Академический Документы
Профессиональный Документы
Культура Документы
Considerations
GRID
Technical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
Breaker Fail Protection Considerations - Agenda
Dependability
• Duplicate:
− Protective Relays
− Trip Coils
− DC Supplies
− Instrument Transformers
• Not Duplicated:
− Circuit Breakers
• Operating Mechanism
• Hydraulic Systems
• Pneumatic Systems
• Objective:
− To Clear the Fault with:
• Minimal time delay
• Minimum disruption to the Power System
Z3A
Z2A
Z1A
A B C
21A 21B
Advantages Disadvantages
• Not affected by local • Slow
station conditions • Sensitivity
• Contributes to both relay • Limited Discrimination
and CB failure protection
Breaker Fail Protection Considerations - P 6
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Remote Backup Protection
R1 R2 R1 I1 I2 R2
I1 I2
I3
21 21
V
V
I
I
Fault
Point Fault Effective
Point Fault
Point
~
~
Why ?
• Advantages
− Faster
− Improved sensitivity
− Minimises network disruption
• Disadvantages
− May be affected by local conditions
− Accidental Operations (“finger trouble”)
• Security
− No unwanted operations
• Dependability
− Guaranteed to operate when required
Breaker Fail Protection Considerations - P 9
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Local Backup Protection
What is it?
CT
AUX. DC CT
SUPPLY
MAIN 1 MAIN 2
PROTECTION PROTECTION
TRIP CIRCUIT
TCS1 SUPERVISION TCS2
RELAYS
TC TC
1 TRIP COILS 2
CIRCUIT
BREAKER
CIRCUIT BREAKER
MECHANISM
Breaker Fail Protection Considerations - P 11
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Local Backup Protection
M2B
TC2B
Circuit Circuit
A B
CT
AUX. DC CT
SUPPLY
MAIN 1 MAIN 2
PROTECTION PROTECTION
Fault
This is the responsibility of the
Intertri
CB Fail protection scheme
p
Breaker Fail Protection Considerations - P 14
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Breaker Fail Protection Considerations - Agenda
2 Setting Of
Timer
Disadvantages of this simple
scheme
86 − Long total fault clearance
times due to long timer
Trip Adjacent setting
Circuits & Intertrip − Security of scheme
− Risk of initiation during
testing causing widespread
Breaker Fail Protection Considerations - P 16 system disruption
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Typical Schemes
52a 2 Setting Of
Timer
Advantage of this scheme is that we
don’t need to consider the main
protection reset time so fault clearance
time is much reduced
86
Disadvantages of this simple scheme
Trip Adjacent − Security of scheme
Circuits & Intertrip − Risk of initiation during testing
causing widespread system
disruption
52a 2 Setting Of
Timer
Additional improvement by
including the CB auxiliary contact
in the back tripping path
− Removes timer overshoot
86
− Increased security of
Trip Adjacent tripping
Circuits & Intertrip
But, consider is it rational or
proper to consider the breaker
status in a CB failure protection
scheme?
Breaker Fail Protection Considerations - P 18
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Typical Schemes
50BF 2 Setting Of
Timer
Advantages of this scheme are:
− 50BF designed for fast reset so
improved total fault clearance
times
86 − Security enhanced by two elements
being required to operate for timer
initiation
Trip Adjacent
Disadvantages of this scheme
Circuits & Intertrip
− 50BF must be set greater than
maximum load current (if security
is to be maintained)
Breaker Fail Protection Considerations - P 19
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Desirable Features
• Sensitive
• Secure
• Dependable
• Fast
• Selective
• Minimise Additional Cabling
Sensitivity
Main 1
•Advantages of 2-stage approach
TC
SV
1 − With lack of use, circuit breakers
Main 2
will become “sticky”
TC
2
− Start verifier, “re-strikes” the trip
coil and may overcome the initial
reluctance of the CB to open
50BF
− First stage may be time-delayed
(if preferred) but will extend
50BF overall fault clearance
SV
52a
•Disadvantages
− Breaker fail timer setting must be
Timer
set longer and overall fault
clearance time is longer
86
• Security
− Duplication with Series connections
− For example, duplicate current detectors & timers
− “AND” logic: 2 out of 2
• Dependability
− Duplication with Parallel connections
− “OR” logic: 1 out of 2
− Cater for single contingency failure
T1B T1A
86
T2B T2A
Unit DC
Supply No 1 T1
+ A
-
T1
B
Unit DC
Supply No 2 T2
+ A
-
T2
Breaker Fail Protection Considerations - P 31 B
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Desirable Features
MI(A) MI(C)
etc.
50BF 50BF 50
(A) (B) BF(C)
50BF 50BF 50BF
T T T
(A)-1 (B)-1 (C)-1
BB BB BB
TR TR
TR
(B) INT
(C) B.B.
(A) INT
(B)
INT Protection
(A)
(C) Buswires
BB RI
R RI C
BB
BF BF
CH BF
(B) (C)
(A)
+ 50BF
50BF 50BF
(A) (B) (C)
50BFT
50BFT 50BFT
(C)
(A) (B)
MTR RTR
RI MI
M RI INT RI INT
M
(A) (B)
I I
BB BB MT RT
TR(A) TR(B) R R
T1B
Main
BF1
2
BF2
Supply 2
+
TC2
TR T2A
Alarm T2B
Supply+ T
B.F.
+ Defective
T1A M R CH T1B 29L
TR
29M T2B 52’a
T2A
’
29R
In this case, the breaker fail timer is completed but the current
check still indicates that the CB is closed. Therefore, a CB Fail
condition is given.
Breaker Fail Protection Considerations - P 46
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Non-Conventional Techniques
In this case, the breaker fail timer is completed and the current
check indicates that the CB is open, even in the presence of the
decaying DC component due to the CB opening.
Breaker Fail Protection Considerations - P 47
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
GRID
Technical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.