regardless of hazard classification

I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.8.7.3
• Installation REQUIREMENTS CONT. :
D. Extended coverage sidewall sprinkler coverage
A N
Construction type Light hazard
Protection area spacing
SS Ordinary hazard
Protection area spacing

Unobstructed ,
smooth , flat
ft2
400
m2
37.2
ft
28
H
m
8.5
A ft2
400
m2
37.2
ft
24
m
7.3

L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-table8.9.2.2.1
• Installation REQUIREMENTS :
D. Extended coverage sidewall sprinkler coverage
A N
Remarks :
 L=room length
SS
 W=room width
 X = distance between sprinkler , wall.
H A
I
 2X = distance between sprinklers.

L
 H = distance between deflector , ceiling
 X ≥ 4 in.
 For sidewall sprinklers :

. A
4 in. < H < 6 in. Otherwise listed for > 6in.

N G
 No sprinklers shall be located within the
maximum protection area of any other
sprinkler
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.9.3
• Installation REQUIREMENTS CONT. :
D. Extended coverage sidewall sprinkler coverage CONT.
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.9.5
• Installation REQUIREMENTS CONT. :
D. Extended coverage sidewall sprinkler coverage CONT.
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.9.5
• Installation REQUIREMENTS CONT. : May be pipe

N
with D ≥ 3in.
D. Extended coverage sidewall sprinkler coverage CONT.

S A
A S
I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.9.5
• Installation REQUIREMENTS CONT. :
D. Extended coverage sidewall sprinkler coverage CONT.
A N
Remarks :

SS
I. From ceiling sidewall sprinkler 4 to 6 in.

A
II. From walls sidewall sprinkler min. 4 in.
III. From wall at which sidewall sprinkler

I H
mounted may be less than 4 in.

A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.9.4
A N
SS
H A
E. RESIDENTIAL
I SPRINKLER
A L
G .
E N
Fire Fighting Tech. For You
• Installation REQUIREMENTS CONT. :
E. RESIDENTIAL SPRINKLER upright & pendent sprinkler
A N
Specification
Protection area
SSValue
According to manufacturer
Maximum spacing
Minimum spacing

H A
According to manufacturer
2.44 m

L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 8.10
• Installation REQUIREMENTS CONT. :
E. RESIDENTIAL SPRINKLER upright & pendent sprinkler (cont’d)
A N
Remarks :
 L=room length
SS
 W=room width
 X = distance between sprinkler , wall.
H A
I
 2X = distance between sprinklers.

L
 Y = distance between deflector , ceiling
 For upright sprinklers :

. A
For unobstructed ceiling …1 in < Y < 4 in.
Otherwise listed for > 4in.

N G
 Minimum distance between sprinklers
is 2.4 m to avoid intercooling.

E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 8.10
• Installation REQUIREMENTS CONT. :

A N
E. RESIDENTIAL SPRINKLER upright & pendent sprinkler (cont’d)

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.4.1.3
• Installation REQUIREMENTS CONT. :

A N
E. RESIDENTIAL SPRINKLER upright & pendent sprinkler (cont’d)

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.10.3.6
• Installation REQUIREMENTS CONT. :

A N
E. RESIDENTIAL SPRINKLER upright & pendent sprinkler (cont’d)

S
 Ceiling obstruction

A S
I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.10.6.2
• Installation REQUIREMENTS CONT. :
E. RESIDENTIAL SPRINKLER upright & pendent sprinkler
A N
S
 Ceiling obstruction (cont’d)

A S
I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.10.6.2
• Installation REQUIREMENTS CONT. :
E. RESIDENTIAL SPRINKLER upright & pendent sprinkler
A N
S
 Floor obstruction

A S
I H
A L
G .
E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.10.6.2
• Installation REQUIREMENTS :
E. RESIDENTIAL sidewall SPRINKLER
A N
Remarks :
 L=room length
SS
 W=room width
 X = distance between sprinkler , wall.
H A
I
 2X = distance between sprinklers.

L
 H = distance between deflector , ceiling
 For sidewall sprinklers :

. A
4 in. < H < 6 in. Otherwise listed for > 6in.

