Академический Документы
Профессиональный Документы
Культура Документы
®úɹ]ÅõMÉ è®ú´É
ÉÉ
No. of GSS= 24
No. of P.H.= 6
Installed =2866.3 MW
capacity
132/220
220 KV LINKAGE
KV T/F BUS TO GRID
132KV
BUS 132/11
KV T/F
132 KV D/C
TR. LINE
11KV
BUS
Generation Evacuation
CT LA
BKR. Power
Transformer
Wave trap
SERIES
Parallel
Ia = Ia1+Ia2+Iao = I1+I2+Io
Ib = Ib1+Ib2+Ibo = a2I1+aI2+Io
Ic = Ic1+Ic2+Ico = aI1+a2I2+Io
TYPE OF FAULTS
V1=V- I1Z1 V2 = 0- I2Z2 V0 = 0- I0Z0
Va=0 Ib=Ic=0
I1=I2=I0 Ia=3I0
Vb=Vc=o
Ia= I1+I2+I0=0
Ia+Ib+Ic=0 I =I =0
2 0
Va=Vb=Vc
EARTH WIRE
LINE
I1 = I2 = I0 = Ia/3
EARTH WIRE
LINE
I1 = - I2 = Ib/√3 = -Ic/√3
EARTH WIRE
LINE
Ia = Ib= Ic
EFFECTS OF FAULT
Loss of system stability.
Loss of life & property.
Interruption of power supply.
Ageing of equipments due to thermal &
dynamic stresses
Rise in temperature.
Earth Potential rise.
Voltage rise of healthy phase.
Mechanical stress.
PROTECTION SCHEME
Fault sensing device .
OR
comparator which operates when
measured value crosses the set
value.
Protection extends tripping
command to circuit breaker for
isolating the fault .
PRIMARY PROTECTION
FUSE
BIMETALLIC STRIP
--
-
Rg
LCM-II Transinor
I3r = I3t – I3p
Z1=100*.4 * .6 *.8
=19.2 Ohms
220 * .577 KV
DC -
110 * .577 V
100 Kms.
SECONDARY Z1=Z2=40
Z0 =160
PROTECTION 1200/1A
DC +
power
0.6
0.4
50 0.2
0
40
time in c/s
20 3Ph.
fault
10
0
0 10 20 30 40 50 60
load angle
PROTECTION SYSTEM
Generator T/F Protection
protection 220 KV LINE
220 KV LINKAGE
BUS TO GRID
LBB
132KV
BUS 132/11
KV T/F
Line protection
132 KV D/C
TR. LINE
11KV
Bus Bar BUS
Protn.
Generation Evacuation
GENERATOR PROTECTION
SYSTEM FAULT:
RESTRAINED O/C
T/F Neutral E/F
OVER LOAD PROT.
Field Failure Neg. Sequence current
GEN. DIFF.
Reverse
Power
INTER TURN
STATOR E /F
REF REF
HV LV
400/1 1200/1
X X X X
X X
Z1
Z3 Z2
X X X X
X X
A B C D
BUS FAULT
BUS BAR PROTECTION
BUS-1
BUS-2
BUS BAR PROTECTION
ZONE-1
BUS BAR PROTECTION
ZONE-1
ZONE-2
+ -
N/O
N/O
N/C
N/O
N/O
N/C
CLOSING
COIL TRIP
COIL
N/O
N/O
N/C
N/C
CIRCUIT BREAKER
CLOSING
COIL TRIP
COIL
N/O
N/O
N/C
N/C
1 29A
BE1 29B1
29AE C1
52
29B 29B2
2 29B
X-wire
52L 29AE
52L 29B
+ 29A -ve
29L 29AE LE
29L
LE C1 29B1
BE1
C2 29L
LE
C2
29AE
SEAL IN(SELF HOLD) OF RELAY
+ -
N/O
N/O
N/C
TRIP CKT. SUPERVISION
PROTECTION REQUIREMENT
SPEED - Minimum damage / PSS
RELIABILITY- must operate when required
SECURITY– REFRAIN when not intended
SELECTIVITY- Discrimination
STABILITY –NO operation under through
fault/ heavy loading
SENSITIVITY- Detection at incipient stage
BACK UP FOR RELAY FAILURE .
BACK UP FOR C.B. FAILURE.
