Академический Документы
Профессиональный Документы
Культура Документы
David Kandel
Application Consultant
Belimo
david.kandel@us.Belimo.com
720-354-0591
Agenda
© Belimo, 2012
Agenda
© Belimo, 2012
Understating Coil Behavior
Coil Performance
Resulting Coil
Output
Coil Power / Flow
ΔT
Valve GPM
BTUh
© Belimo, 2012
Valve Specs
• Pressure/Temperature Ratings
• Body Pressure
• Close-Off Pressure
• Close-Off Leakage
• DP
• Temp Ratings
• Valve Flow
• Characterization Curve
• Rangeability/Turndown
• Valve Authority
• Actuation
• Fail Safe
• Normally Open/Normally Closed
Body Pressure
P1
The maximum pressure that a valve can withstand without leakage while in the
fully closed position.
Close-Off Pressure
Rule of Thumb
• 2-way Valve
• Close-off pressure should at least equal the maximum pressure produced
by the circulating pump
• 3-way Valve
• Close-off pressure should at least equal the system differential pressure
Close-Off Pressure
Close-Off Leakage
P1 P2
• Equal Percentage
• Linear
• Quick Opening
• Modified Equal Percentage
Flow
• Varies
Modulating
2 Position
based
control
Control
on design
of Steam
a Coil
•Coil
CCV,
Zone
Butterfly
or Bypass
Valves
PI-Valves,
Valves,
Applications
Globe
others Valve
• ePIV, Globe Valves
Valve Position
Rangeability & Turndown
Rangeability:
The ratio of maximum flow to minimum controllable flow
of a valve body only under laboratory conditions with a
constant differential pressure applied across the valve.
Turndown Ratio:
The ratio of maximum usable flow to minimum
controllable flow of the valve assembly under installed
conditions. It is always lower than the rangeability
factor.
Agenda
© Belimo, 2012
Flow Coefficient
gpm
Cv
P
Hydronic Valve Sizing
gpm 8 8
Cv Cv 4
P 4 2
Example:
• Coil Requires 8 GPM
• Design DP for valve, 4 psi
• DP of Valve not to exceed 5
psi
Hydronic Valve Sizing
8 8
Cv 4
4 2
Example:
• Coil Requires 8 GPM
• Design DP for valve, 4 psi
• DP of Valve not to exceed 5
psi
Hydronic Valve Sizing
Checking DP
2
GPM
P
Cv
Example:
• Coil Requires 8 GPM
• Design DP for valve, 4 psi
• DP of Valve not to exceed 5
psi
Hydronic Valve Sizing
Checking DP
2
GPM
P
Cv
2
8
P 7.1 psi
3
2
8
P 2.9 psi
4.7
Hydronic Valve Sizing
Checking DP
2
GPM
P
Cv
Which should we select? 2
8
And Why? P 7.1 psi
3
2
8
P 2.9 psi
4.7
Valve Authority
pvalve
A
pbranch
pvalve
Balance
Coil Valve
Flow (%)
pBranch
Valve Opening (%)
24
Valve Authority
8
2 pvalve
P 7.1 psi A
3 pbranch
2
8
P 2.9 psi
4.7 pvalve
Balance
Coil Valve
90
70
60
50
Flow (%)
40 0.2
30
1
20
10
0 10 20 30 40 50 60 70 80 90 100
26
Hydronic Valve Sizing
Rules of Thumb
1
Fp
d 2
1 1.51 -
D C 2
2
v
2
890 d
C vc Fp C v
Fp pipe geometry factor
C v rated sizing coefficien t without reducers
d nominal valve size (in.)
D inside diamter of the pipe (in.)
C vc corrected C v
Pipe Reduction Factor
Rules of Thumb
• Which is Correct?
And
• Why is it Correct?