N G
 Minimum distance between sprinklers
is 2.4 m to avoid intercooling.

E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.9.3
• Installation REQUIREMENTS CONT. :
E. Residential sidewall sprinkler (cont’d)
 Ceiling obstruction
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.10.7.1
• Installation REQUIREMENTS CONT. :
E. Residential sidewall sprinkler (cont’d)
 Ceiling obstruction (cont’d)
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.10.7.1
• Installation REQUIREMENTS CONT. :
E. Residential sidewall sprinkler (cont’d)
 Ceiling obstruction (cont’d)
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.10.7.2
• Installation REQUIREMENTS CONT. :
E. Residential sidewall sprinkler (cont’d)
 Ceiling obstruction (cont’d)
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.10.7.2
A N
SS
H A
F. Dry SPRINKLER
I
A L
G .
E N
Fire Fighting Tech. For You
• Installation REQUIREMENTS CONT. :
F. Dry sprinkler
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.4.9
• Installation REQUIREMENTS CONT. :
F. Dry sprinkler cont. :
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.4.9
A N
SS
H A
G. Pilot Isprinkler
A L
G .
E N
Fire Fighting Tech. For You
• Installation REQUIREMENTS CONT. :
G. Pilot sprinkler
A N
Item
Maximum horizontal spacing
Outdoor
2.5m
SS Indoor
3.7m

A
Maximum vertical spacing 5.2m ------

H
Maximum distance below ceiling ------ 0.56m

L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.15.20.4
A N
SS
H. General & Special
H A
L I
installation requirement
. A
N G
E
Fire Fighting Tech. For You
• Installation REQUIREMENTS CONT. :
 Return bend
A N
Remarks :

SS
I.
A
Shall be used when water supplied from

H
raw water – mill pond – open tank.

II.

L I
Shall not be required for deluge systems.

A
III. Shall not be required with dry pendant

G . sprinkler.

IV. Shall not be required with sprinklers

E N have k-factor ≥ 11.2.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.15.20.4


• Installation REQUIREMENTS CONT. :
 Return bend cont. :
A N
SS (Max. 4in.)

H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.15.20.4
• Installation REQUIREMENTS CONT. :
 Above and below ceiling sprinkler :
A N
S
Remarks :

S
Ceiling US  When above ceiling sprinkler shall
be installed :

H A
 According to NFPA 13 requirement :

I
False ceiling PS
I. If ceiling constructed from

A L combustible material like wood.

G . II. If concealed space used for storage.

III. If concealed spaces used for

E N maintenance (like hygienic places..).

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.15.1.2.2


• Installation REQUIREMENTS CONT. :
 Above and below ceiling sprinkler (cont’d) :
A N
S
Remarks :

S
Ceiling US  When above ceiling sprinkler shall
be installed :

A
> 80cm

H
 According to British codes:

I
False ceiling PS
I. If ceiling depth larger than 80cm.

A L II. Concealed space contain combustible


material.

G .
E N
Fire Fighting Tech. For You
• Installation REQUIREMENTS CONT. :
 Escalator Draft stop

A N sprinkler

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-secA.8.15.4
• Installation REQUIREMENTS CONT. :
 Library Stack Areas and Medical Record Storage.
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• Installation REQUIREMENTS CONT. :
 Library Stack Areas and Medical Record Storage cont.
A N
Remarks :

SS
A
I. Classified as ordinary hazard group II.

II.
H
Where Y ≥ 18 in. sprinklers installed without
regard to aisles.

I
L
III. Where Y < 18 in. there is two situations:

A
G .
• If there is complete dividers , sprinklers
shall installed in every aisle and tier with

N
spacing ≤ 3.7 m.
• With non complete dividers sprinkler shall

E
be staggered.
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.15.10
• Installation REQUIREMENTS CONT. :
 Library Stack Areas and Medical Record Storage.
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.15.10
• Installation REQUIREMENTS CONT. :
 Elevator Hoistways and Machine Rooms.
A N
Remarks :

SS
A
I. Sidewall spray sprinklers shall be installed at the
bottom of each elevator hoistway not more than
0.61 m above the floor of the pit.