NO BLIND SPOT
RELIABILITY / SECURITY
MORE – R LESS – R MORE – R
LESS - S MORE – S MORE - S
LINE PROT. BBP & LBB
VITAL LINKS OF PROT.SYSTEM
CT / CVT
D.C. SUPPLY
CIRCUIT BREAKER
RELAY
COMMUNICATION
Control wiring
LOCATION OF CT
DP
DP
BBP BBP
Blind
Zone
DP
BBP BBP
DP
Broader Classification
• MAGNITUDE RELAY
Current/voltage relays i.e. Attracted armature,
Induction disc type
• RATIO RELAY
Impedance i.e. Balanced beam type
• DIFFERENTIAL RELAY
% biased, REF, BBP
• DIRECTIONAL RELAY
Mho / reactance , Directional O/C i.e. induction
cup type
GENERAL RELAY EQUATION
Torque= K1I2 – K2V2 + V I cos($ - #) – K3
Current relay : ζ = K1I2 – K3
I = constant
Impedance relay: ζ = K1I2 – K2V2 – K3
Z = constant
Direction relay: ζ = V I cos($ - #) – K3
MHO relay: ζ = – K2V2 + V I cos($ - #) – K3
Z = ZR cos($ - #)
Reactance relay: ζ= K1I2 – VI cos($ - #) –K3
ZR = Z cos(900- #) = Z sin # = X
DIRECTION IMPEDANCE
Op.
#
$
MHO REACTANCE
$
Relays requiring SINGLE quantity for operation
1 Electrical quantity
0 8 5 flowing through coil
wound on magnetic
core produces
mechanical
force/torque.
Ampli
-tude
IAI
PHASE
COMPARATOR
Phase
Relays requiring DOUBLE quantity for operation
AMPLITUDE
Balanced Beam COMPARATOR
v I
PHASE
I COMPARATOR
TMS
1
0 8 5
I
INDUCTION DISC RELAY
MODULE/PCB
CPU
NUMERICAL RELAY
+ START
RL
-
STOP
STATIC CIRCUITORY
+
RL
STOP START
_
NUMERICAL RELAY
STOP
RL
START
Based on COMPARATOR
• AMPLITUDE COMPARATOR
• PHASE COMPARATOR
AMPLITUDE COMPARATOR
ATTRACTED ARMATURE RELAY
measuring element, flag indicators,
monitoring & supervision, tripping,
annunciation, auxiliary and logic functions
F = B2 A / 8 π
A
B
F
Armature travel
TRIP
K1I2=S+K2d/t= K1I02+K2d/t COMMAND
t=K2d/I2 -I02 5000
ms.
10 TMS
8 5
4A +ve - ve
PS
.5 .75 1.0 1.25 1.5 1.75 2.0
AMPLITUDE COMPARATOR
Z
Balanced beam
Impedance
V I
AMPLITUDE COMPARATOR
Compares the magnitude of two or more input quantities
i.e. output can be IAI – IBI or IAI / IBI
Circulating current protection
Inputs – Current entering &
Operating Restraining current leaving protected zone
input-A input -B Impedance relay
Inputs- CT current & PT voltage
Biased differntial relay
Inputs – Differential & biased
current
-- Permanent
moving coil relay
--Sensitive
polarised relay
--Static integrator
PT
Directional
Relay
Io Ir
operates
when Io > Ir -- Permanent
moving coil
relay
--Sensitive
polarised relay
--Static
integrator
Phase
IZ+V
V+IZ
V+IZ
IZ-V
IZ
IZ-V
IZ-V
IZ
V
V
V
<i + <ii = 1800 <i + <ii < 1800 <i+ <ii > 1800
IZr-V
IZr-V IZr-V
30A
Z
MHO MEASURING
ELEMENT +
K2
Mark /space
ratio < 1
V V
IC1 TRIP
Mark /space
ratio > 1
. IC3
Coincidence LEVEL
DETECTOR INTEGRATOR
DETECTOR
IC2
V–IZ
1200
1000
Morkulla
800 Moose
Current
Zebra
600 Goat
Panther
400 Wolf
Dog
200
0
0 10 15 20 30 40 50 60
Ambient Temp
CURRENT RATING OF ACSR CONDUCTORS CORRESPONDING TO MAX.
CONDUCTOR TEMPRATURE OF 67 0C & WIND SPEED 0.61 M/SEC
TYPE 0F SIZE
CAPACITY IN AMPERE (at ambient temp. in 0 C )
CONDUCTOR IN
Sq.
inch
15 20 25 30 35 40 45 50
MORKULLA 0.5 1089 1025 955 880 800 707 600 475
MOOSE 0.5 1050 987 925 855 775 687 587 455
ZEBRA 0.4 925 875 813 755 687 605 518 413
GOAT 0.3 806 763 713 656 587 528 463 363
PANTHER 0.2 613 575 537 500 463 413 350 287
WOLF 0.15 500 475 450 413 375 337 287 237
DOG 0.1 363 350 325 300 275 250 213 175
RELAY INDICATIONS
TYPE MM3V MR3V MM1T RR3V MICRO L3WYS LZ- LZ- SSRR3V RAZO EPAC MICOM BACK UP
OF MM3V MHO / L3S 96 92 MHO A P-442/ IDMT HIGH
FAULT new STAR P430 SET
TER
PHASE-PHASE
R-Y 30A 30(A-B) A-B 30A A,B R,S R,S,D R,S A,B R,S S,AB A,B 51A 50A
Y-B 30B 30(B-C) B-C 30B B,C S,T S,T,D S,T B,C S,T S,BC B,C 51C 50C
B-R 30C 30(C-A) C-A 30C C,A T,R T,R,D R,T C,A T,R S,CA C,A 51A,51C 50A,
50C
PHASE -EARTH
R-E 30D 30A A-N 30D A,N R,E R,D R,E A R,N S,A,N A,N 51A, 50A,
51N 50N
Y-E 30E 30B B-N 30E B,N S,E S,D S,E B S,N S,B,N B,N 51N 50N
B-E 30F 30C C-N 30F C,N T,E T,D T,E B T,N S,C,N C,N 51C, 50C,
51N 51N
Rg
Z1 T2
Z2
Rg
---
T2 Z1
Z2
Rg
Z1 Z1
Z1 Z1
EARTH WIRE
LINE
Philosophy
Even with single component failure fault clearance
time should not exceed 100 ms.