© Belimo, 2012
Steam Valve Sizing
Low Pressure Steam (under 15psi)
Cv = Flow Coefficient
Q Q = lbs per hour of steam
Cv
3 * P Po ΔP = Differential Pressure in psig
Po = Outlet Pressure in psia
(psia = psig + 14.7)
Q
Cv
3 * P P 2
160 160
Cv 6.73
3 * 4 15.7 23.774
Steam Valve Sizing
More than 15psi
Cv = Flow Coefficient
Q
Cv Q = lbs per hour of steam
3 * P Po ΔP = Differential Pressure in psia
Po = Outlet Pressure in psia
(psia = psig + 14.7)
ΔP =
42% absolute inlet pressure (psia)
Steam Valve Sizing
More than 15psi Example: Size modulating
1/3-2/3 valves for a heat
exchanger with a design
flow of 600 lb/hr at 30
Q
Cv psig.
3 * P Po
200 200
1/3rd: Cv 3.02
3 * 18.8 25.9 66.2
400 400
2/3rd: Cv 6.04
3 * 18.8 25.9 66.2
1/3-2/3 Valve Sequencing
Open
Closed
0% 25% 50% 75% 100%
Control Signal
2/3 valve
1/3 valve
Agenda
© Belimo, 2012
Control Valve Technologies
CCV
2-way
CCV
Valve Summary
• Pros • Applications
• Inexpensive • Hot & chilled water coils
• Equal Percentage (for air handling units)
Characteristic • Unit ventilators
• High Close Off • Fan coils
• Large Range of Cv • VAV units
• Cons
• Hot and Chilled Water with
Glycol Only
Globe Valves
Globe Valves
• Linear Action
• Plug Design
Globe Valves
Close-Off Pressure
• Close-Off Rating Determined by Force
Applied to Stem
• Close-Off is Actuator Dependent
Pd
Pu
Globe Valves
3-way Mixing
Globe Valves
3-way Mixing
Globe Valves
3-way Diverting
Globe Valves
3-way Diverting
Globe Valves
Valve Summary
• Pros • Applications
• Equal Percentage or • Hot & chilled water coils
Linear Characteristic (for air handling units)
• SS Trim works for Steam • Chillers
• Cons
• Expensive
• Large
• 2 Versions of 3-way
• Close off depends on
Actuator
Globe Valves
Pu
Pd Pd
Pd
Pu
Pu
Holes in Plate
Balance the
Pressure
Globe Valves
Butterfly Valves
• Rotary Action
• Flow Characteristic:
• Modified Equal Percentage
• Rotating Disc and Resilient Seat
Butterfly Valves
Butterfly Valves
Valve Summary
• Pros • Applications
• Up to 30” • Chiller and Cooling Tower
• Inexpensive Isolation
• High Close-Off • Change Over Systems
• SS and HP Available • Large Air Handlers
• Cons • Bypass Controls
• Modified Eq %
• High Cv Relative to Size
• Velocity Limitations
V-Ball (Segmented Ball Valve)
V-Ball Valves
• For Extreme Conditions
• 400F Water
• 250 PSI Steam
• 150 PSI Close-off
• Controls
• Equal Percent Flow Characteristic
• 300:1 Rangeability
V-Ball (Segmented Ball Valve)
V-Ball Valves
• Rotatory Valve
• Single seat
• Partial Ball reduced torque requirement
V-Ball (Segmented Ball Valve)
Valve Summary
• Pros • Applications
• For extreme applications • Hot & chilled water coils
• High Temp Water (for air handling units)
• High Pressure Steam • Chillers
• High rangeability
• Cons
• Expensive
• Limited sizes and Cv
• Large (heavy)
Zone Valves
Zone Valves
• Inexpensive
• 2 Position
• Spring Return
• “Paddle” Design
Zone Valves
Valve Summary
• Pros • Applications
• Cheap • Baseboards
• Fail Safe • Low Flow needing 2
• Cons position, fail safe
• Cheap
• 2 Position Only
• Low Close-Off
Pressure Independent Valves
Pressure
PI Valve
Flow
Pressure Independent
Technologies
• Pros • Applications
• Accurate Flow Regardless of • Hot & chilled water coils
Pressure Conditions (for air handling units)
• Increased Water-side DT • Unit ventilators
• Reduced Pump Energy • Fan coils
Usage • VAV units
• Valve Authority = 1.0
• Eliminates need of
Automatic Balancing Valves
• Cons
• Higher Initial Cost
Control Valves:
Specifications, Sizing & Technologies
Questions?