Dasherkandi Sewage

Treatment Plant
Project,500MLD
Cable Study
Cable Physical Information
• Power cables for DSTP : 0.6/1 KV LT & 8.7/15 KV HT

• Insulation : XLPE

• Conductor max. operating temp. : 90°C

• Manufacter : Human Valin Wire & Cable Co, Ltd.

& People ELE, Appliance Group Shanghai Ltd.


Cable Insulation
• Cable Insulation Property

• Thermoset, Thermoplastic

• Severe Corrosive Environment Consideration

• Armor material Specification


Exposer Case in
Dasherkandi
• UV Exposer

• Sunlight Exposer

• Chemical Exposer

• Ambient Maximum Temperature Exposer


ADVANTAGES OF XLPE

• Excellent Electrical and Physical Properties


• Excellent Chemical Resistance Property
• Capability of Carrying Large Currents
• Ease of Installation
• Free from Height Limitation and Maintenance
• No Metallic Sheath Required
Examples of installation
methods
Single-core
cables in conduit
in a thermally
insulated wall

Cables on
perforated tray run
horizontally or
vertically
Cables on a
wire mesh
tray

Multi-core cables in
conduit or in cable
ducting in the
ground
Cable Sizing Method

• Ampacity Table

• Actual Sizing Calculation

• Cable Derating Factors Consideration

• Proper Cable Size Selection after Satisfying


Required Conditions
Cable Derating Factors
• Temperature Correction Factor

• Ground Temperature Correction Factor

• Thermal Resistance Correction Factor

• Cable Depth Correction Factor

• Cable Distance correction Factor

• Cable Grouping Factor


Cable Distance correction
Factor
• Case 1 : Groups of one or more circuits of
cables laid directly in the ground

(a) Single-core
cables

(b) Multi-core
chables
• Case 2 : Groups of one or more circuits of cables
laid in ducts in the ground

(a) Single-core
cables

(b) Multi-core
chables
Cable Grouping Factor
• Perforated cable tray systems
Vertical perforated cable tray systems
Unperforated Cable

Tray Systems

• Cable Ladder Systems, Cleats, etc.


Conditions for Proper Cable
Size Selection
• Cable derating amp should be higher than full load
current of load.
• Cable voltage drop should be less than defined voltage
drop.
• No. of cable runs ≥ (Full load current / Cable derating
current).
• Cable short circuit capacity should be higher than
system short circuit capacity at that point.