MAIN -1 PROTECTION
Non Switched Distance Protection Scheme .
MAIN - 2 PROTECTION
• Preferably Scheme working on principle other than
distance i.e. phase comparison or differential
principal.
• If distance protection is to be provided ,it should
work on different algorithm or of different make.
MICOM P-442 and MICOM P437 of ALSTOM
MICOM P-442 of ALSTOM and REL-511 of ABB
BACK UP PROTECTION
• Directional IDMT with 2 O/C & 1 E/F
GRID DISTURBANCE ON 6.07.05 at 01:23 Hrs.
1
RIHAND
L 137 57
AGRA
HV DC
815
B 194 kms.
33 kms.
B
Ballabgarh
133
Z3- 50 ohms Moradabad
= 117 Kms.
53
At 02:30:50:684 Hrs.
Muradnagar end breaker
Mandola
112
2.Failure of extension of LBB
Panipat
command to Dadri line bkr.
And failure of direct trip for
840 Th 182 remote
MW
3.Non provision of Back up
RISHIKESH prot. At Dadri end and fault
830 G was beyond Z3 set reach of
395
MW
D.P. scheme
PANKI
MURADNAGAR
DADRI
Setting of back up protection
o/c&
E/F
PS and TMS should be
such that Op. Time >
zone-3 time for almost
bus fault
14
8
TIME
4
TMS =10
10
2
5
0 1
0 5 10 15 20 25
PSM
H.S.=60A
Distance Protection
• Over current protection is based on
measurement of fault current only which is;
susceptible to source impedance & arc
resistance
Slow & no effective grading
• In distance protection Fault coverage is based
on measurement of Impedance or Reactance
of protected line from relay location to fault
point which is:
Virtually independent of source impedance
Fast in operation
Compatible to signalling channel
Non unit protection
Distance Protection
• SWITCHED / NON SWITCHED
• SEQUENCE
Fault detection / Phase selection / Starter /
check
Direction decision
Measurement / Zone decision
• TRIP decision
Check + Direction+ Measurement = TRIP
Switched / nonswitched
• SWITCHED SCHEME :
Single element : SSRR3V, L3WYS, RAZOA
Four elements : LZ96
Single loop : PD-520, MICOM-430
• NON SWITCHED SCHEME:
6 elements : MR3V, MM3V,RR3V,MM3T
12 elements : LZ96,MM3T
18 elements : Micro mho, Quadra mho
Six loops : EPAC,LFZR,MICOM-442/437
SWITCHED SINGLE MEASURING
ELEMENT
V V
Phase
I selector I
NON SWITCHED
V Phase
SIX or MORE
MEASURING ELEMENTS
I selector
V
I
STARTER / FAULT DETECTOR
• Provides check for TRIP logic
• To switch measuring element
• Changing distance steps
• Selection of correct phase for A/R
• To prepare carrier equipment
• Back up to measuring
TYPES OF STARTER
• U/V & O/C
• Under impedance
• MHO
• O/C for Ph-Ph & Residual current for E/F
• V & I
• Negative phase sequence current
• Current and voltage level detectors
U/V & O/C IMPEDANCE
ZONE-2
ZONE-1
R3
ZONE-4
X4
Zk Rb
SHAPED
QUADRILATERAL
b
a
BLINDER
MHO with
LENTICULAR Blinder
DIRECTION Decision
i) Angle between V & I ZR
F
ii) V I = Negative
R
X
POLARISATION
• NEED : correct direction for close up faults
& CVT transient error, fast operation and
expansion of resistive reach
• TYPES
Self polarisation
Cross polarisation (full/partial)
Memory polarisation
TRIP logic for measuring elements
A-N ,B-N ,C-N ,A-B ,B-C ,C-A
Z1
Z2 T2
OR
0 & Trip
T3
Check
Z3
0
Z1=100*.4 * .6 *.8
=19.2 Ohms
220 * .577 KV
DC -
S=A , T = A ,B,C, Z1 110 * .577 V
D= 50.4 kms
Va=39.5V, Vb=64.3,VC=62 100 Kms.