I H
II. If hoistway enclosed with noncombustible shaft

L
(don’t contain hydraulic fluids) shall not
required sprinkler at the pit.

. A
III. Upright or pendent or sidewall sprinkler shall be
installed at the top of hoistway.

N G
IV. If hoistway is non or limited combustible and car
enclosure material according to ASME A17.1
shall not required sprinkler at the top.

E
(except if belt is combustible)
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.15.5
• Installation REQUIREMENTS CONT. :
 Elevator Hoistways and Machine Rooms.
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• Installation REQUIREMENTS CONT. :
 Sprinklers & fans.
A N
I. Fan up to 1.5m diameter :

SS
Sprinklers shall be permitted to be placed without regard to the blades of ceiling

A
fans less than 60 in. (1.5 m) in diameter.

II. High volume low speed fan (HVLS) :

I H
The installation of HVLS fans in buildings equipped with sprinklers, including

L
ESFR sprinklers, shall comply with the following:
a) The maximum fan diameter shall be 24 ft (7.3 m).

. A
b) The HVLS fan shall be centered approximately between four adjacent
sprinklers.

N G
c) The vertical clearance from the HVLS fan to sprinkler deflector shall be a
minimum of 3 ft (0.9 m).

E
d) All HVLS fans shall be interlocked to shut down immediately upon
receiving a waterflow signal from the alarm system.
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec8.6.5.2.1.10
 Refer to NFPA 13-2013ed-sec11.1.7
• Installation REQUIREMENTS CONT. :
 Sprinklers & fans.
A N
SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
• Installation REQUIREMENTS CONT. :
 Sprinklers & fans.
A N
II. High volume low speed fan (HVLS) cont. :

SS
H A
L I
. A
N G
E
Fire Fighting Tech. For You
A N
SS
HA
PIPE ISIZING
A L
G .
E N
Fire Fighting Tech. For You
A N
SS
H A
A. PIPE SCHEDULES
I
A L
G .
E N
Fire Fighting Tech. For You
• Pipe schedules :
1) LIGHT HAZARD:
A N
S
Light hazard Light hazard above and below

S
Steel Copper
ceiling
Steel Copper

A
Pipe No. of No. of Pipe No. of No. of
size (in) sprinklers sprinklers size (in) sprinklers sprinklers
1 in.
1 ¼ in.
2
3
2
3
I H 1 in.
1 ¼ in.
2
4
2
3
1 ½ in.
2 in.
5
10
5
12

A L 1 ½ in.
2 in.
7
15
5
18
2 ½ in.
3 in.
30
60
G . 40
65
2 ½ in. 50 65

N
3 ½ in. 100 115

E
4 in. ------ ------
Max. 30sp above or below
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-table23.5.2.2.1
 Refer to NFPA 13-2013ed-table23.5.2.4
• Pipe schedules :
 Remarks :
A N
S
I. Maximum no of sprinkler per branch is 8 sprinklers.
II. No of sprinkler per branch may be increased to 9 sprinklers by making

thereafter standard.
A S
the two end lengths 1 in. and 1 1/4 in. respectively, and the sizes

III. Ten sprinklers shall be permitted to be placed on a branch line, making

sprinkler by a 2 ½ in. pipe.


I H
the two end lengths 1 in. and 1 1/4 in. respectively, and feeding the tenth

A
according to ordinary hazard.
L
IV. For light hazard if sprinkler No. exceeding 100 sprinklers sizing then

.
V. For above & below ceiling if sprinklers exceed 50 then sizing is

G
increased to 3 in. then according to standard schedule for the number of
sprinklers above or below a ceiling, whichever is larger.