Ia =IN =1.65A, Ib=Ic=0 Z1=Z2=40
Z0 =160
1200/1A
DC +
2
Measuring E/F
element 64
Y2A 86 Y3BX Y3CX
AX
Y1X
30A
Y1X
86AX
30G Zone-1
2-1
Zone-2
30H
2-2 Zone-3
30J
Mark /space
ratio < 1
V V
IC1 TRIP
Mark /space
ratio > 1
. IC3
Coincidence LEVEL
DETECTOR INTEGRATOR
DETECTOR
IC2
V–IZ
B = V - 900
B.A1 B1.A
A.B A1.B1
B.A1 TRIP
B
CONDITION
A = V- IZ
Present Software
Default
settings executn.
set./para
Al/E/F/m
record Battery
backed
EEPROM SRAM Flash P442
EPROM
SRAM
Main & co boards
FRONT LCD CPU comm.
RS232 CPU
PARALLEL PORT
MMI
FPGA SRAM
Main Processor Board
Thresholds used by
IRIG-B protection functions
SIGNAL Processing of
IRIG-B
distance algorithm
CPU
OFC REAR
COMM. PORT Coprocessor Board
Input Board
Watch dog V I
D.C. contact RS485 Digital inputs(16)
Analogue inputs(8)
G(t)
G(t-2T) G(t-T)
Fault Confirmation :
ΔU >0.1Vn or Δ I > 0.2In Phase
Phase Selection :
TRIP Fault
selection
x
Direction
x
confirmation
Sa,Sb,Sc,Sab,Sbc,Sca are derivative of X3 ZONE-3
transition values of currents x
x
Sbc<Sca<Sab , Sbc<<Sca , Sc<Sb<Sa- A x ZONE-2
Sbc<Sca<Sab , Sbc=Sca , Sc<Sb<Sa -AB x
ZONE-1
Start
Fault Direction : X
convergence
ΔV * Δ I < 0 Forward direction R3
ZONE-4
X4
Why ! Numerical relays only
• NUMEROUS ADVANTAGES
Reduced size , reduced wiring, low cost, low burden.
Data processing, double algorithm, multi group settings,
programmable logics, accuracy & speed etc.
Fault location, disturbance & event recording, breaker
condition monitoring and fault recording.
Additional protection functions of IDMT/DTOC, DEF, negative
sequence current, under and over voltage/frequency, CB fail,
broken conductor, CT supervision, loss of load, built in auto
reclosure with synchro check , trip circuit supervision etc.
Measurement of analogue values, digital I/O and logic status.
Local communication through MMI, RS-232 & 485, remote
communication through RS-485, supervisory & control
functions for automation. RTU function and synchronization.
Self diagnostic feature.
Why ! Numerical relays only
The era of protective relays began with electromechanical
relays consist of number of moving parts requiring huge
maintenance. The development of semi conductor devices
gave birth to second generation static relays having very
less moving parts thus demanding lesser maintenance.
The introduction of high speed microprocessor in protection
technology has brought revolution through self supervising
numerical relays because these are highly informative and
communicative with numerous features, provide better
availability & options than electromechanical and static
relays and require almost no maintenance. The numerical
relays will bring complete automation in the system.
Why ! Numerical relays only
In view of down ward trend in the prices of
numerical relays, its numerous advantages
(i.e. mainly fault location, fault recording,
disturbance recording, remote access for
automation & self monitoring, speed,
accuracy, multi options), higher availability
and compact size, the introduction of
numerical relays in the system is growing
exponentially.
Disturbance Recording And Fault Location Equipment:
Under this section, CBIP manual recommends as below:-
Disturbance Recorders:
Disturbance recorders shall be microprocessor based and shall be used to record
also the graphic form of instantaneous values of voltage and current in all three
phases, open delta voltage and neutral current, open or closed positions of relay
contacts and breaker during the system disturbances.
Disturbance recorders are recommended for all the 400 KV lines. At 220 KV level
also they are recommended for all interconnecting lines. In other cases utilities
may decide depending on their need.
The CBPI Manual further recommended that all the disturbance recorders in the
station are synchronized with GPS.
Fault Locators:
Distance to fault locator is recommended to be provided as a standard for all 400 KV
and 220 KV lines on both ends. However, for short lines of length up to 20 KMs, fault
locator can be provided at one end only.
Event Loggers:
The Event logger is used to record the state of Switchyard equipment and relays and
occurrences of alarms. In case all required events can be accommodated in the in-
built disturbance recorder then no separate event logging equipment is
recommended. However if the disturbance recorder and event loggers falls short
than the required one then external to the relays may be provided.
CEA guide lines further recommend the protection for the
transmission lines of the various voltages as under:-
Disturbance Recording And Monitoring:
Unique and unanticipated protection problems can result from the changed system
configuration due to interconnection with the Project. CTU/STU may, at its
discretion, install monitoring equipment to identify possible protection
scheme problems and to provide power quality measurements of the new
configuration. If monitoring or relay performance indicates inadequate
protection of the CTU/STU system, the owner of the Project will be notified of
additional protection requirements. The monitor provides information similar to
that of an oscillograph or fault recorder. The availability of current and voltage
measurements determines the number of channels for the device. Monitoring
equipment is also installed to aid in the understanding of the electrical
phenomena, such as over voltages and ferroresonance that can be associated
with these projects. Remote access to monitor quantities is often accomplished
using the Revenue Metering System (RMS) communication equipment.
Availability Calculation
Electromechanical Failure rate = 2% p.a. A = Uptime * 100
& Static relays Uptime + Mean down time
Test cycle = 1 Year
= 99 years * 100
99Years + 1 Year
= 99 %
GPS
IEC-61850
S/S LAN
PROT. PROT.
PROT.
CTRL. CTRL.
Process bus
600/1
.588 1200/1
1200/1
353A 353
.294
642 642A
.535
289
1/.577 .535
.535A
.241 0 1/.577
.535
REF
.309
350 353 359
.588 .535
642 369 376
.588 .351 A .535
.309
.588 .351A .535
.309
Diff. Relay
MASUREMENT
MHO REACTANCE QUADRILATERAL
Directional Non directional Directional
medium short line short & medium
underreach overreach No prefault load oR/UR
Ra = 28710 * L / If 1.4
L=6.7 M , If =2KA Ra= 5 ohms
L=8M , If =1KA Ra=14.5 ohms
TRIPPING OF 220 KV DHULKOTE-PANIPAT –I ON 06.03.06
Z1 X1
FAULT LOCATION :
LENGTH = 124 KMS.
10.05 + j 11.16 Z1= 2.82 + j11.30
Z2 = 4.5 + j 18.07
18.63 / 760
66KV DKT-CHD – 1 , LENGTH=45 KMS.
X3 ZONE-3
X1=8.24 , R1= 5
ZONE-2
ZONE-1
R3
ZONE-4
X4
0.47+ j 5.3
ZONE-2
ZONE-1
R3
ZONE-4
X4
6.34+ j1.46
RECOMMENDATIONS OF CBIP
Protection Of Transmission Lines:
(CBIP publication manual No. 274 on protection )
i) 400 KV lines :
For 400 KV lines, CBIP Manual has recommended the provision of Main-1, Main-II
and 3rd back up protection in the form of directional earth fault Inverse Definite
Minimum Time (IDMT). 2 stages over voltage protection with provision of 1st stage
as alarm and the 2nd stage for tripping. Single / Three phase auto-reclose has also
been recommended. It has also been mentioned that Main I & Main II both should
be non-switched and the Distance Protection Schemes should have minimum 3
zones. Main I and Main II should preferably be of different types. However, they
may not be of different make.
ii) 220 KV lines:
For 220 KV lines, 2 different protections Main I & Main II with provision of auto-
reclose, suitable for single phase and three phase auto-reclose and the 3rd back up
protection as directional IDMT earth fault relay has been recommended. Main I
have been recommended to be non-switched and it is optional for the utility to
choose Main II as non-switched or switched.
CEA guide lines further recommend the protection for the
transmission lines of the various voltages as under:-
220 KV
Two independent sets of directional line protection shall be installed at each line
terminal to trip the line terminal breakers.
A pilot communication scheme may be required. A scheme common to both relay
sets is acceptable.
Total fault clearing time with a pilot scheme must not be more than four
cycles, including relay and breaker time.
Pilot scheme must be compatible with existing CTU/STU equipment.
Relays shall provide back up protection for loss of communication channel.
BFR protection at the requester’s facilities is required. It must not have more than
eight cycle pickup delay for backup tripping. Total time for BFR scheme fault
clearing must not exceed 14 cycles.
Automatic reclosing for SL-G faults shall be no faster than 35 cycles and no slower
than 60 cycles.
Automatic reclosing is not allowed for multiphase faults.
LINE PROT. TYPES IN BBMB
MM3V MR3V RR3V SSRR3V L3WYS Total
E /Mech.
42 33 8 43 9 135
P40 P10 MM1T MM3T M.MHO Q.MHO OP.MHO PYTS
4 19 13 8 24 8 1 6
TOTAL 366
Basis of operation for Line Protection
Both end breakers Only of faulty line should open in zone-1 time
X X X X
X X
S1
S2
X X X X
X X
A B C D
DIRECTION & REACH
• DIRECTION
Both schemes look towards Bus
Both schemes look towards Line
• ZONE-1 REACH
More than the section
Less than the section
100% of the section
REACH < 100%
ERRORS –
• CT/CVT error
• Line data error
• measuring error
MARGIN – 15-20%
REACH
Zone-2
Zone-1
A B
Zone-1
Zone-2
Setting Criterion
SAFETY MARGIN – 15%
• CT/CVT error
• Line data error
• measuring error
ZONE-1 : cover max. portion of first section
without crossing Bus at remote end.
ZONE-2 : DO not overlap with zone-2 of any
relay at next S/S but ensure coverage of first
section.