N
VI. For above and below ceiling max .No of sprinklers is 8 for above and 8

E
for below ceiling.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec23.5.2


• Pipe schedules :
2) ORDINARY HAZARD:
A N
S
Ordinary hazard

Pipe
size (in)
Steel
No. of
sprinklers
Copper
No. of
sprinklers
A S
Pipe
size (in)
Steel
No. of
sprinklers
Copper
No. of
sprinklers
1 in.
1 ¼ in.
2
3
2
3
I H 5 in.
6 in.
160
275
180
300
1 ½ in.
2 in.
5
10
5
12

A L 8 in. ------- -------

2 ½ in.
3 in.
20
40
G . 25
45
o If distance between sprinklers or

N
3 ½ in. 65 75
branches ≤ 3.7m

E
4 in. 100 115

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-table23.5.3.4


• Pipe schedules :
2) ORDINARY HAZARD CONT. :
A N
No. of sprinklers – greater than 3.7m
separation (branches or sprinklers)
SS
ordinary hazard above and below ceiling

A
Steel Copper
Steel Copper

H
Pipe No. of No. of
size (in) sprinklers sprinklers

I
Pipe No. of No. of
size (in) sprinklers sprinklers 1 in. 2 2
2 ½ in.
3 in.
15
30
20
35
A L 1 ¼ in.
1 ½ in.
4
7
4
7
3 ½ in. 60

G . 65 2 in.
2 ½ in.
15
30
18
40

N
3 in. 60 65

E
Max. 40sp above or below
(separation ≤ 3.7)
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-table23.5.3.5
 Refer to NFPA 13-2013ed-table23.5.3.7
• Pipe schedules :
 Remarks :
A N
S
I. Maximum no of sprinkler per branch is 8 sprinklers.

S
II. No of sprinkler per branch may be increased to 9 sprinklers by
making the two end lengths 1 in. and 1 1/4 in. respectively, and
the sizes thereafter standard.

H A
III. Ten sprinklers shall be permitted to be placed on a branch line,

I
making the two end lengths 1 in. and 1 1/4 in. respectively, and
feeding the tenth sprinkler by a 2 ½ in. pipe.

A L
IV. For above & below ceiling if sprinklers exceed 60 then sizing is
increased to 4 in. then according to standard schedule for the

G .
number of sprinklers above or below a ceiling whichever is larger.
V. For above and below ceiling max .No of sprinklers is 8 for above
and 8 for below ceiling.

E N
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec23.5.3
• Pipe schedules :
3) EXTRA HAZARD :
A N
S
Extra hazard

S
Steel Copper Steel Copper

A
Pipe No. of No. of Pipe No. of No. of
size (in) sprinklers sprinklers size (in) sprinklers sprinklers
1 in.
1 ¼ in.
1
2
1
2

I H 5 in.
6 in.
90
150
100
170

L
1 ½ in. 5 5

A
2 in. 8 8 Remarks :
2 ½ in.
3 in.
15
27

G . 20
30
This table is reprinted only as a
guide for existing systems.

N
3 ½ in. 40 45
4 in. 55 65

E
Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-tableA.23.5.4
• Project Design Stages :
Schematic design
A N
S
and basis of
Concept design. Developed design.

S
design report
(BODR).

H A
Shopdrawings.

L I
Tender document. Detailed design.

. A
N G
As built (after
construction).

E
Fire Fighting Tech. For You
• Project Design Procedure:
1.

A N
Find NFPA 101 or NFPA 5000 fire extinguishment requirements for your
building (with respect to local codes or AHJ).
2.
3.
Determination the building hazard .

SS
Locating non sprinklered spaces. (ex. Rooms need gas systems) then calculate

A
gas volume required for extinguishment.
4. Distribution for sprinklers according to hazard requirement .

H
5. Determination No. of risers and standpipe needed for sprinklers and FHCs.

I
6. Pipe routing .
7. Pipe sizing by pipe schedule according to material and hazard.
8.
9.

A L
Locating the design area (most demand flow and pressure) .
Hydraulic calculation for pump sizing .
10.
11.
12.
Pump selection .

G .
Tank capacity calculation .
Pump room design .
13.

14.
E N
If there is room need foam system (ex. Generator room) calculate foam
concentrate quantity.
Fire extinguisher distribution.
Fire Fighting Tech. For You
A N
SS
H A
Thank I You!
A L
G . Ali Hassan Mohamed
Fire & plumbing design engineer

N
(+02)01001737218

E
Ali_hassan644252@yahoo.com

Fire Fighting Tech. For You

Вам также может понравиться