ZONE-3 : Cover max. portion of next
longest section without crossing TRF. at
next S/S.
ZONE SETTING
ZONE- 1 : 80 - 85 % OF FIRST SECTION
A B C D
line Parameters
Line Parameters are in p.u. on 100 MVA base
Z2 T2
OR
0 & Trip
T3
Check
Z3
0
CARRIER ACCELERATION
Zone-2
Zone-1
A B
Zone-1
Zone-2
86
F.D./ Z3 off set
Dead pole t
condition 500ms Trip
&
FD
CVT / PT VOLTAGE SUPERVISION
MHO X3 ZONE-3
ZONE-2
ZONE-1
R3
ZONE-4
X4
OP
AFTER FUSE
FAILURE
CVT / PT VOLTAGE SUPERVISION
Prevent unwanted operation of the
comparators due to an open or short circuit
of VT circuitory.
The Distance protection is blocked.
Old practice is to monitor fuses or provide MCB
which is not fool proof.
Neg. Seq. Vol. w/o Neg. Seq. Current for
unbalanced sec. voltage fault. But for 3 phase
fuse missing one of the fuses is monitored.
Even as per latest, all the voltages to relay are
monitored for 3 phase fuses missing.
CVT/PT FUSE FAILURE RELAY
o/c
BLOCKING D.P.
27
SCHEME
CVT / PT VOLTAGE SUPERVISION
D.P.SCHEME
R
B
Vo
Vo
1 Fuse failure
V Blocking
I neg.
CVT / PT VOLTAGE SUPERVISION
Protection functions not blocked
in the event of FAULT
Tc
Vr > 0.7 Vn Confirmed fuse failure
& 0
Protection
S functions blocked
Q in the event of
OPEN LINE FAULT
Io < Sc
R
> >
Distance prot. Blocked
I2 < Sc & Healthy
Imax < Sc network
Power Swing Blocking
Power swings are variations in power flow when voltage of
Generators at different points of power system slips relative to
each other to cater for changed load conditions or faults &
their clearance. Power swing is balanced 3 Phase condition.
Fault is distinguished from power swing on the basis of rate of
change of impedance which is lower in case of power swing
Impedance moves away from load area and passes through
the relay characteristics.
Distance scheme to be blocked for suitable time ” t”
Separate zone for detecting power swing should have
diameter 1.3 times outermost characteristic & time less than
fastest swing.
80ms
MR3V
0.33*Z3
Z3
PSB Z3
t
To Block
tripping
Z6
Z5
BLOCK
Z6 Z1
t
& Z2
inhibition & 0 Z3
Z5
>1
Z6
Z5
BLOCK
Z6 Z1
T
& Z2
inhibition & 0 Z3
Z5
>1
Autoreclosing
95% 0f the faults are temporary i.e. due to
lightning ,tree touching, kite flying, pollution
To reduce outage time & system stability
Autoreclosing
IEC publication 56.2 ,Breaker duty cycle : O- 0.3s-
CO- 3min –CO at full rated breaking current
High/Low speed
Single shot and multi shot
single , three , single and three phase A/R
Dead time : > de-ionising time (De-ionisation time depends
upon arcing time ,fault duration, wind condition, circuit voltage, capacitive
coupling etc.)
Minimum de-energisation time for 66,132, 220 & 400 KV lines are 0.1, 0.17,
0.28, 0.5 sec. respectvely and longer for single phase tripping.
t 1 PH > t 3 PH as Capacitive coupling between healthy phases
maintain arc.
t1Ph recommended 1.0 sec.
Reclaim time recommended 25 sec.
Check syn./Dead line feature
Autoreclosing
Protections which block autoreclose
LBB relay
Line Reactor protection
O/V protection
Direct transfer trip signal received
Bus bar protection
Zone-2/3/4/5/6 of D.P.Scheme
Carrier fail condition
Circuit breaker problems i.e. low air pressure
etc.
---
td td
Z1 A/R A/R Z1
Rg
MUTUAL COMPENSATION
Vr=Ijo(2Z1+Zo) – Iho*Zmo
SO, OVER REACHING
Vg =Ibo(2Z1+Zo) +Iao*ZmoAt
G UNDERREACHING
Vh=Ico(2Z1+Zo) – Iao*Zno
So,at H OVERREACHING
Multiple infeeds
I1 I4
I3
IL I2
IL(ZL+Z+Ra)+( I1+I2+I3)* [( Z1+Z2+Z0) / 3 +Ra ] + I4* Ra
SO , UNDER REACHING
Earth Fault Compensation
RF
I1 I2
ZL1
I1
#
I2
Tee & Multi feed feeders
G
G
Advantages :
• Simple measuring principle.
• Only current transformers are necessary.
• No time delay (fast).
• Strong sensitivity.
Disadvantages :
• Necessary communication link with the opposite
ends.
• No back up protection functions.
Differential Protection
Unit protection for two or multi ended feeders
Phase currents sampled, digitised, filtered and
transmitted in a binary coded form to other ends.
Data samples must be accurately time alligned .
Like conventional differential relay for operation
IDIFF. >K IBIAS & IS
Phase wise differential protection.
Error
CT error
Line charging current error.
OFC link
IN section fault
TRIP TRIP
L.S. L.S.
Out section fault
TRIP
NO NO
TRIP TRIP
L.S. L.S.
Phase comparison scheme
Summation, sequence filter, modulation squarer , transmission ON/OFF for
alternate half cycle ,receiver ,gap detector, discriminator & output bistable.
Fault detectors :
• Impulse (Change): Balanced & unbalanced faults
PPS : HS - 30-60% In LS - 0.5* HS
NPS : HS – 5-20% In LS-0.67* HS
• Non impulse(absolute value) : Unbalanced faults
NPS : HS -1.5-8 times I2 LS-0.67*HS
Dwell times
High Set (HS) : Dwell time= 0.5 S (Enable phase angle measurement)
Low Set (LS) : Dwell time =0.6 S (controls HF transmission)
Marginal guard =100 ms (Through fault stability)
Post trip MG mute =350 ms (Inhibit continuous tr. due to MG )
Modulation Squarer : Compensate for line charging current and
controls the phase angle transmission (7.5 -15% In)
Marginal guard for through fault stability & Post trip marginal guard mute for
Immediate trip in case of internal fault
IN section fault
H.S. H.S.
TRIP TRIP
L.S. L.S.
.
>SET gap >SET gap
& &
OUT section fault
H.S. H.S.
TRIP
NO NO
TRIP TRIP
L.S. L.S.
& &
TRANSFORMER
CONSERVATOR
BUSHING
CORE
OIL
BREATHER
WINDING
TANK
Current at various voltages
Voltage Current in Ampere per
1MVA 10MVA 100MVA
400 KV 1.43 14.3 143
220 KV 2.6 26 260
132 KV 4.375 43.75 437.5
66 KV 8.75 87.5 875
33 KV 17.5 175 1750
11 KV 52.5 525 5250
433 V 1333.7 13337 133370
SKELTON Conductor
TISSUE Cellulose
Blood Oil
BRAIN PROT. SYSTEM
PREVENTION PREVENTION
External :accident, enmity, External : o/v, o/l, o/f, sustained faults
walk/exercise.
Internal :fat , sugar, germs, organ Internal : moisture, oxygen, high temp.
malfunction
DETECTION OF ABNORMALITY AT INCIPIENT STAGE
HEALTH DIAGNOSIS CONDITION MONITORING
Regular check up : Periodical tests :
ECG & BLOOD TEST Electrical tests & OIL TEST
X-Ray FRA, P.D.
DETECTION AT LATER STAGE
BRAIN PROTECTION SYSTEM :
Senses at threshold level Detects at set point
Pain, Fever, Giddiness Insulation failure, Gas, Temperature
TRASFORMER PROTECTION
Differential zone
Differential
element
400/1 1200/1
100MVA , 220/66 KV
262.5A 875A
00 00
Yy0
HV REF ZONE LV REF ZONE
REF REF
HV LV
400/1 1200/1
Circulating current high Only internal earth fault with very high sensitivity to detect earth fault even at
impedance restricted earth fault incipient stage.
Definite time High set overcurrent Stressing of transformer due to prolonged un cleared through faults.
relay.
LBB relay Stressing due to un-cleared electric fault as a result of HV breaker stuck up
Buchholz relay/OSR Gas formation due to internal fault and hot spot etc
Winding temperature trip Over heating due to various reasons associated with load current compensation
Pressure relief device. Excessive gas pressure due to severe internal fault
% BIAS DIFFERENTIAL PROT.
• Low Set
Minimum pick up of differential current
Percentage biasing to compensate for unbalance due
to TAP MISMATCH & CT ERROR
• Magnetizing Inrush blocking
Second harmonic restraint.
By measuring period of small current in each cycle.
• Over flux blocking
Fifth harmonic restraint / by pass
• High Set
Unrestrained instantaneous high set differential
element to ensure faster clearance of internal fault
during magnetizing inrush/ saturated CTs/over
excitation condition
% BIAS DIFFERENTIAL PROT.
1. MISMATCH DUE TO TAP CHANGER
2. CT ERROR
Although not very sensitive
but Detects all type of faults
IO with in differential zone i.e.
between HV & LV CTs
SLOPE
Ip.u.
IF
Magnetic inrush current
FIFTH HARMONIC RESTRAINT
I2 I1
132 /66KV
I2 I1
I1 + I2 = 0
Id = I I1 + I2 I Ib = ( I I1 I + I I2 I ) / 2
FAULT OUTSIDE Differential ZONE
2400 A 4800A
600/1 A 1200/1A
0A
4A 4A
132Kv
66Kv
FAULT INSIDE DIFFERENTIAL ZONE
2400 A 3600A
600/1A 1200/1A
7A
4A 3A
132KV 66Kv
400/1 1200/1
P1
. .
P2 262.5A 875A
.
P2
.
P1
100MVA ,220/66KV
.729
.656
P1 P1
No Fault
.656/.577 P2 P2 .729/.577
S2
S2
S1
DIFFERENTIAL S1
1A 1A
1A 1A
400/1 1200/1
P1
. .
P2 262.5A 875A
.
P2
.
P1
100MVA ,220/66KV
.729
.656
P1 In Zone Fault P1
.656/.577 P2 P2 .729/.577
S2
S2
S1
DIFFERENTIAL S1
1A 1A
1A 1A
NUMERICAL FEATURE
400/1 1200/1
100MVA , 220/66 KV
262.5A 875A
00 00
Yy0
0.656A 00 0.729A 00
Ydy0 1A Ydy0
Differential 1A Software
Software
ICT-1.52 00 element 00 ICT-1.37
VECTOR GROUP
D leading Y by 300
11 12
YD11
12 1
D lagging Y by 300
YD1
T/F CONNECTION – Dyn1
400/1 1200/1
100MVA , 220/66 KV
262.5A 875A
00 -300
Dyn1
0.729A -300
0.656A 00
Yy0 Yd11
1A Differential 1A Software
Software
ICT-1.52 00 element 00 ICT-1.37
T/F CONNECTION – Dd10
400/1 1200/1
100MVA , 220/66 KV
262.5A 875A
00 +600
Dd10
Yd11 1A Yd1
Differential 1A Software
Software
ICT-1.52 300 element 300 ICT-1.37
REF PROTECTION 1200/1
400/1
Is
If
Differential
element
HIGH IMPEDANCE CIRCULATING
CURRENT (REF)PROT.
• Detects only earth fault beteen HV CT &
HV NCT and LV CT & LV NCT
• SENSITIVE THAN % BIASED PROTN.
• REQUIRE identical CTs OF good
characteristics
• Remains stable in the event of CT
saturation during through fault.
FAULT INSIDE HV REF ZONE
300/1 600/1
66/33KV
600/1
300/1
Fault inside LV REF ZONE
300/1 600/1
300A
600/1
300/1
Fault out side REF ZONE
300/1 600/1
300A
600/1
300/1
OVER FLUXING
Transient over fluxing : During load throw off
condition due to transient over voltage transient over
fluxing occurs . The differential relay is restrained for fifth
harmonic .
400/1A
890A
3500A 8.75A
IDMT HS
IDMT
TRF. With HS & TIMER
400/1A
132 / 33KV
20MVA 400/1A
87.5A 350A
96.5 385
110% 100%
trip ALARM
150/1 250/1
250/1
P1 87 .872
.873/.577 P2 P1
S2
P2 .873/.577
REF
S1 S2
Ir-Iy S1
DIFFERENTIAL
1A 1A
Ir-Iy
1A 1A
1A 1A
No Fault
ELECTRICAL TESTS
Electrical tests carried out at site are:-
(i) I.R.Value
(ii) Vector group
(iii) Ratio test
(iv) Magnetizing current
(v) Short circuit current
(vi) Magnetic balance
(vii) Winding resistance
(viii) Capacitance and Tan Delta of
bushings and windings.
OIL TESTS
< 0.1 0 1 0
0.1 TO 1.0 1 0 0 (Code of range of ratios )
1.0 TO 3.0 1 2 1
> 3.0 2 2 2
S.No Characteristic fault C2H2 CH4 C2H4 Diagnosis
. C2H4 H2 C2H6
1. No fault 0 0 0 Normal ageing
2. Partial discharges of low energy 0 1 0 Discahrge in gas filled cavaties resulting from incomplete
density impregnation, or super-saturation or cavitation of high
humadity.
3. Partial discharges of high energy 1 1 0 As above, but leading to tracking or performation of solid
density insulation.
4. Discharges of low energy. 1to 2 0 1 to 2 Continuous sparkling in oil between bad connections of differ-
ent potential or to floating potential break-down of oil between
solid materials.
5. Discharges of high energy 1 0 2 Discharges with power flow through. Arcing breakdown of oil
between winding or coils or between oils to earth. Selector
breaking current.
6. Thermal fault of low temperature 0 0 1 General insulated conductor overheating.
150 C
7. Thermal fault of low temperature 0 2 0 Local overheating of the core due to concentration of flux.
ranging 150 C to 300 C
8 Thermal fault of medium 0 2 1 Increasing hot spot temperature, varying from small
temp.300 C to 700 0C hot spots in core shorting links in core
9 Thermal fault of high temp. 0 2 2 overheating of copper due to oddy currents, bad
contacts/ joints (pyrolitic carbon formation) upto core
700 C
and tank circulating currents.
FURAN ANALYSIS
AS PER S.D. MYERS INC. BASED ON ANALYSIS CARRIED
OUT ON 15000 Trs.
FURAN CONC. IN PPB RECOMMENDATIONS